50
Operating Limitations
TEMPERATURES
Unit operating temperature limits are listed in the table below.
LEGEND
* Lowest allowable ambient temperature for the standard unit to start
and operate is 32°F (0°C). With the inclusion of wind baffles and vari-
able speed fans (field fabricated and installed), the unit is capable to
start as low as 0°F (–17.8°C) and to operate as low as –20°F (–29°C)
ambient temperature.
† For sustained operation, EWT should not exceed 70°F (21.1°C).
** Unit requires brine fluid for operation below this temperature.
Low Ambient Temperature Operation
If unit operating temperatures below 32°F (0°C) are expected,
the following measures are recommended:
• Consider higher loop volumes, 6 to 10 gallons per nominal ton.
• Loop freeze protection with glycol is strongly recommend-
ed to a minimum of 15°F (8.3°C) below lowest anticipated
ambient temperature.
• Chilled water pump control is required.
• If wind velocity is expected to be greater than 5 mph
(8 km/h) wind baffles and brackets must be field fabricated
and installed. See the 30XV Installation Instructions for
more information.
VOLTAGE
Main Power Supply
Minimum and maximum acceptable supply voltages are listed
in the Installation Instructions.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance between
phases is greater than 2%.
To determine percent voltage imbalance:
The maximum voltage deviation is the largest difference be-
tween a voltage measurement across 2 legs and the average
across all 3 legs.
Example: Supply voltage is 240-3-60.
AB = 243v
BC = 236v
AC = 238v
Corner Grounded Delta Supply
The Compressor and Fan VFDs used on 30XV units are automati-
cally compatible with a Corner Grounded Delta Power Supply to
the system. No changes are required to be made to the VFDs.
1. Determine average voltage:
2. Determine maximum deviation from average voltage:
(AB) 243 – 239 = 4 v
(BC) 239 – 236 = 3 v
(AC) 239 – 238 = 1 v
Maximum deviation is 4 v.
8. Determine percent voltage imbalance:
This voltage imbalance is satisfactory as it is below the
maximum allowable of 2%.
MINIMUM FLUID LOOP VOLUME
To obtain proper temperature control, loop fluid volume must be
at least 3 gallons per ton (3.25 L per kW) of chiller nominal ca-
pacity for air conditioning and at least 6 gallons per ton (6.5 L
per kW) for process applications or systems that must operate at
low ambient temperatures (below 32°F [0°C]). Refer to applica-
tion information in Product Data literature for details.
FLOW RATE REQUIREMENTS
Standard chillers should be applied with nominal flow rates
within those listed in the Minimum and Maximum Evaporator
Flow Rates table. Higher or lower flow rates are permissible to
obtain lower or higher temperature rises. Minimum flow rates
must be exceeded to assure turbulent flow and proper heat
transfer in the evaporator. See Tables 33 and 34. See Fig. 45-50
for evaporator pressure drop curves.
Consult application data section in the Product Data literature
and job design requirements to determine flow rate require-
ments for a particular installation.
TEMPERATURE
F
C
Maximum Ambient Temperature
125
52
Minimum Ambient Temperature*
32
0
Maximum Evaporator EWT†
95
35
Maximum Evaporator LWT
60
15
Minimum Evaporator LWT
38**
3.3
Maximum Evaporator Glycol EWT†
95
35
Minimum Evaporator Glycol LWT
30
16.7
EWT —
Entering Fluid (Water) Temperature
LWT —
Leaving Fluid (Water) Temperature
% Voltage Imbalance = 100 x max voltage deviation from avg voltage
average voltage
Average voltage
=
243+236+238
3
= 717
3
= 239
% Voltage Imbalance = 100 x
4
239
=
1.7%
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact the local electric utility company
immediately. Do not operate unit until imbalance condition
is corrected.
CAUTION
Operation below minimum flow rate could generate alarms,
which could result in damage to the evaporator.
Содержание AquaForce 30XV140
Страница 79: ...79 Fig 76 VFD Communication Wiring Compressor A B Fan VFD A1 A2 B1 B2...
Страница 82: ...82 Fig 81 VFD Compressor Locations 30XV225 325 30XV350 500 30XV140 325 COMPRESSOR A VFD COMPRESSOR B VFD...
Страница 228: ...228 Fig 90 30XV Typical Field Wiring Schematic cont...
Страница 229: ...229 Fig 91 30XV Standard Tier 140 275 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 230: ...230 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 231: ...231 Fig 92 30XV Standard Tier 300 325 All Voltages Power Schematic cont NOTE See Legend on page 226...
Страница 232: ...232 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 233: ...233 Fig 93 30XV Standard Tier 350 500 380 400 415 440 460 575v Power Schematic cont NOTE See Legend on page 226...
Страница 234: ...234 Fig 94 30XV High Tier 350 450 All Voltages Mid Tier 350 500 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 235: ...235 Fig 95 30XV Mid Tier 140 All Voltages 160 275 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 236: ...236 Fig 96 30XV High Tier 140 200 380 400 415 440 460 575v Power Schematic NOTE See Legend on page 226...
Страница 237: ...237 Fig 97 30XV High Tier 140 200 208 230v Mid Tier 160 200 208 230v Power Schematic NOTE See Legend on page 226...
Страница 238: ...238 Fig 98 30XV High Tier 225 325 All Voltages Mid Tier 300 325 All Voltages Power Schematic NOTE See Legend on page 226...
Страница 240: ...240 Fig 99 30XV Communication Wiring...
Страница 241: ...241 Fig 100 30XV 115V Control Wiring All Tonnages All Voltages...
Страница 242: ...242 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages...
Страница 243: ...243 Fig 101 30XV 24V Control Wiring 30XV140 325 All Voltages cont...
Страница 244: ...244 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages...
Страница 245: ...245 Fig 102 30XV 24V Control Wiring 30XV350 500 All Voltages cont...
Страница 246: ...246 Fig 103 Component Arrangement Diagram for 30XV140 325...
Страница 247: ...247 Fig 103 Component Arrangement Diagram for 30XV140 325 cont...
Страница 248: ...248 Fig 104 Component Arrangement Diagram for 30XV350 500...
Страница 337: ...337 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig L System Information...
Страница 338: ...338 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig M Unit and Language Settings...
Страница 339: ...339 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig N Hand Off Auto This is set in Auto mode for sensorless operation...
Страница 341: ...341 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig P Data Input 2...
Страница 342: ...342 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig Q Data Input 3...
Страница 347: ...347 APPENDIX J FACTORY SUPPLIED PUMPS cont Fig U Pump Wiring Diagram...