Table 4–7 Controller Pre-Trip Test Codes
CODE #
TITLE
DESCRIPTION
NOTE
“Auto” or “Auto1” menu includes the: P, P1, P2, P3, P4, P5, P6 and rSLts. “Auto2” menu
includes P, P1, P2, P3, P4, P5, P6, P7, P8, P9, P10 and rSLts.”Auto3 menu includes P, P1, P2, P3,
P4, P5, P6, P7, P8 and rSLts
P
Pre-Trip Initiated
All lights and display segments will be energized for five seconds at the start
of the pre-trip. Since the unit cannot recognize lights and display failures,
there are no test codes or results associated with this phase of pre-trip.
P1-0
Heaters Turned On
Setup:
Heater must start in the OFF condition, and then be turned on. A
current draw test is done after 15 seconds.
Pass/Fail Criteria:
Passes if current draw change is within the range
specified.
P1-1
Heaters Turned Off
Setup:
Heater must start in the ON condition, and then be turned off. A
current draw test is done after 10 seconds.
Pass/Fail Criteria:
Passes if current draw change is within the range
specified.
P2-0
Condenser Fan On
Requirements:
Water pressure switch (WP) input must be closed.
Setup:
Condenser fan is turned ON, a current draw test is done after 15
seconds.
Pass/Fail Criteria:
Passes if current draw change is within the range
specified.
P2-1
Condenser Fan Off
Setup:
Condenser fan is turned OFF, a current draw test is done after 10
seconds.
Pass/Fail Criteria:
Passes if current draw change is within the range
specified.
P3
Low Speed Evaporator
Fans
Requirements:
The unit must be equipped with a low speed evaporator fan,
as determined by the Evaporator Fan speed select configuration variable.
If the unit is configured for single evaporator fan operation, Pre-Trip tests
P3-0, P3-1, P4-0 and P4-1 will fail immediately if Controller alarm codes
AL11 or AL12 are active at the start of testing.
P3-0
Low Speed Evaporator
Fan Motors On
Setup:
The high speed evaporator fans will be turned on for 10 seconds,
then off for two seconds, then the low speed evaporator fans are turned
on. A current draw test is done after 60 seconds.
Pass/Fail Criteria:
Passes if change in current draw is within the range
specified. Fails if AL11 or AL12 activates during test.
P3-1
Low Speed Evaporator
Fan Motors Off
Setup:
The low speed Evaporator Fan is turned off, a current draw test is
done after 10 seconds.
Pass/Fail Criteria:
Passes if change in current draw is within the range
specified. Fails if AL11 or AL12 activates during test.
P4-0
High Speed Evaporator
Fan Motors On
Setup:
The high speed Evaporator Fan is turned on, a current draw test
is done after 60 seconds.
Pass/Fail Criteria:
Passes if change in current draw is within the range
specified. Fails if AL11 or AL12 activates during test.
P4-1
High Speed Evaporator
Fan Motors Off
Setup:
The high speed Evaporator Fan is turned off, a current draw test
is done after 10 seconds.
Pass/Fail Criteria:
Passes if change in current draw is within the range
specified. Fails if AL11 or AL12 activates during test.
Содержание 69NT40-541-001
Страница 2: ......
Страница 4: ......
Страница 10: ...T 316 vi...
Страница 14: ......
Страница 20: ......
Страница 24: ......
Страница 36: ......
Страница 79: ...5 9 T 316 Figure 5 3 Controller Operation Perishable Mode Figure 5 4 Controller Operation Frozen Mode...
Страница 138: ......
Страница 141: ...8 3 T 316 Figure 8 2 SCHEMATIC DIAGRAM...
Страница 142: ...T 316 8 4 Figure 8 3 SCHEMATIC DIAGRAM Units with Single Evaporator Fan Capability...
Страница 144: ...T 316 8 6 Figure 8 5 SCHEMATIC DIAGRAM Emergency Bypass To ST10 To TRX2 To QC1 To QC1 To QC1 To MC6 CONTROLLER...
Страница 150: ......
Страница 154: ......
Страница 155: ......