Carrier 58CTA/CTX Скачать руководство пользователя страница 11

11

AIR DELIVERY—CFM (With Filter)* continued

UNIT SIZE

RETURN-AIR

SUPPLY

SPEED

EXTERNAL STATIC PRESSURE (In. wc)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

110-12

Bottom

or

Side(s)

High

Med-High

Med-Low

Low

1625

1510

1360

1195

1575

1470

1335

1180

1515

1415

1295

1155

1445

1355

1250

1115

1355

1285

1180

1065

1260

1185

1100

980

1165

1070

985

860

990

890

810

740

785

725

670

605

595

530

475

410

110-16

Bottom

or

Side(s)

High

Med-High

Medium

Med-Low

Low

2055

1750

1545

1300

1050

1990

1725

1525

1290

1045

1910

1670

1490

1275

1015

1815

1605

1445

1235

975

1695

1515

1355

1165

935

1575

1400

1260

1085

880

1425

1255

1135

1005

815

1230

1120

1020

895

715

1090

975

880

750

610

910

785

750

620

515

110-22

Bottom

Only

High

Med-High

Medium

Med-Low

Low

2530

2225

1895

1565

1320

2460

2190

1885

1555

1295

2380

2135

1865

1535

1265

2285

2075

1820

1505

1235

2200

1995

1770

1465

1205

2085

1910

1700

1410

1160

1970

1805

1610

1350

1105

1835

1695

1520

1265

1035

1695

1565

1410

1175

950

1545

1430

1290

1050

870

Both Sides

or 1

Side & Bottom

High

Med-High

2205

2175

2415

2120

2330

2065

2235

1975

2125

1900

1995

1790

1860

1685

1735

1580

1605

1460

1 Side Only

High

Med-High

Medium

Med-Low

Low

2485

2155

1830

1520

1275

2430

2135

1830

1505

1260

2360

2100

1810

1490

1240

2270

2040

1780

1470

1210

2175

1970

1730

1430

1180

2070

1885

1665

1385

1135

1950

1790

1595

1330

1090

1825

1680

1505

1250

1025

1685

1560

1395

1165

930

1535

1420

1275

1055

840

135-16

Bottom

or

Side(s)

High

Med-High

Med-Low

Low

2090

1790

1545

1325

2010

1755

1525

1320

1930

1705

1500

1295

1835

1640

1450

1265

1710

1550

1380

1210

1590

1465

1315

1150

1470

1360

1215

995

1335

1210

1005

865

1025

945

855

745

835

785

670

540

135-22

Bottom

Only

High

Med-High

Med-Low

Low

2485

2195

1880

1640

2400

2150

1850

1635

2310

2090

1820

1615

2215

2000

1780

1585

2110

1920

1715

1530

2000

1825

1635

1465

1880

1720

1540

1370

1725

1565

1415

1255

1535

1405

1290

1150

1355

1255

1160

1040

Both Sides

or 1

Side & Bottom

High

Med-High

Med-Low

Low

2180

1880

1640

2145

1850

1635

2385

2060

1820

1615

2305

2010

1780

1585

2195

1945

1715

1530

2085

1865

1635

1465

1960

1765

1540

1370

1825

1660

1415

1255

1670

1515

1290

1150

1465

1325

1160

1040

1 Side Only

High

Med-High

Med-Low

Low

2320

2125

1845

1640

2250

2065

1825

1620

2155

1995

1765

1580

2055

1910

1710

1540

1970

1815

1650

1485

1855

1710

1570

1410

1725

1610

1475

1330

1600

1490

1370

1220

1450

1340

1240

1080

1280

1175

1100

960

155-20

Bottom

Only

High

Med-High

Med-Low

Low

2465

2115

1800

1570

2430

2105

1790

1565

2375

2075

1770

1551

2305

2030

1735

1525

2230

1980

1695

1495

2110

1910

1640

1445

2000

1830

1570

1370

1865

1725

1465

1270

1725

1590

1345

1175

1545

1425

1225

1070

Both Sides

or 1

Side & Bottom

High

Med-High

2155

2135

2375

2095

2285

2040

2200

1975

2105

1895

1995

1790

1870

1685

1730

1550

1570

1400

1 Side Only

High

Med-High

2140

2095

2260

2040

2180

1975

2085

1890

1975

1810

1865

1705

1740

1595

1605

1480

1455

1325

* A filter is required for each return---air supply. Airflow performance includes 3/4---in. (19 mm) washable filter media such as contained in factory---authorized

accessory filter rack. To determine airflow performance without this filter, assume an additional .1 available external static pressure.

