![Carrier 69NT40-561-019 Скачать руководство пользователя страница 113](http://html1.mh-extra.com/html/carrier/69nt40-561-019/69nt40-561-019_operation-and-service-manual_2563845113.webp)
7–27
T-359
7.19.1
Sensor Checkout Procedure
To check a sensor reading, do the following:
a. Remove the sensor and place in a 0°C (32°F) ice-water bath. The ice-water bath is prepared by filling an
insulated container (of sufficient size to completely immerse bulb) with ice cubes or chipped ice, then filling
voids between ice with water and agitating until mixture reaches 0°C (32°F) measured on a laboratory ther-
mometer.
b. Start unit and check sensor reading on the control panel. The reading should be 0°C (32°F). If the reading is
correct, reinstall sensor; if it is not, continue with the following.
c. Turn unit OFF and disconnect power supply.
d. Refer to
and remove controller to gain access to the sensor plugs.
e. Using the plug connector marked “EC” that is connected to the back of the controller, locate the sensor
wires (RRS, RTS, SRS, STS, AMBS, DTS, or CPDS as required). Follow those wires to the connector and
using the pins of the plug, measure the resistance. Values are provided in
Due to the variations and inaccuracies in ohmmeters, thermometers or other test equipment, a reading
within 2% of the chart value would indicate a good sensor. If a sensor is defective, the resistance read-
ing will usually be much higher or lower than the resistance values given.
Содержание 69NT40-561-019
Страница 2: ......
Страница 4: ......
Страница 74: ......
Страница 127: ...8 3 T 359 Figure 8 2 SCHEMATIC DIAGRAM Evergreen Unit Configuration ...
Страница 128: ...T 359 8 4 Figure 8 3 UNIT WIRING DIAGRAM Evergreen Unit Configuration Sheet 1 of 2 ...
Страница 129: ...8 5 T 359 Figure 8 4 UNIT WIRING DIAGRAM Evergreen Unit Configuration Sheet 2 of 2 ...
Страница 130: ......
Страница 134: ......
Страница 135: ......