T-354
4–12
4.6.4
Logging Interval (dCF03)
The user may configure four time intervals between data recordings. Data is logged at exact intervals in accor-
dance with the real-time clock. The clock is factory set at Greenwich Mean Time.
4.6.5
Thermistor Format (dCF04)
The user may configure the format in which the thermistor readings are recorded. The low resolution is a 1 byte for-
mat and the normal resolution is a 2 byte format. The low resolution requires less memory and records temperature
in 0.25
C (0.45
F) increments when in perishable mode or 0.5
C (0.9
F) increments when in the frozen mode. The
normal resolution records temperature in 0.01
C (0.02
F) increments for the entire range.
Table 4–2 DataCORDER Configuration Variables
CONFIGURATION NO.
TITLE
DEFAULT
OPTION
dCF01
(Future Use)
-
-
dCF02
Sensor Configuration
2
2,5,6,9,54,64,94
dCF03
Logging Interval (Minutes)
60
15,30,60,120
dCF04
Thermistor Format
Short
Low, Normal
dCF05
Thermistor Sampling Type
A
A,b,C
dCF06
Controlled Atmosphere/Humidity Sampling Type
A
A,b
dCF07
Alarm Configuration USDA Sensor 1
A
Auto, On, Off
dCF08
Alarm Configuration USDA Sensor 2
A
Auto, On, Off
dCF09
Alarm Configuration USDA Sensor 3
A
Auto, On, Off
dCF10
Alarm Configuration Cargo Sensor
A
Auto, On, Off
Table 4–3 DataCORDER Standard Configurations
STANDARD CONFIGURATION
DESCRIPTION
2 sensors
(dCF02=2)
2 thermistor inputs (supply & return)
5 sensors
(dCF02=5)
2 thermistor inputs (supply & return)
3 USDA thermistor inputs
6 sensors
(dCF02=6)
2 thermistor inputs (supply & return)
3 USDA thermistor inputs
1 humidity input
9 sensors
(dCF02=9)
Not Applicable
6 sensors
(dCF02=54)
2 thermistor inputs (supply & return)
3 USDA thermistor inputs
1 cargo probe (thermistor input)
7 sensors
(dCF02=64)
2 thermistor inputs (supply & return)
3 USDA thermistor inputs
1 humidity input
1 cargo probe (thermistor input)
10 sensors
(dCF02=94)
2 thermistor inputs (supply & return)
3 USDA thermistor inputs
1 humidity input
1 cargo probe (thermistor input)
3 CA inputs (NOT APPLICABLE)
Содержание 69NT40-541-306
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 14: ......
Страница 78: ...T 354 5 8 Figure 5 3 Controller Operation Perishable Mode Figure 5 4 Controller Operation Frozen Mode ...
Страница 142: ...T 354 8 2 Figure 8 2 Schematic Diagram Standard Unit Configuration BASED ON 62 66686 00 ...
Страница 143: ...8 3 T 354 Figure 8 3 Unit Wiring Diagram Standard Unit Configuration 1 of 2 BASED ON 62 66686 00 ...
Страница 144: ...T 354 8 4 Figure 8 4 Unit Wiring Diagram Standard Unit Configuration 2 of 2 BASED ON 62 66686 00 ...
Страница 148: ...T 354 8 8 ...
Страница 152: ......
Страница 153: ......