— Indicates unstable operating conditions.

58C

TA

/C

TX

Содержание 58CTA/CTX

Страница 1: ...ology Intelligent microprocessor control S Two stage heating with single stage thermostat with patented Adaptive Control Technology S Very low operating sound through low stage operation and QuieTecht system SmartEvapt Humidity control when using a Thermidistatt Infinityt control Comfort Fant adjustable constant fan speed from the thermostat S High Efficiency Media Filtration Cabinet included S Mi...

Страница 2: ...00 Btuh 08 800 CFf7 12 1200 CFM 14 1400 CFM 16 1600 CFM Input Capacity 20 2000 CFM 045 44 000 Btuh 110 110 000 Btuh 22 2200 CFM 070 66 000 Btuh 135 132 000 Btuh 090 88 000 Btuh 155 154 000 Btuh Series Number EFFICIENCY RATING CERTIFIED MEETS DOE RESIDENTIAL CONSERVATION SERVICES PROGRAM STANDARDS Before purchasing this appliance read important energy cost and efficiency information available from ...

Страница 3: ...TCH BLOWER AND MOTOR RATING PLATE NOT SHOWN LOCATED ON BLOWER DOOR GAS MANIFOLD GAS BURNER BLOWER DOOR SAFETY SWITCH FLAME SENSOR Elbow may be turned to a different position depending on type of installation A04138 NOTE The 58CTA CTX Furnaces are factory shipped for use with natural gas These furnaces can be field converted for propane gas with a factory authorized and listed accessory conversion ...

Страница 4: ... C Auto Changeover TP NAC TC NAC For use with 1 speed Heat Pump deg F C Auto Changeover TP NHP TC NHP For use with 2 speed Air Conditioner deg F C Auto Changeover TP NRH For use with multi use stage configurations deg F C Auto Changeover Temperature and Humidity control TP PRH THERMOSTAT PROGRAMMABLE For use with 1 speed Air Conditioner deg F C Auto Changeover 7 Day Programmable TP PAC For use wit...

Страница 5: ...2UPH X X X X X X X X X X X X X X Twinning Kit KGATW0601HSI X X X X X X X X X X X X X X Combustible Floor Base KGASB0201ALL X X X X X X X X X X X X X X Downflow Vent Guard KGAVG0101DFG X X X X X X X X X X X X X X Vent Extension Kit KGAVE0101DNH X X X X X X X X X X X X X X Chimney Adapter Kit KGACA02014FC X X X X X X X X X X X KGACA02015FC X X X Natural to Propane Conversion Kit KGANP4601ALL X X X X...

Страница 6: ...75 1195 1265 1030 1580 1325 Cooling 895 1175 955 1240 1605 1385 1755 2005 LIMIT CONTROL SPST HEATING BLOWER CONTROL Solid State Time Operation BURNERS Monoport 2 2 3 3 3 4 4 4 GAS CONNECTION SIZE 1 2 in NPT GAS VALVE Redundant Manufacturer White Rodgers Minimum Inlet Pressure In wc 4 5 Natural Gas Maximum Inlet Pressure In wc 13 6 Natural Gas IGNITION DEVICE Hot Surface Gas input ratings are certi...

Страница 7: ...2230 LIMIT CONTROL SPST HEATING BLOWER CONTROL Solid State Time Operation BURNERS Monoport 5 5 5 6 6 7 GAS CONNECTION SIZE 1 2 in NPT GAS VALVE Redundant Manufacturer White Rodgers Minimum Inlet Pressure In wc 4 5 Natural Gas Maximum Inlet Pressure In wc 13 6 Natural Gas IGNITION DEVICE Hot Surface Gas input ratings are certified for elevations to 2000 ft 610 M For elevations above 2000 ft 610 M r...

