Optical smoke alarm device
Commercial reference: 2106-008
Developed by CAVIUS
The smoke alarm is designed for private homes.
SAFETY INSTRUCTIONS:
The device comes with a 3V lithium battery.
Bat-teries are to be handled with care and battery
pow-ered devices should be kept out of reach of
chil-dren. Do not try to recharge or burn the bat-
teries.
TECHNICAL INFORMATION:
The maximum number of alarms that can be inter-
linked within a house group are 32.
Please note: These must be alarms from the CAVIUS
The distance between interlinked alarms depends
on the house layout and they should always be
tested after installation. It is not advised to get
more than 10m distance between two smoke
alarms.
Diameter: 78mm. Height: 44mm
The alarm is powered by a non-replaceable 10
year battery (pack of 2 CR123A Lithium batteries).
In normal situations, minimum battery life is 10
years, but severe RF interferences may affect
battery life of your device.
Certified to EN 14604 : 2005 + AC2008 , EN 3000-
220
1. HOW TO SET UP AND CONNECT ALARMS:
Please note: The product label must not be
removed as it contains important information
regarding the product.
All alarms that need to be connected in the
house should be put into ‘Learn Mode’ by sliding
the switch on the back of the alarm to the ‘Learn
Mode’ position.
The red LED will light up to indicate that ‘Learn
Mode’ has been selected.
Please note that when the alarms are placed
in ‘Learn Mode’ they can’t be inserted into the
mounting base.
Press and hold the test button at one alarm only,
until it beeps and the LED flashes. This alarm
will send out a specific house code to the other
alarms.
As the other alarms receive the specific house
code, they will also flash the LED light.
When the red LED light flashes on all alarms,
they are connected and MUST BE SWITCHED
OUT OF ‘LEARN MODE’ and installed.
Label the original “Learn” alarm in order to easily
add new Cavius Wireless Family alarms to the
system.
2. THE BEST AREAS TO INSTALL THE SMOKE
ALARM:
• Install an alarm between possible fire sources
and bedrooms as a minimum.
• Install alarms on each floor of the house, in hall-
ways and stairways.
• Alarms in each room such as bed rooms and
living rooms. Additional alarms increase the se-
curity.
3. AREAS WHERE NOT TO INSTALL SMOKE-
ALARMS:
• In dusty rooms.
• At the top of a high pointed ceiling, in ceiling
corners, and within 30cm of a wall.
• In rooms where the temperature goes out side
+4
o
to 38
o
C or above 90% relative humidity not
condensing.
• In kitchens, garages, laundries, or too close to
fireplaces; areas where either dampness, gases
or smoke could occur.
Place the alarm where it is reachable in order to
test the battery and for maintenance.
4. PLACEMENT:
Centrally located ceiling mounted is preferred but
if must fit on a wall please consider the following:
For ceiling installation:
The smoke alarm should be a minimum of 30cm
from the wall.
For catheral or peak ceiling or wall installation:
With a minimum of one smoke alarm per floor and
a maximum distance between smoke alarms of
10 meters.
5. INSTALLING THE SMOKE ALARM:
Detach the alarm from the mounting base by
twisting counter clockwise.
MOUNTING
BASE
CHAMBER
FILTER
TEST BUTTON
RED LED
UK
Peak ceiling
Minimum 50cm
from peak
Minimum 30cm and
maximum 50cm from
ceiling
Wall
Ceiling
Minimum30cm
from wall
Wall
Ceiling
LEARN MODE
NORMAL MODE
MARK UP
SCREW HOLES
WITH A PEN
Optical
Siting of Optical Smoke alarms
PLEASE READ THE INSTALLATION GUIDE
CAREFULLY BEFORE INSTALLATION AND
RETAIN FOR FUTURE USE.