background image

16

GENERAL JADE W7220 CONTROLLER AND 

SENSOR INFORMATION

W7220 Economizer

The economizer controller used on electromechanical

units is the Honeywell W7220 which is to be located in the

RTU base unit’s control box. See Fig. 35 for button descrip-

tions of the W7220 controller. The W7220 controller pro-

vides the following:

• 2-line LCD interface screen for setup, configuration, and

troubleshooting.

• On-board fault detection and diagnostics
• Sensor failure loss of communications identification
• Automatic sensor detection
• Capabilities for use with multiple-speed indoor fan systems

Fig. 35 — W7220 Controller

User Interface

The user interface consists of a LCD display and a 4-button

keypad on the front of the economizer controller.

Keypad

The four navigation buttons (see Fig. 35) are used to scroll

through the menus and menu items, select menu items, and

change parameter and configuration settings.

Using the Keypad with Menus

To use the keypad when working with menus:

• Press 

 (Up arrow) button to move to the previous menu.

• Press  the 

 (Down arrow) button to move to the next menu.

• Press the 

 (Enter) button to display the first item in

the currently displayed menu.

• Press the 

 (Menu Up/Exit) button to exit a menu’s

item and return to the list of menus.

Using the Keypad with Settings and Parameters

To use the keypad when working with Setpoints, System

Setup Advanced Settings, Checkout Tests and Alarms:
1. Navigate to the desire menu.
2. Press the 

 (Enter) button to display the first item in

the currently displayed menu.

3. Use the 

 and 

 buttons to scroll to the desired parameter.

4. Press the 

 (Enter) button to display the value of the

currently displayed item.

5. Press the 

 button to increase (change) the displayed

parameter value.

6. Press the 

 button to decrease (change) the displayed

parameter value.

NOTE: When values are displayed, pressing and holding the 

or 

 button causes the display to automatically increment.

7. Press the 

 (Enter) button to accept the displayed value

and store it in nonvolatile RAM.

8. “CHANGE STORED” displays.
9. Press the 

 (Enter) button to return to the current menu

parameter.

10. Press the 

 (Menu Up/Exit) button to return to the pre-

vious menu.

Menu Structure

Table 11 illustrates the complete hierarchy of menus and

parameters for the EconoMi$er X system.

The menus in display order are:

• STATUS
• SETPOINTS
• SYSTEM SETUP
• ADVANCED SETUP
• CHECKOUT
• ALARMS

PROGRAMMING JADE W7220 CONTROLLER

The next several pages detail the different status displays,

setpoints, setup, and alarms available on the controller. This

list below and Table 10 summarizes the inputs required for a

standard application with a single outside air sensor. 
NOTE: Default settings already set in the Jade controller may be

used instead of setting the SETPOINTS; see default settings be-

low. See Table 10 for summarized standard settings or for more

detail see Table 11 — Menu Structure.

Setpoints

• MAT SET: this sets the mixed air temperature (MAT) set-

ting. The controller has a default of 53°F, but the range is

anywhere from 38 to 70°F.

• LOW T LOCK: This setting locks out the compressor (or

mechanical cooling) at a given temperature. The default

is 32°F, but the controller’s range is from -45 to 80°F.

• DRYBULB SET: for an economizer with a dry bulb out-

side air sensor, set the DRYBULB SET. The default set-

ting is 63°F but the controller’s range is 48 to 80°F.

• ENTH CURVE: for a single enthalpy outside air sensor in-

stead of a dry bulb, set the ENTH CURVE setting. There

are 5 setting options: ES1 through ES5. Check the econo-

mizer literature for the limits for each of these settings.

ES3 is the default setting.

• MIN POS: The minimum position allows for ventilation

even when not in the free-cooling mode. A single speed

unit has only one minimum position setting. The default is

4.4 volts, but the range is 2-10Vdc.

• MIN POS H and MIN POS L: A 2 speed unit has 2 mini-

mum position settings that show up on the menu. The first

is MIN POS H (for high speed) which has a default of 4.4

volts. The second is MIN POS L (for low speed), which

has a default of 6.0. Note that MIN POS H and MIN POS

L are only displayed if under SYSTEM SETUP: AUX2 IN

is set to “W1” and FAN TYPE is set to 2 speed.

IMPORTANT: The default setting on the W7220 con-

troller is for a Fan Type” with 2 speed. For a 1 (single)

speed unit, the setting under SYSTEM SETUP > FAN

TYPE must be changed to 1 speed.

Содержание CRECOMZR067A01

Страница 1: ...safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the poten tial for personal injury Understand the signal words DANGER WARNING CAU TION and NOTE The...

Страница 2: ...8 50TC 04 07 CRECOMZR067A01 Large Cabinet 48 50HC 07 12 48 50LC 07 48 50TC 08 14 50HCQ 07 09 50TCQ 08 12 CRECOMZR069A01 Extra Large Cabinet 48 50HC 14 48 50LC 08 12 48 50TC 16 50HCQ 12 50TCQ 14 CRECOM...

Страница 3: ...base in the re turn air chamber See Fig 4 Table 5 EconoMi er X Sensor Usage APPLICATION ECONOMI ER X WITH OUTDOOR AIR DRY BULB SENSOR Accessories Required Outdoor Air Dry Bulb HH79AH001 outdoor air dr...

