APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Surge Correction
LEGEND
*Default value is shown only if configurable in this table.
Maintenance VFD Config
LEGEND
CCN TABLE NAME: MAISURGE
PIC6 PATH: Main Menu
Maintenance Menu
Surge Correction
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Surge Region
0 = No, 1 = Low, 2 = High,
3 = Deadband, 4 = Noise
act_reg
0 to 4
RO
2
Active Delta Tsat
dts_act
°F
RO
3
Calc Ref Delta Tsat
dts_cal
°F
RO
4
High Eff Delta Tsat
dts_he
°F
RO
5
Amps Change Surge Prot
amps_dta
%
RO
6
Max Amps Change Value
amch_max
%
RO
7
Surge Counts
sc
RO
8
Surge Protection Counts
spc
RO
9
Surge Prevention Active
surg_act
NO/YES
RO
10
Surge Protection Active
surg_pro
NO/YES
RO
11
EC Valve Change Flag
0 = Close, 1 = Hold, 2 = Open
hgbp_chg
0 to 2
RO
12
Cal Surge Delta Tsmax
dts_maxc
0 to 150.0
°F
RO
13
Cal Surge Delta Tsmin
dts_minc
0 to 150.0
°F
RO
14
Cal Surge Delta Tsmed
dts_medc
0 to 150.0
^F
RO
15
IGV1 Full Load Position
gv1_sful
0 to100.0
%
RO
16
IGV1 Minimum Position
gv1_smin
0.0 to 100.0
%
RO
17
Opti-Sound IGV1 Position
gvi_smed
%
RO
18
Envelope Line Optimized
enlp_opt
NO/YES
RO
RO —
Read Only
CCN TABLE NAME: VFD_MCFG
PIC6 PATH: Main Menu
Maintenance Menu
Maintenance VFD Config
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE
UNIT
READ/WRITE
1
VFD Config Conflict
vfd_cflt
NO/YES
No
RO
2
Delete VFD Config
Yes = Delete, No = Keep
del_vfdc
NO/YES
No
RW
3
Rated Line Voltage
rlv_i
460
V
RO
4
Motor Rated Load Current
rla_load
200
amps
RO
5
Motor Nameplate Current
rla
200
amps
RO
6
Motor Nameplate Voltage
rlv
460
volts
RO
7
Motor Nameplate RPM
rpm
3000
rpm
RO
8
Motor Nameplate kW
rlkw
1500
kW
RO
9
Compressor Speed 100
%
comp_100
50
Hz
RO
10
Skip Frequency 1
skipfrq1
102
Hz
RO
11
Skip Frequency 2
skipfrq2
102
Hz
RO
12
Skip Frequency 3
skipfrq3
102
Hz
RO
13
Skip Frequency Band
skipband
0
Hz
RO
14
Increase Ramp Time
ramp_inc
30
sec
RO
15
Decrease Ramp Time
ramp_dec
30
sec
RO
16
Line Voltage Imbalance
%
lvim_th
10
%
RO
17
Line Volt Imbalance Time
lvim_per
10
sec
RO
18
Line Current Imbalance
%
lcim_th
40
%
RO
19
Line Current Imbal Time
lcim_per
10
sec
RO
20
Motor Current Imbalance
mcim_th
40
%
RO
21
Motor Current Imbal Time
mcim_per
10
sec
RO
22
Single Cycle Dropout
scycd_en
DISABLE/ENABLE
DISABLE
RO
23
PWM Switch Frequency
0 = 2 kHz, 1 = 4 kHz
pwm_freq
0/1
0
RO
24
Restore Defaults
res_def
NO/YES
No
RO
25
Communication Timeout
com_tout
10
sec
RO
RO —
Read Only
RW —
Read/Write