3 - DIMENSIONS, CLEARANCES
3.3 - 30XAS 442-482
Legend
All dimensions are given in mm.
NOTE: Drawings are not contractually binding. Before
designing an installation, consult the certified dimensional
drawings supplied with the unit or available on request.
For the positioning of the fixing points, weight distribution
and centre of gravity coordinates please refer to the
dimensional drawings.
B
Required clearances for maintenance and air flow
C
Recommended space for evaporator tube removal
Water inlet
Water outlet
Air outlet - do not obstruct
Power supply connection
C
Control circuit connection
3.4 - Multiple chiller installation
It is recommended to install multiple chillers in a single row,
arranged as shown in the example below, to avoid recycling of
warm air from one unit to another.
1,5 m
mini
1,5 m
mini
If the situation at the site does not permit this arrangement, contact
your Carrier distributor to estimate the space required between
units.
3.5 -
Distance to the wall
To ensure correct operation for most cases:
If h < H (2.3 m), minimum S = 3 m
If h > H or S < 3 m, contact your Carrier distributor.
H
S
h
Anti-vibration
mounts