Страница 4: ...Harness to Unit PL6 Economizer Harness 8 Remove and save the 12 pin jumper plug from the unit economizer harness located in the upper left corner of the unit Insert the EconoMi er X plug into the unit...

Страница 5: ...ee Fig 9 and page 9 Fig 9 Connect 10 pin Plugs Together 13 Connect the 10 pin female plug from the Jade controller harness to ECON on the CTB See Fig 10 and page 9 Fig 10 Connect 10 Pin Jade Plug to C...

Страница 6: ...box and the indoor blower section See Fig 14 Fig 14 Route 48TMHSRSE A20 Harness to Indoor Blower Section Some control box configurations may differ 19 Screw the HH79AH001 mixed air MAT sensor Hon eywe...

Страница 7: ...ween the filters Fig 17 EconoMi er X Hood Assembly Fig 18 Filter Divider on CRECOMZR071A01 Hood 23 Install aluminum filter s in EconoMi er X hood Clips at top of hood will hold filters in place See Fi...

Страница 8: ...2 See base unit installation manual to make adjustments to meet building ventilation requirements See Fig 23 for typi cal EconoMi er X wiring diagram Fig 21 Barometric Relief Flow Capacity Fig 22 Retu...

Страница 9: ...RA ORG YEL BLK BRN RED VIO 1 1 2 2 3 3 4 10 6 4 5 9 1 3 8 2 7 1 2 3 4 5 6 7 8 9 10 4 9 3 8 10 2 6 7 5 1 4 10 Pin Female Plug Disconnected from CTB CO2 Optional Ground W1 on CTB W7220 JADE Controller F...

Страница 10: ...oller NOTE The 4 wire 48TMHSRSE A20 harness provided with the economizer will also NOT be used on the 48 50LC07 12 units see Fig 25 Fig 25 48TMHSRSE A20 Not Used on 48 50LC 07 12 Units 3 Step LC3 The...

Страница 11: ...of Fig 26 on the 48LCHSRADH A00 harness attach to the unit s CSC board Connect J3 and J5 plugs to the CSC board 7 Step LC7 Screw the green wire with yellow stripe in the 48LCHSRADH A00 harness to the...

Страница 12: ...d is 48LCHSRADH A00 harness which is shipped in the control box of 48 50LC 07 12 units and must be field connected to the W7220 controller provided with the economizer 2 Harness attached to the W7220...

Страница 13: ...wires with a plug from the EconoMi er X har ness in the return chamber plug directly into the HH57AC081 enthalpy sensor See Fig 23 and 28 for wiring Fig 29 Enthalpy Curve Boundaries Fig 30 HH57AC081...

Страница 14: ...ive Director At altitudes substantially different than sea level the Fixed Enthalpy limit value shall be set to the enthalpy value at 75 F and 50 rela tive humidity As an example at approximately 6 00...

Страница 15: ...acceptable to some codes is an an nunciator light visible by service personnel See Fig 34 for typical wiring to the Jade controller Refer to codes for proper labeling of light Fig 33 Thermostat Wired...

Страница 16: ...nt menu parameter 10 Press the Menu Up Exit button to return to the pre vious menu Menu Structure Table 11 illustrates the complete hierarchy of menus and parameters for the EconoMi er X system The me...

Страница 17: ...10 Standard Jade W7220 Controller Configuration for 1 or 2 Speed Unit CONTROLLER MENU ITEM FOR SINGLE SPEED UNIT FOR 2 SPEED UNITS NOTE DEFAULT SET TO DEFAULT SET TO SETPOINTS MAT SET 53 F 38 to 70 F...

Страница 18: ...d displays measured discharge temperature Displays_____ if sensor sends invalid value if not connected short or out of range OA TEMP nn F or C 40 to 140 F 40 to 60 C OUTSIDE AIR TEMPERATURE Displays m...

Страница 19: ...t and 2 cool then set for LOW SPEED COOLING ventilation MIN POS M 5 4V 2 to 10 Vdc VENTILATION MINIMUM POSITION AT MEDIUM SPEED Only displays if unit is set for 3 speed with 1 heat and 2 cool and CO2...

Страница 20: ...ON Damper position when freeze protection is active CLO closed MIN MIN POS or VENTMIN CO2 ZERO 0 ppm 0 to 500 ppm increment by 10 CO2 ppm level to match CO2 sensor start level CO2 SPAN 2000 ppm 1000 t...

Страница 21: ...A Positions damper to the fully closed position CONNECT Y1 O N A N A Closes the Y1 O relay Y1 O CONNECT Y2 O N A N A Closes the Y2 O relay Y2 O CONNECT AUX1O N A N A Energizes the AUX1O output If Aux...

Страница 22: ...to Minimum Damper po sition if indoor fan is running or fully closed if fan is off If accessory power exhaust is installed the power exhaust fan motors will be energized by the economizer control as...

Страница 23: ...24 V 24 V 0 V Y2 0 V 0 V 0 V 24 V 0 V W1 0 V 0 V 0 V 0 V 24 V SUPPLY FAN MOTOR SPEED SUPPLY FAN MOTOR SPEED OFF LOW LOW HIGH HIGH DAMPER POSITION No CO2 Sensor CLOSED MIN POS L MIN POS L MIN POS H MI...

Страница 24: ...ls If my enthalpy sensor drifts in accuracy over time can I recalibrate it The sensor cannot be re calibrated in the field however a menu item under the ADVANCED menu allows input of a limited offset...

Отзывы: