59
APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
19DV
LEGEND
*Default value is shown only if configurable in this table.
General VFD
LEGEND
*Default value is shown only if configurable in this table.
IOB
* These will need to be configured for unit feature to be operational if
installed to IOB - Auto Demand Type = 2, Remote Reset = 4, Auto
Reset Type = 2
NOTE: 0=Disable, 1=V, 2=mA, 3= 10K thermistor, 4=5K thermistor,
5=Resistance, 6=RTD
CCN TABLE NAME: CFG_19DV
PIC6 PATH: Main Menu
Configuration Menu
19DV
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
Pressure Sensor Option (0=Tianmo,
1=Texas, 2=Sensata)
sen_opt
0 to 2
0
RW
2
Purge System Option
pg_opt
DISABLE/ENABLE
DISABLE
RW
3
Purge Active Temp SP
pgt_set
30 to 300
65
°F
RW
4
Purge On Idle Option
pgon_opt
DISABLE/ENABLE
DISABLE
RW
5
Purge Regen Lasting Time
reg_tim
0 to 65535
120
min
RW
6
Purge Discharge Temp
dis_temp
–10000000 to
10000000
8.0
°F
RW
7
Purge Drainage Temp
dra_temp
–10000000 to
10000000
9.0
°F
RW
8
Purge Discharge Time
dis_time
0 to 65535
5
sec
RW
9
PG Discharge Delay Time
dly_time
0 to 65535
30
sec
RW
10
Daily PG Pumpout Limit
pgpumplm
20 to 200
50
min
RW
11
Motor Pole Pair
Single=1, Double=2
1 to 2
1
RW
12
IGV2 Travel Limit
gv2_lim
0 to 100
96
%
RW
13
IGV2 Minimum Degree
gv2_dmin
0 to 20
2.0
RW
14
IGV2 Full Load Open Deg
gv2_dfw
10 to 100
90.0
RW
15
IGV2 Actuator Max Deg
gv2_dmax
90 to 120
94.0
RW
16
IGV2 Deg @IGV1 20 Deg
gv2_d20
28.1
RW
17
IGV2 Deg @IGV1 30 Deg
gv2_d30
37.2
RW
18
IGV2 Deg @IGV1 50 Deg
gv2_d50
71.6
RW
19
Comp Based Speed Hz
vfd_ratf
10 to 200
80.5
Hz
RW
20
Liquid Bypass Temp Band
lqby_lmt
2 TO 10
3.0
^3
RW
21
4-valve Lube (Legay DV4)
lega_lub
DISABLE/ENABLE
DISABLE
RW
22
Pre Lube From Colder HX
opt_7
DISABLE/ENABLE
DISABLE
RW
RW —
Read/Write
CCN TABLE NAME: CFGGEVFD
PIC6 PATH: Main Menu
Configuration Menu
General VFD
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
VFD Gain
vfd_gain
0.10 to 1.50
0.75
RW
2
VFD Max Speed Per
vfd_max
90.0 to 110.0
100.0
%
RW
3
VFD Min Speed Per
vfd_min
65.0 to 100.0
70.0
%
RW
4
VFD Start Speed Per
vfd_str
65.0 to 100.0
100.0
%
RW
5
VFD Current Limit
vfdculm
0.0 to 99999.0
250
amp
RW
RW —
Read/Write
CCN TABLE NAME: CONF_IOB
PIC6 PATH: Main Menu
Configuration Menu
IOB
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
ECW Sensor Type
0 to 6
4
RW
2
LCW Sensor Type
0 to 6
4
RW
3
ECDW Sensor Type
0 to 6
4
RW
4
LCDW Sensor Type
0 to 6
4
RW
5
MTRW1 Sensor Type
0 to 6
4
RW
6
Auto Demand Type
0*
4
RW
7
Reg Leak Sensor Type
2
4
RW
8
Remote Reset Type
0*
4
RW
9
Auto Reset Type
0 to 6
4
RW
10
ISM Input Enable
DISABLE/ENABLE
DISABLE
RW