15
4 - PHYSICAL AND ELECTRICAL DATA FOR 30XAS UNITS
4.2 - Electrical data
30XAS
242
282
342
442
482
Power circuit
Nominal power supply
V-ph-Hz
400-3-50
Voltage range
V
360-440
Control circuit
24 V via internal transformer
Start-up current
(1)
A
303
388
388
587
587
Standard units
Cosine Phi maximum
(2)
0,89
0,88
0,88
0,87
0,87
Cosine Phi nominal
(3)
0,85
0,85
0,86
0,84
0,85
Total harmonic distortion
%
0
0
0
0
0
Maximum power input
(4)
kW
101
113
134
184
213
Nominal unit current draw
(3)
A
141
153
174
258
278
Maximum unit current draw (Un)
(4)
A
165
185
218
305
353
Maximum unit current draw (Un)
with option 231
(4)
A
148
167
201
284
333
Maximum unit current draw (Un -10%)
(2)
A
180
198
231
324
375
Units with option 119
Cosine Phi maximum
(2)
0,88
0,88
0,88
0,87
0,87
Cosine Phi nominal
(3)
0,84
0,85
0,85
0,83
0,84
Maximum power input
(4)
kW
105
118
139
190
221
Nominal unit current draw
(3)
A
141
153
175
254
271
Maximum unit current draw (Un)
(4)
A
172
194
229
318
368
Maximum unit current draw (Un -10%)
(2)
A
187
207
242
337
390
(1) Instantaneous start-up current (locked rotor current with star connection of the compressor).
(2) Values obtained at operation with maximum unit power input.
(3) Values obtained at standard Eurovent unit operating conditions: air 35 °C, water 12/7 °C.
(4) Values obtained at operation with maximum unit power input. Values given on the unit name plate.
Note:
Motor and fan electrical data if the unit operates at Eurovent conditions (ambient motor temperature 50 °C): 1.9 A, start-up current: 8.4 A, power input: 760 W.
4.3 - Electrical data, optional hydraulic module (option 116C)
The pumps that are factory-installed in these units comply with the European Ecodesign directive ErP. The additional electrical
data required* is as follows:
No
(2)
Description
(3)
Units
30XAS
282
342
442
482
1
Nominal efficiency at full load and nominal voltage
%
88,1
89,4
90,1
91,3
1
Nominal efficiency at 75% rated load and nominal voltage
%
88
88,9
89,7
91,4
1
Nominal efficiency at 50% rated load and nominal voltage
%
86,1
86,7
87,9
90,3
2
Efficiency level
-
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model
at the time of incorporation. Please refer to the motor name plates.
4
Manufacturer's name and trademark, commercial registration
number and place of manufacturer
-
5
Product's model number
-
6
Number of motor poles
-
2
7-1
Rated shaft power input at full load and nominal voltage (400V)
kW
4,0
5,5
7,5
11
7-2
Maximum power input (400V)
(4)
kW
4,5
6,2
8,3
12,0
8
Rated input frequency
Hz
50
9-1
Rated voltage
V
3*400
9-2
Maximum current drawn (400V)*
A
7,4
9,7
13,2
18,7
10
Rated speed
r/s - rpm
49 - 2915
49 - 2930
49 - 2935
49 - 2945
11
Product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools.
Disposal and recycling using an appropriate company.
12
Operating conditions for which the motor is specially designed
I Altitudes above sea level
m
< 1000**
II Ambient air temperature
° C
< 40
IV Maximum air temperature
° C
Please refer to the operating conditions given in this manual or in
the specific conditions in the Carrier selection programs.
V Potentially explosive atmospheres
-
Non-Atex environment
(1) Required by regulation 640/2009 with regard to the application of directive 2009/125/EC on the eco-design requirements for electric motors
(2) Item number imposed by regulation 640/2009, annex I2b.
(3) Description given by regulation 640/2009, annex I2b.
(4) To obtain the maximum power input for a unit with hydraulic module add the maximum unit power input from the electrical data table to the pump power input.
*
To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current
draw.
** Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration..