W7220 Economizer Module Wiring

Use Tables 12 and 13 to locate the wiring terminals for the

economizer module.

 

Time-out and Screen Saver

When no buttons have been pressed for 10 minutes, the

LCD displays a screen saver, which cycles through the Status

items. Each status item displays in turn and cycles to the next

item after 5 seconds.

START-UP AND OPERATION

Cooling, Unit with EconoMi$er

®

 X

For Occupied mode operation of EconoMi$er X system,

there must be a 24-v signal at terminals R and OCC (provided

through PL6-3 from the unit’s IFC coil). Removing the signal

at OCC places the EconoMi$er X control in Unoccupied

mode. See Table 14 for Damper Position Control.

During Occupied mode operation, indoor fan operation

will be accompanied by economizer dampers moving to Min-

imum Position setpoint for ventilation. If indoor fan is off,

dampers will close. During Unoccupied mode operation,

dampers will remain closed unless a Cooling (by free cool-

ing) or DCV demand is received.

When free cooling using outside air is not available, the

unit cooling sequence will be controlled directly by the space

thermostat. Outside air damper position will be closed or

Minimum Position as determined by Occupancy mode and

fan signal.

When free cooling is available as determined by the appro-

priate changeover command (dry bulb, outdoor enthalpy, dif-

ferential dry bulb or differential enthalpy), a call for cooling

(Y1 closes at the thermostat) will cause the economizer con-

trol to modulate the dampers open and closed to maintain the

unit supply air temperature. Default mixed air temperature is

53°F, with a range of 38°F to 70°F. Compressor will not run.

Should 100% outside air not be capable of satisfying the

space temperature, space temperature will rise until Y2 is

closed. The economizer control will call for compressor oper-

ation. Dampers will modulate to maintain MAT at set point

concurrent with Compressor 1 operation. The “Low T Lock”

setting (default 32°F) will lock out compressor operation

when outside air temperature is below setpoint.

When space temperature demand is satisfied (thermostat

Y1 opens), the dampers will return to Minimum Damper po-

sition if indoor fan is running or fully closed if fan is off.

If accessory power exhaust is installed, the power exhaust

fan motors will be energized by the economizer control as the

dampers open above the EXH1 SET setpoint and will be de-

energized as the dampers close below the EXH1 SET set-

point. (For single speed unit.)

Damper movement from full closed to full open (or vice

versa) will take between 1 

1

/

2

 and 2 

1

/

2

 minutes.

Heating with EconoMi$er

®

 X

During Occupied mode operation, indoor fan operation will

be accompanied by economizer dampers moving to Minimum

Position setpoint for ventilation. If indoor fan is off, dampers

will close. During Unoccupied mode operation, dampers will

remain closed unless a DCV demand is received.

When the room temperature calls for heat (W1 closes), the

heating controls are energized.

Table 12 —  Economizer Module - Left Hand 

Terminal Blocks

LABEL

TYPE

DESCRIPTION

Top Left Terminal Block

MAT

MAT

20k NTC 

and COM

Mixed Air Temperature Sensor (Polarity 

Insensitive Connection)

OAT

OAT

20k NTC 

and COM

Outdoor Air Temperature Sensor 

(Polarity Insensitive Connection)

S-BUS

S-BUS

S-BUS (Sylk 

Bus)

Enthalpy Control Sensor 

(Polarity Insensitive Connection)

Bottom Left Terminal Block

IAQ 2-10

2-10 vdc

Air Quality Sensor Input (e.g. CO

2

 

sensor)

IAQ COM

COM

Air Quality Sensor Common

IAQ 24V

24 vac

Air Quality Sensor 24 vac Source

ACT 2-10

2-10 vdc

Damper Actuator Output (2-10 vdc)

ACT COM

COM

Damper Actuator Output Common

ACT 24v

24 vac

Damper Actuator 24 vac Source

Table 13 — Economizer Module - Right Hand 

Terminal Blocks

LABEL

TYPE

DESCRIPTION

Top Right Terminal Blocks

na

The first terminal is not used.

AUX2 I

24 vac IN

Shut Down (SD) or HEAT (W) 

Conventional only

and

Heat Pump Changeover (O-B) in Heat 

Pump mode.

OCC

24 vac IN

Occupied/Unoccupied Input

E-GND

E-GND

Earth Ground - System Required

EXH1

24 vac OUT Exhaust Fan 1 Output

AUX1 O

24 vac OUT

Programmable:

Exhaust fan 2 output

or

ERV

or

System alarm output

Bottom Right Terminal Blocks

Y2-I

24 vac IN

Y2 in - Cooling Stage 2 Input from 

space thermostat

Y2-O

24 vac OUT Y2 out - Cooling Stage 2 Output to 

stage 2 mechanical cooling

Y1-I

24 vac IN

Y1 in - Cooling Stage 2 Input from 

space thermostat

Y1-O

24 vac OUT Y1 out - Cooling Stage 2 Output to 

stage 2 mechanical cooling

C

COM

24 vac Common

R

24 vac

24 vac Power (hot)

Содержание CRECOMZR067A01

Страница 1: ...safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the poten tial for personal injury Understand the signal words DANGER WARNING CAU TION and NOTE The...

Страница 2: ...8 50TC 04 07 CRECOMZR067A01 Large Cabinet 48 50HC 07 12 48 50LC 07 48 50TC 08 14 50HCQ 07 09 50TCQ 08 12 CRECOMZR069A01 Extra Large Cabinet 48 50HC 14 48 50LC 08 12 48 50TC 16 50HCQ 12 50TCQ 14 CRECOM...

