4 - PHYSICAL AND ELECTRICAL DATA
4.2 - Electrical data
61XWHLZE / 61XWH-ZE
Model
3
5
7
10
14
15
17
Power circuit
Nom. power supply
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit
24 V via the built-in transformer
Maximum start-up current - Standard unit
(1)
Circuit A
A
1210
1828
1919
1828
1919
1919
1919
Circuit B
A
-
-
-
1828
1919
1919
1919
Option 81
A
-
-
-
2158
2425
2425
2407
Maximum start-up current - Star/delta start option
(2)
Circuit A
A
388
587
-
587
-
-
-
Circuit B
A
-
-
-
587
-
-
-
Transient (< 150ms)
A
1210
1828
-
1828
-
-
-
Option 81
A
-
-
-
943
-
-
-
Transient (< 150ms)
A
-
-
-
2158
-
-
-
Cosine phi
Nominal
0,70
0,80
0,81
0,80
0,81
0,81
0,83
Maximum
(2)
0,89
0,89
0,89
0,89
0,89
0,89
0,89
Total harmonic distortion
(2)
%
Closed to 0% (negligible)
Maximum power input
(3)
Circuit A
kW
137
203
312
203
312
312
301
Circuit B
kW
-
-
-
203
312
312
301
Option 81
kW
-
-
-
406
624
624
602
Maximum current drawn (Un)
(3)
Circuit A
A
222
330
506
330
506
506
488
Circuit B
A
-
-
-
330
506
506
488
Option 81
A
-
-
-
660
1012
1012
976
Maximum current drawn (Un -10%)
(2)
Circuit A
A
240
356
546
356
546
546
527
Circuit B
A
-
-
-
356
546
546
527
Option 81
A
-
-
-
712
1092
1092
1054
61XWHHZE
Model
3
5
7
10
14
15
17
Maximum start-up current - Standard unit
(1)
Circuit A
A
1210
1828
1919
1828
-
1919
-
Circuit B
A
-
-
-
1828
-
1919
-
Option 81
A
-
-
-
2188
-
-
-
Maximum start-up current - Star/delta start option
(2)
Circuit A
A
388
587
-
587
-
-
-
Circuit B
A
-
-
-
587
-
-
-
Transient (< 150ms)
A
1210
1828
-
1828
-
-
-
Option 81
A
-
-
-
947
-
-
-
Transient (< 150ms)
A
-
-
-
2188
-
-
-
Maximum power input
(3)
Circuit A
kW
148
220
334
222
-
334
-
Circuit B
kW
-
-
-
222
-
334
-
Option 81
kW
-
-
-
444
-
-
-
Maximum current drawn (Un)
(3)
Circuit A
A
241
360
543
360
-
543
-
Circuit B
A
-
-
-
360
-
543
-
Option 81
A
-
-
-
720
-
-
-
Maximum current drawn (Un -10%)
(2)
Circuit A
A
260
389
586
389
-
586
-
Circuit B
A
-
-
-
389
-
586
-
Option 81
A
-
-
-
778
-
-
-
(1) Instantaneous start-up current for delta connection (maximum operating current of the smallest compressor(s) + locked rotor current or reduced start-up current of the
largest
compressor).
(2) Both Max start-up current and transient peak to be considered for installation
(3) Values obtained at operation with maximum unit power input.
(4) Values obtained at operation with maximum unit power input. Values given on the unit name plate.