6–3
T-365
6.5
UNIT WILL NOT TERMINATE HEATING
Condition
Possible Cause
Remedy/Refer-
ence Section
Unit fails to stop heating
Controller improperly set
Reset
Controller malfunction
Heater termination thermostat remains closed along with
the heat relay
6.6
UNIT WILL NOT DEFROST PROPERLY
Condition
Possible Cause
Remedy/Refer-
ence Section
Will not initiate defrost automati-
cally
Defrost timer malfunction (Cd27)
Loose terminal connections
Tighten
Defective wiring
Replace
Defrost temperature sensor defective or heat termination
thermostat open
Replace
Heater contactor or coil defective
Replace
Will not initiate defrost manually
Keypad is defective
Replace
Defrost temperature sensor open
Replace
Initiates but relay (DR) drops out
Low Line Voltage
Initiates but does not defrost
Heater contactor or coil defective
Replace
Heater(s) burned out
6.7
ABNORMAL PRESSURES
Condition
Possible Cause
Remedy/Refer-
ence Section
High discharge pressure
Condenser coil dirty
Condenser fan rotating backwards
Condenser fan inoperative
Refrigerant overcharge or non-condensibles
Discharge service valve partially closed
Open
Electronic expansion valve (EEV) control malfunction
Replace
Содержание 69NT40-561-300
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 14: ......
Страница 22: ......
Страница 34: ......
Страница 108: ......
Страница 116: ......
Страница 164: ...T 365 8 2 Figure 8 2 Unit Wiring Diagram Based on Drawing 62ï11755 ...
Страница 165: ...8 3 T 365 Figure 8 3 Wiring Diagram Based on Drawing 62ï11755 ...
Страница 166: ...T 365 8 4 Figure 8 4 Wiring Diagram Based on Drawing 62ï11755 ...
Страница 168: ......
Страница 172: ......
Страница 173: ......