APPENDIX A - CONTROL MODULE
User Interface Display
Explanation
CH Settings
C H
S E T T I N G S
▲
B o o s t
F u n c t i o n
T e m p
1 0 ° F
T i m e
2 0 m i n
▼
Outdoor reset boost function increases CH set point by
increment (‘Temp’) if CH demand continues beyond pre-set
time limit (‘Time’).
CH set point will continue to increase until set point reaches
195°F / 91°C
Allowable Temperature Increment: 0..36 °F (0..20 °C)
Default Temperature increment: 0 °F (10 °C)
Allowable Time Delay: 1..120 minutes
Default Time Delay: 20 minutes
C H
S E T T I N G S
▲
M a x i m u m P o w e r
C H
M a x
1 0 0 %
▼
Maximum boiler power in CH mode limited by adjusting
‘Maximum Power CH’ setting. Boiler will not exceed this
value while operating in CH Mode.
Allowable Range: 1..100%
Default Setting: 100%
DHW Settings
D H W
S E T T I N G S
D H W m o d e
M O D E : 1
D H W
s t o r e w i t h
s e n s o r
▼
Two DHW modes are available
• DHW Mode = 0 ‘No DHW
• DHW Mode is disabled
• The DHW thermostat input is ignored and the DHW
pump is not used.
• DHW Mode = 2 ‘DHW Store with Thermostat’
• Boiler reacts to DHW demand when DHW thermostat
input closes.
• Boiler modulates to meet DHW demand similar to CH
Mode except DHW set point is used. DHW set point set
in Settings’ submenu found in 'User Menu’.
• Simultaneous CH & DHW demands handled using DHW
Priority Timing. See ‘DHW Maximum Priority Time’
setting below.
Note:
• Outdoor reset function disabled while operating in DHW
Mode.
• Typical when using a DHW indirect storage tank.
• After DHW demand satisfi ed, boiler enters post purge
mode and DHW pump continues to run for 15 seconds.
0
Содержание BWMAAN000050
Страница 46: ...46 13 TROUBLE SHOOTING ...
Страница 48: ...48 13 TROUBLE SHOOTING ...
Страница 53: ...53 14 WIRING DIAGRAM 14 1 Connection Diagram ...
Страница 54: ...54 14 WIRING DIAGRAM 14 2 Schematic Diagram of Ladder Form ...
Страница 60: ...60 APPENDIX A CONTROL MODULE ...
Страница 61: ...61 APPENDIX A CONTROL MODULE ...
Страница 64: ...64 APPENDIX A CONTROL MODULE ...
Страница 70: ...70 NOTES ...
Страница 71: ...71 Date Service Performed Company Name Tech Initials Company Address Phone ...
Страница 72: ...CAC BDP 7310 West Morris St Indianapolis IN 48231 ...