14.3 - Accessory 00PPG000488200- Heating System Manager type C
Heating system control (as accessory 00PPG000488100-) with
the possibility to obtain additional heating and domestic hot-
water production capacity from a district heating system
Allows control of a non-reversible heating system that includes a
61AF heat pump and two different heat emitter types and/or two
independent comfort zones. For optimised energy efficiency the
heat pump is controlled by a configurable weather compensation
system.
The control box controls the heating and/or domestic hot-water
production support from a district heating system. The control box
supplies power to the circulating pumps. Hot-water production can
be permanent or programmable with a second setpoint at the heat
pump and control of a switching valve.
Heating system example: with the possibility to obtain additional heating and domestic hot-water
productioncapacity from a district heating system
GT1
GT4 P4 SV34
SV31
P2
P7
P1
GT5
P5
SV35
GT7
GT2
GT7:2
SV21
SV27
SV32
GT1:4
GT1:3
GT3
GT..
P..
SV..
61AF + HSM
Heating system
Floor heating
Domestic hot
water in
Hot water
Legend
Thermistors
GT1
Water temperature loop 1
GT1:3
Heat exchanger leaving water temperature, district heating
GT1:4
Heat exchanger entering water temperature, district heating
GT2
Domestic hot water tank temperature
GT3
Outdoor air temperature
GT4
Water temperature loop 2
GT5
Domestic hot water temperature
GT7
Additional domestic hot water tank temperature
GT7:2
Back-up heat exchanger temperature for domestic hot water
Pompes
P1
Pump for water loop 1 (radiators)
P2
External water pump for the heat pump
P4
Pump for water loop 2 (floor heating)
P5
Pump to pre-heat the domestic hot water valve loop
P7
Pump for domestic hot water circulation
Vannes
SV21
Valve for district heating heat exchanger for heating
SV27
Valve for district heating heat exchanger for domestic hot water
SV31
Three-way mixing valve for the back-up heater
SV32
Heating/domestic hot water change-over valve
SV34
Three-way control valve for water loop 2
SV35
Three-way mixing valve for domestic hot water
14 - HEATING SYSTEM MANAGER (HSM)
Содержание AquaSnap 61AF 022