45
30XB
1100
1200
1300
1400
1500
1550
1700
Maximum current (Un-10%)
(1)
- 30XB
Standard unit
Circuit 1
(a)
A
341
390
474
506
538
780
633
Circuit 2
(a)
A
510
541
506
534
538
390
633
Option 081
A
850
931
979
1039
1075
Unit + option 15LS
Circuit 1
(a)
A
331
380
458
490
521
756
611
Circuit 2
(a)
A
496
524
490
518
521
378
611
Option 081
A
826
904
948
1008
1041
Nominal start-up current
(3)
- 30XB
Standard unit
Circuit 1
(a)
A
587
587
629
629
629
828
759
Circuit 2(
a)
A
629
629
629
629
629
587
759
Option 081
A
936
976
982
1014
1018
Option 081 & Opt 25c
A
687
702
729
744
744
Unit + option 15LS
Circuit 1
(a)
A
587
587
629
629
629
828
740
Circuit 2
(a)
A
629
629
629
629
629
587
740
Option 081
A
922
959
966
998
1001
Option 081 & Opt 25c
A
674
685
714
729
727
Maximum start-up current(Un)
(2)
- 30XB
Standard unit
Circuit 1
(a)
A
587
587
629
629
629
828
813
Circuit 2
(a)
A
629
629
629
629
629
587
813
Option 081
A
1051
1094
1097
1132
1136
Option 081 & Opt 25c
A
802
820
844
862
862
Unit + option 15LS
Circuit 1
(a)
A
587
587
629
629
629
828
805
Circuit 2
(a)
A
629
629
629
629
629
587
805
Option 081
A
1037
1077
1081
1116
1119
Option 081 & Opt 25c
A
789
803
829
847
845
(1) Values obtained at unit continuous maximum operating conditions (data given on the unit nameplate)
(2) Operating current of the smallest compressor(s) + fan c locked rotor current or reduced start-up current of the largest compressor.
(3) Standardised EUROVENT conditions, water-cooled exchanger water inlet/outlet = 12°C/7°C, outdoor air temperature = 35°C.
(a) When the machines are equipped with two power supplies, circuit 1 supplies the refrigerant circuit A and circuit 2 supplies the refrigerant circuit B or for units 30XB1550
to 1700 units: Circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D.
4.7 - Compressor electrical data
Compressor
I Nom
(1)
I Max
(Un)
(2)
I Max
(Un - 10%)
(3)
LRYA
A
(4)
LRDA
A
(5)
Cos
Phi nom.
(6)
Cos
Phi Max.
(7)
06TSA155
64
93
99
170
530
0,87
0,9
06TSA186
80
111
118
170
530
0,86
0,89
06TTA266
117
162
172
303
945
0,86
0,9
06TTA301
132
177
188
388
1210
0,87
0,9
06TTA356
153
207
220
388
1210
0,87
0,9
06TUA483
225
292
311
587
1828
0,87
0,88
06TUA554
241
338
360
587
1828
0,88
0,89
06TVA680
302
400
436
629
1919
0,87
0,89
06TVA753
315
430
468
629
1919
0,88
0,89
06TVA819
347
465
496
629
1919
0,88
0,89
Legend
(1) Nominal current draw at standard Eurovent conditions (see definition of conditions under nominal unit current draw)
(2) Maximum operating current
(3) Maximum compressor operating current, limited by the unit (current given for maximum capacity at 360 V)
(4) Locked rotor current for star connection (connection during compressor start-up)
(5) Locked rotor current for delta connection
(6) Value at standard Eurovent conditions: evaporator entering/leaving water temperature 12°C/7°C, condenser entering/leaving water temperature 30°C/35°C.
(7) Value at maximum capacity and nominal voltage
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XB UNITS