40
© 2021 Carrier
Screen Saver / Date
Screen settings can be adjusted from this screen.
Brightness: The brightness can be adjusted with a slider.
Screen saver: The screen saver causes the screen to black out – a touch will wake the screen back up. This
feature can be turned on and off as well as the inactivity duration set.
Inactivity log out: The log in level can be set to automatically log out after a specified period of duration.
This feature can be turned on and off as well as the inactivity duration set.
Date: The date and time can be set here. The time will also be written to the connected NXF4000 or
PPC4000.
A common error when connecting to a newer NXF4000 or PPC4000 is that the NXTSD507HD or
NXTSD512HD may be trying to send a date to the control that is outside of the valid range. Newer
NXF4000 and PPC4000 units must have a year that is 2020 or later. This may result in errors that reference
the device name, a parameter number and the message “Invalid Parameter”. If the device is named NXF, an
example of this would be
NXF.2319 Invalid Parameter
. To correct, simply enter the correct date and
time.