Table 4B — Electrical Data, 30HXA Units
LEGEND
*Units with one MCA, MOCP, and fuse size value have one terminal block and
require one power supply. Units with two MCA, MOCP, and fuse values have
2 terminal blocks.
†Wye-delta start is standard. Not available in across-the-line start.
NOTES:
1. Main power must be supplied from a field-supplied fused electrical service
with a (factory- or field-installed) disconnect located in sight from the unit.
2. Control circuit power must be supplied from a separate source through a
field-supplied disconnect (except for 380/415-50 units). An accessory con-
trol transformer may be used to provide control circuit power from the main
unit power supply.
3. Maximum incoming wire size for each terminal block is 500 kcmil.
4. Maximum allowable phase imbalance is: voltage, 2%; amps, 5%.
5. Use copper conductors only.
6. The MOCP is calculated as follows:
MOCP = (2.25) (largest RLA) + the sum of the other RLAs. Size the fuse
one size down from the result. The RLAs are listed on the unit nameplate.
7. The recommended fuse size in amps (RFA) is calculated as follows:
RFA = (1.50) (largest RLA) + the sum of the other RLAs. Size the fuse one
size up from the result. The RLAs are listed on the unit nameplate.
Units have the following power wiring terminal blocks and parallel
conductors:
UNIT
30HXA
UNIT VOLTAGE
POWER CIRCUIT*
CONTROL CIRCUIT
V-Hz
(3 Ph)
Supplied
Power
Supply
Qty
Req’d
No. of
Power Supply
Conductors
Req’d
MCA
MOCP
ICF
Recommended
Fuse Size
V-Hz
(Single Ph)
Supplied
MCA
and
MOCP
Min
Max
XL
WD
Min
Max
076
230-60
207
253
1
3
291.2
400
†
436.4
350
115-60
104
127
15
208/230-60
187
253
1
3
323.6
450
†
450.8
400
115-60
104
127
15
460-60
414
506
1
3
146.0
200
549.9
217.9
175
115-60
104
127
15
575-60
518
633
1
3
116.8
150
439.9
174.9
150
115-60
104
127
15
380-60
342
418
1
3
177.1
250
614.7
247.7
200
230-60
207
254
15
380/415-50
342
440
1
3
183.4
250
686.5
272.5
225
230-50
198
254
15
230-50
207
253
1
3
303.3
400
†
439.8
350
230-50
207
254
15
086
230-60
207
253
1
3
322.8
450
†
496.4
400
115-60
104
127
15
208/230-60
187
253
1
3
358.7
500
†
510.8
450
115-60
104
127
15
460-60
414
506
1
3
161.9
225
644.9
247.9
200
115-60
104
127
15
575-60
518
633
1
3
129.5
175
535.9
198.9
150
115-60
104
127
15
380-60
342
418
1
3
196.2
250
719.7
281.7
225
230-60
207
254
15
380/415-50
342
440
1
3
205.5
300
796.5
307.5
250
230-50
198
254
15
230-50
207
253
1
3
339.7
500
†
495.8
400
230-50
207
254
15
096
230-60
207
253
1
3
365.4
500
†
562.4
450
115-60
104
127
15
208/230-60
187
253
1
6
406.1
600
†
576.8
500
115-60
104
127
15
460-60
414
506
1
3
183.4
250
749.9
280.9
225
115-60
104
127
15
575-60
518
633
1
3
146.5
200
599.9
224.9
175
115.60
104
127
15
380-60
342
418
1
3
221.1
300
835.7
317.7
300
230-60
207
254
15
380/415-50
342
440
1
3
231.4
350
937.5
351.5
300
230-50
198
254
15
230-50
207
253
1
6
382.6
500
†
566.8
450
230-50
207
254
