Table 4B — Unit Electrical Data, 30HXA Units (cont)
LEGEND
*Units with one MCA, MOCP, and fuse size value have one terminal block and
require one power supply. Units with two MCA, MOCP, and fuse values have
2 terminal blocks.
†Wye-delta start is standard. Not available in across-the-line start.
NOTES:
1. Main power must be supplied from a field-supplied fused electrical service
with a (factory- or field-installed) disconnect located in sight from the unit.
2. Control circuit power must be supplied from a separate source through a
field-supplied disconnect (except for 380/415-50 units). An accessory con-
trol transformer may be used to provide control circuit power from the main
unit power supply.
3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
5. Use copper conductors only.
6. The MOCP is calculated as follows:
MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse
one size down from the result. The RLAs are listed on the unit nameplate.
7. The recommended fuse size in amps (RFA) is calculated as follows:
RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one
size up from the result. The RLAs are listed on the unit nameplate.
Units have the following power wiring terminal blocks and parallel
conductors:
UNIT
30HXA
UNIT VOLTAGE
POWER CIRCUIT*
CONTROL CIRCUIT
V-Hz
(3 Ph)
Supplied
Power
Supply
Qty
Req’d
No. of
Power
Supply
Conductors
Req’d
MCA
MOCP
ICF
Recommended
Fuse Size
V-Hz
(Single Ph)
Supplied
MCA
and
MOCP
Min
Max
XL
WD
Min
Max
161
230-60
207
253
1
6
605.6
800
†
955.3
700
115-60
104
127
15
208/230-60
187
253
1
6
672.9
1000
†
978.9
800
115-60
104
127
15
460-60
414
506
1
3
304.0
450
1281.6
477.6
350
115-60
104
127
15
575-60
518
633
1
3
242.9
350
1025.1
382.1
300
115-60
104
127
15
380-60
342
418
1
3
368.0
500
1428.0
539.0
450
230-60
207
254
15
380/415-50
342
440
1
6
384.9
500
1398.4
533.4
450
230-50
198
254
15
230-50
207
253
1
6
635.7
800
†
858.3
800
230-50
207
254
15
171
230-60
207
253
1
6
651.5
800
†
1001.2
800
115-60
104
127
15
208/230-60
187
253
1
6
723.9
1000
†
1029.9
1000
115-60
104
127
15
460-60
414
506
1
3
327.0
450
1304.6
500.6
400
115-60
104
127
15
575-60
518
633
1
3
261.4
350
1043.6
400.6
300
115-60
104
127
15
380-60
342
418
1
6
395.9
500
1455.9
566.9
450
230-60
207
254
15
380/415-50
342
440
1
6
413.2
600
1426.7
561.7
500
230-50
198
254
15
230-50
207
253
1
6
682.6
1000
†
905.2
800
230-50
207
254
15
186
230-60
207
253
1
6
707.9
1000
†
1057.6
800
115-60
104
127
15
208/230-60
187
253
2
12
437.0/437.0
700/700
†
43.0/743.
600/600
115-60
104
127
15
460-60
414
506
1
3
355.3
500
1332.9
528.9
400
115-60
104
127
15
575-60
518
633
1
3
284.0
400
1066.2
423.2
350
115-60
104
127
15
380-60
342
418
1
6
430.2
600
1490.2
601.2
500
230-60
207
254
15
380/415-50
342
440
1
6
452.7
600
1466.2
601.2
600
230-50
198
254
15
230-50
207
253
1
6
747.7
1000
†
970.3
1000
230-50
207
254
15
206
230-60
207
253
2
12
468.6/379.8
700/600
—
726.8/743.0
600/500
115-60
104
127
15
208/230-60
187
253
2
12
520.6/422.0
800/700
—
743.0/743.0
600/600
115-60
104
127
15
460-60
414
506
1
6
400.1
500
1377.7
573.7
450
115-60
104
127
15
575-60
518
633
1
3
319.9
400
1102.1
459.1
400
115-60
104
127
15
380-60
342
418
1
6
484.4
600
1544.4
655.4
600
230-60
207
254
15
380/415/50
342
440
1
6
505.2
700
1518.7
653.7
600
230-50
198
254
15
230-50
207
253
2
12
486.0/415.4
700/600
—
771.0/638.0
600/500
230-50
207
254
15
246
230-60
207
253
2
12
592.1/379.8
800/600
—
955.3/743.0
700/500
115-60
104
127
15
208/230-60
187
253
2
12
657.9/422.0
800/700
—
978.9/743.0
800/600
115-60
104
127
15
460-60
414
506
1
6
461.9
600
1439.5
635.5
600
115-60
104
127
15
575-60
518
633
1
3
369.1
450
1151.3
508.3
450
115-60
104
127
15
380-60
342
418
1
6
559.2
700
1619.2
730.2
700
230-60
207
254
15
380/415-50
342
440
1
6
586.1
700
1599.6
734.6
700
230-50
198
254
15
230-50
207
253
2
12
653.7/415.4
800/700
—
858.3/638.0
800/500
230-50
207
254
15
261
230-60
207
253
2
12
638.0/379.8
800/600
—
1001.2/743.0
800/500
115-60
104
127
15
208/230-60
187
253
2
12
708.9/422.0
1000/700
—
1029.9/743.0
800/600
115-60
104
127
15
460-60
414
506
1
6
484.9
600
1462.5
658.5
600
115-60
104
127
15
575-60
518
633
1
6
387.6
500
1169.8
526.8
450
115-60
104
127
15
380-60
342
418
1
6
387.1
700
1647.1
758.1
700
230-60
207
254
15
380/415-50
342
440
1
6
614.4
800
1627.9
762.9
700
230-50
198
254
15
230-50
207
253
2
12
682.6/415.4
1000/700
—
905.2/638.0
800/500
230-50
207
254
15
271
230-60
207
253
2
12
683.6/379.8
800/600
—
1046.8/743.0
800/500
115-60
104
127
15
208/230-60
187
253
2
12
759.6/422.0
1000/700
—
1080.6/743.0
1000/600
115-60
104
127
15
460-60
414
506
1
6
513.2
600
1490.8
686.8
600
115-60
104
127
15
575-60
518
633
1
6
410.2
500
1192.4
549.4
450
115-60
104
127
15
380-60
342
418
1
6
621.4
800
1681.4
792.4
700
230-60
207
254
15
380/415-50
342
440
1
6
653.9
800
1667.4
802.4
800
230-50
198
254
15
230-50
207
253
2
12
747.7/415.4
1000/700
—
970.3/638.0
1000/500
230-50
207
254
15
FLA
—
Full Load Amps
ICF
—
Maximum Instantaneous Current Flow during start-up (the
point in the starting sequence where the sum of the LRA for the
start-up compressor, plus the total RLA for all running com-
pressors, plus the total FLA for all running fan motors is at a
maximum)
LRA
—
Locked Rotor Amps
MCA
—
Minimum Circuit Ampacity (for wire sizing)
MOCP —
Maximum Overcurrent Protection
RLA
—
Rated Load Amps
WD
—
Wye-Delta Start
XL
—
Across-the-Line Start
VOLTAGE
TERMINAL BLOCKS
OR NON-FUSED
DISCONNECTS
CONDUCTORS
208/230
(Sizes 076-171)
1
6
208/230
(Sizes 186-271)
2
6
460
1
3
575
1
3
380
1
3
230 (Sizes 076-171)
1
6
230 (Sizes 186-271)
2
6
380/415
1
3
Содержание ComfortLink 30HXA076
Страница 39: ......