APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Inputs Status
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: INPUTS
PIC6 PATH: Main Menu
Inputs Status
LINE
PIC6 DESCRIPTION
CCN NAME
RANGE
DEFAULT
VALUE*
UNIT
READ/WRITE
1
EC Valve Status
0=Closed, 1=Interim, 2=Opened
3=Failure
HGBP_ACT
0 to 3
RO
2
High Pressure Switch
HP_SW
OPEN/CLOSE
RO
3
Remote Contact
REM_CON
OPEN/CLOSE
RO
4
Remote Stop Contact
REM_STOP
OPEN/CLOSE
RO
5
Emergency Stop Contact
E_STOP
OPEN/CLOSE
RO
6
Ice Build Contact
ICE_CON
OPEN/CLOSE
RO
7
Chiller Lockout
REM_LOCK
OPEN/CLOSE
RO
8
Spare Safety Input
SAFETY
OPEN/CLOSE
RO
9
Starter Fault Feedback
STARTFLT
OPEN/CLOSE
RO
10
Fire Security Interlock
FS_LOCK
OPEN/CLOSE
RO
11
Guide Vane 1 Actual Pos
GV1_ACT
%
RO
12
Guide Vane 2 Actual Pos
GV2_ACT
%
RO
13
Actual VFD Speed Per
VFD_ACT
%
RO
14
Auto Demand Limit Input
AUTO_DEM
mA
RO
15
Auto Water Temp Reset
AUTO_RES
mA
RO
16
Refrig Leak Sensor
REF_LEAK
mA
RO
17
VFD Speed Feedback
VFD_IN
V
RO
18
Guide Vane 1 Pos Feedback
GV1_MA
mA
RO
19
Guide Vane 2 Pos Feedback
GV2_MA
mA
RO
20
VFD Current Input
VFDC_MA
mA
RO
21
Actual ECV Pos Per
HGBPACTP
%
RO
22
ECV Current Feedback
HGBP_MA
mA
RO
23
Free Cool Start Switch
FC_SS
Off/On
RO
24
Customer Alert
CUS_ALE
OPEN/CLOSE
RO
25
Purge Level Switch Low
PGLE_LO
OPEN/CLOSE
RO
26
Purge Level Switch High
PGLE_HI
OPEN/CLOSE
RO
27
Liquid Level Switch
HF_LS
OPEN/CLOSE
RO
RO —
Read Only