23
9 - HIGH CONDENSING OPTION (OPTION 150)
9.1 -
Physical data, units with option 150
30XW-PZE / 30XWHPZE
301
401
451
551
601
651
801
901
1001
1101
Sound levels - unit with option 150
Sound power level
(1)
dB(A)
93
97
97
100
100
100
100
100
103
103
Sound pressure level at 1 m
(2)
dB(A)
76
80
80
82
82
82
81
81
84
84
Sound levels - standard unit + option 257
(3)
Sound power level
(1)
dB(A)
-
94
94
98
98
98
97
97
101
101
Sound pressure level at 1 m
(2)
dB(A)
-
76
76
80
80
80
78
78
82
82
Dimensions - unit with option 150
Length
mm
2724
3059
3059
3290
3290
3290
4730
4730
4730
4730
Width
mm
928
936
936
1105
1105
1105
1039
1039
1202
1202
Height
mm
1567
1743
1743
1970
1970
1970
1997
1997
2071
2071
Operating weight
(4)
kg
2157
3050
3050
4102
4147
4175
6932
7010
7844
8182
Compressors
Semi-hermetic 06T screw compressors, 50 r/s
Circuit A
-
1
1
1
1
1
1
1
1
1
1
Circuit B
-
-
-
-
-
-
-
1
1
1
1
Refrigerant - unit with option 150
R-1234ze(E)
Circuit A
kg
78
130
130
180
175
170
120
120
130
130
teq CO
2
0,5
0,9
0,9
1,3
1,2
1,2
0,8
0,8
0,9
0,9
Circuit B
kg
-
-
-
-
-
-
120
120
150
130
teq CO
2
-
-
-
-
-
-
0,8
0,8
1,1
0,9
Refrigerant - unit with option 150 and option 330
R-515B
Circuit A
kg
79
132
132
183
178
173
122
122
132
132
teq CO
2
23,1
38,7
38,7
53,6
52,2
50,7
35,7
35,7
38,7
38,7
Circuit B
kg
-
-
-
-
-
-
122
122
152
132
teq CO
2
-
-
-
-
-
-
35,7
35,7
44,5
38,7
Oil - unit with option 150
Circuit A
l
20
20
20
25
25
25
20
20
25
25
Circuit B
l
-
-
-
-
-
-
20
20
20
25
Capacity control
SmartVu
TM
, electronic expansion valves (EXV)
Minimum capcity
%
30
30
30
20
20
25
15
15
15
10
Evaporator
Multi-pipe flooded type
Water volume
l
61
101
101
154
154
154
293
293
321
321
Water connections (Victaulic)
in
5
6
6
8
8
8
8
8
8
8
Drain and vent connections (NPT)
in
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Max. water-side operating pressure
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
Condenser
Multi-pipe flooded type
Water volume
l
55
103
103
148
148
148
316
316
340
340
Water connections (Victaulic)
in
5
6
6
8
8
8
8
8
10
10
Drain and vent connections (NPT)
in
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Max. water-side operating pressure
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
(1) In dB ref=10
-12
W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
For information, calculated from the sound power level Lw(A).
(3) Option 257 = Low noise level.
(4) Weight shown is guideline only. Please refer to the unit nameplate.