15
106
230-60
207
253
1
6
416.9
600
†
647.4
500
115-60
104
127
15
208/230-60
187
253
1
6
463.2
700
†
661.8
600
115-60
104
127
15
460-60
414
506
1
3
209.2
300
884.9
323.9
250
115-60
104
127
15
575-60
518
633
1
3
167.2
250
707.9
258.9
200
115-60
104
127
15
380-60
342
418
1
3
253.3
350
984.7
364.7
300
230-60
207
254
15
380/415-50
342
440
1
3
263.3
400
1041.5
384.5
300
230-50
198
254
15
230-50
207
253
1
6
435.1
600
†
619.8
500
230-50
207
254
15
116
230-60
207
253
1
6
442.1
600
†
672.7
500
115-60
104
127
15
208/230-60
187
253
1
6
491.3
700
†
689.9
600
115-60
104
127
15
460-60
414
506
1
3
221.9
300
897.6
336.6
300
115-60
104
127
15
575-60
518
633
1
3
177.4
250
718.1
269.1
225
115-60
104
127
15
380-60
342
418
1
3
268.6
400
1000.0
380.0
350
230-60
207
254
15
380/415-50
342
440
1
3
281.0
400
1059.2
402.2
350
230-50
198
254
15
230-50
207
253
1
6
464.2
700
†
648.9
600
230-50
207
254
15
126
230-60
207
253
1
6
476.3
700
†
706.8
600
115-60
104
127
15
208/230-60
187
253
1
6
529.2
700
†
727.8
600
115-60
104
127
15
460-60
414
506
1
3
239.1
350
914.8
353.8
300
115-60
104
127
15
575-60
518
633
1
3
191.0
250
731.7
282.7
225
115-60
104
127
15
380-60
342
418
1
3
289.3
400
1020.7
400.7
350
230-60
207
254
15
380/415-50
342
440
1
3
301.7
400
1079.9
422.9
350
230-50
198
254
15
230-50
207
253
1
6
498.5
700
†
683.2
600
230-50
207
254
15
136
230-60
207
253
1
6
539.1
800
†
769.8
700
115-60
104
127
15
208/230-60
187
253
1
6
599.1
800
†
790.8
700
115-60
104
127
15
460-60
414
506
1
3
270.7
400
1014.8
385.8
350
115-60
104
127
15
575-60
518
633
1
3
216.2
300
811.7
308.7
250
115-60
104
127
15
380-60
342
418
1
3
327.5
450
1131.7
435.7
400
230-60
207
254
15
380/415-50
342
440
1
3
343.4
500
1345.9
506.9
300
230-50
198
254
15
230-50
207
253
1
6
567.3
800
†
817.2
700
230-50
207
254
15
146
230-60
207
253
1
6
580.3
800
†
811.0
700
115-60
104
127
15
208/230-60
187
253
1
6
644.8
800
†
836.5
800
115-60
104
127
15
460-60
414
506
1
3
291.3
400
1035.4
406.4
350
115-60
104
127
15
575-60
518
633
1
3
232.7
300
828.2
325.2
300
115-60
104
127
15
380-60
342
418
1
3
352.5
500
1156.7
460.7
400
230-60
207
254
15
380/415-50
342
440
1
3
358.9
500
1371.4
532.4
450
230-50
198
254
15
230-50
207
253
1
6
609.3
800
†
859.2
700
230-50
207
254
15
FLA
—
Full Load Amps
ICF
—
Maximum Instantaneous Current Flow during start-up (the
point in the starting sequence where the sum of the LRA for the
start-up compressor, plus the total RLA for all running com-
pressors, plus the total FLA for all running fan motors is at a
maximum)
LRA
—
Locked Rotor Amps
MCA
—
Minimum Circuit Ampacity (for wire sizing)
MOCP —
Maximum Overcurrent Protection
RLA
—
Rated Load Amps
WD
—
Wye-Delta Start
XL
—
Across-the-Line Start
VOLTAGE
TERMINAL BLOCKS
OR NON-FUSED
DISCONNECTS
CONDUCTORS
208/230
(Sizes 076-171)
1
6
208/230
(Sizes 186-271)
2
6
460
1
3
575
1
3
380
1
3
230 (Sizes 076-171)
1
6
230 (Sizes 186-271)
2
6
380/415
1
3