Страница 3: ...base in the re turn air chamber See Fig 4 Table 5 EconoMi er X Sensor Usage APPLICATION ECONOMI ER X WITH OUTDOOR AIR DRY BULB SENSOR Accessories Required Outdoor Air Dry Bulb HH79AH001 outdoor air dr...

Страница 4: ...Harness to Unit PL6 Economizer Harness 8 Remove and save the 12 pin jumper plug from the unit economizer harness located in the upper left corner of the unit Insert the EconoMi er X plug into the unit...

Страница 5: ...ee Fig 9 and page 9 Fig 9 Connect 10 pin Plugs Together 13 Connect the 10 pin female plug from the Jade controller harness to ECON on the CTB See Fig 10 and page 9 Fig 10 Connect 10 Pin Jade Plug to C...

Страница 6: ...box and the indoor blower section See Fig 14 Fig 14 Route 48TMHSRSE A20 Harness to Indoor Blower Section Some control box configurations may differ 19 Screw the HH79AH001 mixed air MAT sensor Hon eywe...

Страница 7: ...ween the filters Fig 17 EconoMi er X Hood Assembly Fig 18 Filter Divider on CRECOMZR071A01 Hood 23 Install aluminum filter s in EconoMi er X hood Clips at top of hood will hold filters in place See Fi...

Страница 8: ...2 See base unit installation manual to make adjustments to meet building ventilation requirements See Fig 23 for typi cal EconoMi er X wiring diagram Fig 21 Barometric Relief Flow Capacity Fig 22 Retu...

Страница 9: ...RA ORG YEL BLK BRN RED VIO 1 1 2 2 3 3 4 10 6 4 5 9 1 3 8 2 7 1 2 3 4 5 6 7 8 9 10 4 9 3 8 10 2 6 7 5 1 4 10 Pin Female Plug Disconnected from CTB CO2 Optional Ground W1 on CTB W7220 JADE Controller F...

Страница 10: ...oller NOTE The 4 wire 48TMHSRSE A20 harness provided with the economizer will also NOT be used on the 48 50LC07 12 units see Fig 25 Fig 25 48TMHSRSE A20 Not Used on 48 50LC 07 12 Units 3 Step LC3 The...

Страница 11: ...of Fig 26 on the 48LCHSRADH A00 harness attach to the unit s CSC board Connect J3 and J5 plugs to the CSC board 7 Step LC7 Screw the green wire with yellow stripe in the 48LCHSRADH A00 harness to the...

Страница 12: ...d is 48LCHSRADH A00 harness which is shipped in the control box of 48 50LC 07 12 units and must be field connected to the W7220 controller provided with the economizer 2 Harness attached to the W7220...

Страница 13: ...wires with a plug from the EconoMi er X har ness in the return chamber plug directly into the HH57AC081 enthalpy sensor See Fig 23 and 28 for wiring Fig 29 Enthalpy Curve Boundaries Fig 30 HH57AC081...

Страница 14: ...ive Director At altitudes substantially different than sea level the Fixed Enthalpy limit value shall be set to the enthalpy value at 75 F and 50 rela tive humidity As an example at approximately 6 00...

Страница 15: ...acceptable to some codes is an an nunciator light visible by service personnel See Fig 34 for typical wiring to the Jade controller Refer to codes for proper labeling of light Fig 33 Thermostat Wired...

Страница 16: ...nt menu parameter 10 Press the Menu Up Exit button to return to the pre vious menu Menu Structure Table 11 illustrates the complete hierarchy of menus and parameters for the EconoMi er X system The me...

Страница 17: ...10 Standard Jade W7220 Controller Configuration for 1 or 2 Speed Unit CONTROLLER MENU ITEM FOR SINGLE SPEED UNIT FOR 2 SPEED UNITS NOTE DEFAULT SET TO DEFAULT SET TO SETPOINTS MAT SET 53 F 38 to 70 F...

Страница 18: ...d displays measured discharge temperature Displays_____ if sensor sends invalid value if not connected short or out of range OA TEMP nn F or C 40 to 140 F 40 to 60 C OUTSIDE AIR TEMPERATURE Displays m...

Страница 19: ...t and 2 cool then set for LOW SPEED COOLING ventilation MIN POS M 5 4V 2 to 10 Vdc VENTILATION MINIMUM POSITION AT MEDIUM SPEED Only displays if unit is set for 3 speed with 1 heat and 2 cool and CO2...

Страница 20: ...ON Damper position when freeze protection is active CLO closed MIN MIN POS or VENTMIN CO2 ZERO 0 ppm 0 to 500 ppm increment by 10 CO2 ppm level to match CO2 sensor start level CO2 SPAN 2000 ppm 1000 t...

Страница 21: ...A Positions damper to the fully closed position CONNECT Y1 O N A N A Closes the Y1 O relay Y1 O CONNECT Y2 O N A N A Closes the Y2 O relay Y2 O CONNECT AUX1O N A N A Energizes the AUX1O output If Aux...

Страница 22: ...to Minimum Damper po sition if indoor fan is running or fully closed if fan is off If accessory power exhaust is installed the power exhaust fan motors will be energized by the economizer control as...

Страница 23: ...24 V 24 V 0 V Y2 0 V 0 V 0 V 24 V 0 V W1 0 V 0 V 0 V 0 V 24 V SUPPLY FAN MOTOR SPEED SUPPLY FAN MOTOR SPEED OFF LOW LOW HIGH HIGH DAMPER POSITION No CO2 Sensor CLOSED MIN POS L MIN POS L MIN POS H MI...

Страница 24: ...ls If my enthalpy sensor drifts in accuracy over time can I recalibrate it The sensor cannot be re calibrated in the field however a menu item under the ADVANCED menu allows input of a limited offset...

Отзывы: