43
Table 3-9 DataCORDER Pre-Trip Result Records
Test
No.
TITLE
DATA
1-0
Heater On
Pass/Fail/Skip Result, Change in current for Phase A, B and C
1-1
Heater Off
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
2-0
Condenser Fan On
Pass/Fail/Skip Result, Water pressure switch (WPS)
−
Open/Closed,
Change in currents for Phase A, B and C
2-1
Condenser Fan Off
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
3-0
Low Speed Evaporator Fan
On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
3-1
Low Speed Evaporator Fan
Off
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
4-0
High Speed Evaporator Fan
On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
4-1
High Speed Evaporator Fan
Off
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
5-0
Supply/Return Probe Test
Pass/Fail/Skip Result, STS, RTS, SRS and RRS
5-1
Secondary Supply Probe Test
Pass/Fail/Skip Result
5-2
Secondary Return Probe Test
Pass/Fail/Skip Result
6-0
Compressor On
Pass/Fail/Skip Result, Change in currents for Phase A, B and C
6-1
Not Applicable
Not Used
6-2
Suction Modulation Valve
Open and Closed
Pass/Fail/Skip Result, Is current or pressure limit in effect (Y,N)
6-4
Not Applicable
Not Used
6-5
Not Applicable
Not Used
7-0
High Pressure Switch Closed
Pass/Fail/Skip Result, AMBS, DPT or CPT (if equipped)
Input values that component opens
7-1
High Pressure Switch Open
Pass/Fail/Skip Result, STS, DPT or CPT (if equipped)
Input values that component closes
8-0
Perishable Heat
Pass/Fail/Skip Result, STS, time it takes to heat to 16
°
C (60
°
F)
8-1
Perishable Pull Down
Pass/Fail/Skip Result, STS, time it takes to pull down to 0
°
C (32
°
F)
8-2
Perishable Maintain
Pass/Fail/Skip Result, Averaged DataCORDER supply temperature
(SRS) over last recording interval.
9-0
Defrost Test
Pass/Fail/Skip Result, DTS reading at end of test, line voltage, line
frequency, time in defrost.
10-0
Frozen Mode Set-up
Pass/Fail/Skip Result, STS, time unit is in heat.
10-1
Frozen Mode Pull Down
Pass/Fail/Skip Result, STS, time to pull down unit to -17.8
°
C (0
°
F).
10-2
Frozen Mode Maintain
Pass/Fail/Skip Result, Averaged DataCORDER return temperature
(RRS) over last recording interval.
Содержание 69NT40-541-300
Страница 2: ......
Страница 4: ......
Страница 20: ......
Страница 32: ......
Страница 128: ......
Страница 131: ...7 3 T 318 Based on Drawing 62 66058 Figure 7 2 SCHEMATIC DIAGRAM Units with 3 Phase Evaporator Motors...
Страница 133: ...7 5 T 318 6 Heater FCCH FCCH Figure 7 4 SCHEMATIC DIAGRAM Units with Normal Evaporator Fan Capability...
Страница 134: ...7 6 T 318 FCCH FCCH Figure 7 5 SCHEMATIC DIAGRAM Units with Single Evaporator Fan Capability...
Страница 136: ...7 8 T 318 To ST10 To TRX2 To QC1 To QC1 To QC1 To MC6 CONTROLLER Figure 7 7 SCHEMATIC DIAGRAM Emergency Bypass...
Страница 138: ...7 10 T 318 Based on Drawing 62 66058 Figure 7 9 UNIT WIRING DIAGRAM Units with 3 Phase Evaporator Motors Sheet 1 of 2...
Страница 139: ...7 11 T 318 Based on Drawing 62 66058 Figure 7 10 UNIT WIRING DIAGRAM Units with 3 Phase Evaporator Motors Sheet 2 of 2...
Страница 144: ......
Страница 150: ......
Страница 151: ......