APPENDIX D — NETWORK CONFIGURATION
OBJECT NAME
OBJECT TYPE
INSTANCE
OPTION
PV ACCESS
DESCRIPTION
ALARMRST_alarm_1
AV
85
RO
Current Alarm 1
ALARMRST_alarm_2
AV
86
RO
Current Alarm 2
ALARMRST_alarm_3
AV
87
RO
Current Alarm 3
ALARMRST_alarm_4
AV
88
RO
Current Alarm 4
ALARMRST_alarm_5
AV
89
RO
Current Alarm 5
BACnet_COLOR
MV
8
RO
Start Free Cooling
BACnet_PRIME_V
AV
150
RO
Start Free Cooling
CAPACTRL_cm_stat1
AV
95
RO
Comp1 Run State Val
CAPACTRL_ctrl_wt
AV
90
RO
Controlled Water Temp
CAPACTRL_gv1_tgt
AV
91
RO
Target GV1 Pos
CAPACTRL_gv2_tgt
AV
92
RO
Target GV2 Pos
CAPACTRL_hgbp_tp
AV
94
RO
ECV Target Percent
CAPACTRL_vfd_tgt
AV
93
RO
Target VFD Speed Per
CFGSURGE_gv1_pful
AV
127
RO
IGV1 Full Load Position
CFGSURGE_gv1_pmin
AV
126
RO
IGV1 Minimum Position
CFGSURGE_sgl_hoff
AV
130
RO
Surge Line Upper DB
CFGSURGE_sgl_loff
AV
129
RO
Surge Line Lower DB
CFGSURGE_sgl_off
AV
128
RO
Surge Line Offset
CFGSURGE_sgl_pro
AV
134
RO
Surge Profile Offset
CFGSURGE_sgl_shfh
AV
131
RO
Surge Line Shape Factor
CFGSURGE_sgl_shfl
AV
132
RO
Sound Line Shape Factor
CFGSURGE_sgl_spdf
AV
133
RO
Surge Line Speed Factor
CONF_OPT_hgbp_opt
No=0, Cont.=1,
ON/OFF=2, mA=3
MV
6
RO
EC Valve Option
CONF_OPT_hgbp_sel
Disable=0, Surge=1
Low Load=2, Comb=3
MV
7
RO
EC Valve Selection
CONF_PRG_oil_flt
AV
136
RO
Oil Filter Failure
CONF_PRG_oil_qly
AV
135
RO
Oil Quality
CONF_PRG_ref_chg
AV
138
RO
Refrig Charge Status
CONF_PRG_tran_dev
AV
137
RO
Transducer Deviation
CONNECT_bac_id
AV
140
RO
BACnet Identifier
CONNECT_bacena
BV
63
RO
BACnet/IP Enable
CONNECT_bacunit
BV
64
RO
BACnet Metric Unit
CONNECT_network
AV
139
RO
BACnet Network
FACTORY_chil_typ
19XR6/7=0,19XR2~E/D/V=1,
19DV=2
MV
4
RO
Chiller Type
FACTORY_vfd_opt
No=0,FS VFD=1,Carrier=2
Rockwell LF2=3, Eaton=4
Rockwell STD=5
MV
5
RO
VFD Option
GENUNIT_AMPS_P
AV
4
RO
Percent Current
GENUNIT_BAC_OCC
BV
9
RO
BACnet Occupied
GENUNIT_ch_state
AV
7
RO
Chiller Status Code
GENUNIT_CHIL_OCC_rd
BV
3
RO
Network:Cmd Occupied
GENUNIT_CHIL_OCC_wr
BV
68
CMD
RW
Network:Cmd Occupied
GENUNIT_CHIL_S_S_rd
BV
2
RO
Network:Cmd Start/Stop
GENUNIT_CHIL_S_S_wr
Local=0, Network=1
Remote=2, Local Sched=3
BV
66
CMD
RW
Network:Cmd Start/Stop
GENUNIT_CTRL_PNT_rd
AV
1
RO
Control Point
GENUNIT_CTRL_PNT_wr
AV
147
CMD
RW
Control Point
GENUNIT_ctl_mode
Local=0, Network=1
Remote=2, Local Sched=3
MV
1
RO
Control Mode
GENUNIT_DEM_LIM_rd
AV
6
RO
Actual Demand Limit
GENUNIT_DEM_LIM_wr
AV
148
CMD
RW
Actual Demand Limit
GENUNIT_EMSTOP_rd
BV
5
RO
Emergency Stop
GENUNIT_EMSTOP_wr
BV
67
CMD
RW
Emergency Stop
GENUNIT_FC_START_rd
BV
8
RO
Start Free Cooling
GENUNIT_FC_START_wr
BV
69
CMD
RW
Start Free Cooling
GENUNIT_HC_SEL_rd
BV
4
RO
Cooling/Heating Select
GENUNIT_HC_SEL_wr
AV
149
CMD
RW
Cooling/Heating Select
GENUNIT_ice_occ
BV
7
RO
Ice Schedule Occupied
GENUNIT_KW_P
AV
5
RO
Motor Percent Kilowatts
GENUNIT_loc_occ
BV
6
RO
Local Schedule Occupied
GENUNIT_reset
AV
2
RO
Control Point Reset
GENUNIT_setpoint
AV
3
RO
Actual Setpoint
GENUNIT_statstop
BV
1
RO
Deter Start Stop Command
HYDRLIC_CDW_FLOW
BV
50
RO
Condenser Water Flow
HYDRLIC_CDW_FV
AV
58
RO
Cond Water Flow Value