21
LEGEND
LEGEND
RIG MACHINE COMPONENTS
Refer to Fig. 16-26 and Carrier Certified Prints for machine com-
ponent disassembly.
NOTE: Label each wire before removal when wiring must be dis-
connected (see Fig. 16 and 17). Clip all wire ties necessary when
removing pressure and temperature sensors. Disconnect all pres-
sure transducer wires at the sensor. Temperature sensors cannot be
disconnected from their cables; remove temperature sensors from
their thermowells and label as required.
Table 18 — 23XRV Waterbox Cover Weights, Frames A/B — English (lb)
a,b,c
NOTE(S):
a. Add to heat exchanger data for total weights or volumes.
b. Weight adder shown is the same for cooler and condenser of equal frame size.
c. For the total weight of a vessel with a marine waterbox, add these values to the heat exchanger weights (or volume).
WATERBOX
DESCRIPTION
COOLER FRAMES A AND B
CONDENSER FRAMES A AND B
Victaulic Nozzles
Flanged
Victaulic Nozzles
Flanged
NIH,1-Pass Cover 150 psig
217
244
242
274
NIH,2-Pass Cover 150 psig
172
265
191
298
NIH,3-Pass Cover 150 psig
228
245
261
277
NIH/Marine Plain End, 150 psig
157
157
173
173
MWB Cover, 150 psig
296
296
332
332
NIH,1-Pass Cover 300 psig
217
271
242
312
NIH,2-Pass Cover 300 psig
172
301
191
334
NIH,3-Pass Cover 300 psig
228
263
261
295
NIH/Marine Plain End, 300 psig
157
157
173
173
MWB Cover, 300 psig
296
296
332
332
MWB
—Marine Waterbox
NIH
—Nozzle-in-Head
Table 19 — 23XRV Waterbox Cover Weights, Frames A/B — SI (kg)
a,b,c
NOTE(S):
a. Add to heat exchanger data for total weights or volumes.
b. Weight adder shown is the same for cooler and condenser of equal frame size.
c. For the total weight of a vessel with a marine waterbox, add these values to the heat exchanger weights (or volume).
WATERBOX DESCRIPTION
COOLER FRAMES A AND B
CONDENSER FRAMES A AND B
Victaulic
Nozzles
Flanged
Victaulic
Nozzles
Flanged
NIH,1-Pass Cover 1034 kPa
98
111
110
124
NIH,2-Pass Cover 1034 kPa
78
120
87
135
NIH,3-Pass Cover 1034 kPa
103
111
118
126
NIH/Marine Plain End, 1034 kPa
71
71
78
78
MWB Cover, 1034 kPa
134
134
151
151
NIH,1-Pass Cover 2068 kPa
98
123
110
142
NIH,2-Pass Cover 2068 kPa
78
137
87
151
NIH,3-Pass Cover 2068 kPa
103
119
118
134
NIH/Marine Plain End, 2068 kPa
71
71
78
78
MWB Cover, 2068 kPa
134
134
151
151
MWB
—Marine Waterbox
NIH
—Nozzle-in-Head
IMPORTANT: Only a qualified service technician should
perform this operation.
WARNING
Do not attempt to disconnect flanges while the machine is
under pressure. Failure to relieve pressure can result in
personal injury or damage to the unit.
CAUTION
Before rigging the compressor, disconnect all wires entering
the power panel.
Содержание AquaEdge 23XRV
Страница 53: ...53 Fig 58 23XRV Controls Schematic ...
Страница 54: ...54 Fig 58 23XRV Controls Schematic cont FROM 2000767952 SHEET 3 ...
Страница 55: ...55 Fig 58 23XRV Controls Schematic cont ...
Страница 56: ...56 Fig 59 23XRV Controls Schematic Rockwell Standard Tier VFD Shown ...
Страница 57: ...57 Fig 60 23XRV LF2 VFD Wiring Diagram ...
Страница 65: ...65 Fig 70 23XRV Insulation Area Units with P Compressor ...