Страница 8: ...installations must use Type B vent immediately after exiting the furnace except when KGAVG0101DFG is used in downflow position 4 Type B vent where required refer to Note 1 5 4 in 102 mm single wall vent must be used inside furnace casing and the KGAVG0101DFG Downflow Vent Guard Kit 6 Accessory Downflow Vent Guard Kit KGAVG0101DFG required in downflow installations with bottom vent configuration 7 ...

Страница 9: ... 8 9 HORIZONTAL RIGHT A02070 SEE NOTES 1 2 4 7 8 9 HORIZONTAL RIGHT A02069 SEE NOTES 1 2 4 7 8 9 HORIZONTAL LEFT A02064 SEE NOTES 1 2 4 5 7 8 9 HORIZONTAL LEFT A02065 SEE NOTES 1 2 4 5 7 8 9 HORIZONTAL LEFT A02066 SEE NOTES 1 2 4 5 7 8 9 HORIZONTAL LEFT A02067 58CTA CTX ...

Страница 10: ... 1320 1160 1465 1380 1260 1120 1385 1300 1195 1065 1285 1220 1120 1005 1175 1115 1025 925 1055 990 915 810 895 830 710 630 645 600 565 510 090 16 Bottom or Side s High Med High Medium Med Low Low 2060 1710 1470 1260 1030 2000 1695 1475 1265 1025 1930 1665 1450 1245 1020 1835 1585 1390 1225 990 1755 1480 1335 1165 940 1620 1390 1230 1090 890 1490 1245 1120 995 810 1315 1110 1005 880 720 1115 955 85...

Страница 11: ...05 1500 1295 1835 1640 1450 1265 1710 1550 1380 1210 1590 1465 1315 1150 1470 1360 1215 995 1335 1210 1005 865 1025 945 855 745 835 785 670 540 135 22 Bottom Only High Med High Med Low Low 2485 2195 1880 1640 2400 2150 1850 1635 2310 2090 1820 1615 2215 2000 1780 1585 2110 1920 1715 1530 2000 1825 1635 1465 1880 1720 1540 1370 1725 1565 1415 1255 1535 1405 1290 1150 1355 1255 1160 1040 Both Sides ...

Страница 12: ...e use of both side inlets a combination of 1 side and the bottom or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM FURNACE SIZE A CABINET WIDTH IN mm D SUPPLY AIR WIDTH IN mm E RETURN AIR WIDTH IN mm F CENTER LINE TOP AND BOTTOM FLUE COLLAR IN mm FLUE COLLAR IN mm SHIP WT LB KG FILTER MEDIA CABINET IN mm 045 08 14 3 16 360 12 9 16 319 12 11 16 322 ...

Страница 13: ...7 432 16 1 4 413 15 381 20 508 mm 21 533 20 1 4 514 19 483 24 610 mm 25 635 24 1 4 616 23 584 23 5 8 23 3 8 Furnace Side 23 3 4 Centerline Screw Slots 25 5 8 Duct Side 24 1 2 With Flanges Bent Out 23 1 8 Opening 5 3 4 C Opening with Flanges Bent In B 600 mm 594 mm 603 mm 146 mm 651 mm 622 mm 587 mm A00444 58CTA CTX 58CTA CTX ...

Страница 14: ...14 A08471 58CTA CTX ...

Страница 15: ... 2 15 14 090 14 115 60 1 127 104 8 2 34 10 3 15 14 090 16 115 60 1 127 104 9 9 28 8 5 15 14 090 20 115 60 1 127 104 12 9 34 10 3 20 12 110 12 115 60 1 127 104 8 2 34 10 3 15 14 110 16 115 60 1 127 104 10 1 28 8 5 15 14 110 22 115 60 1 127 104 13 7 32 9 7 20 12 135 16 115 60 1 127 104 10 2 27 8 2 15 14 135 22 115 60 1 127 104 14 5 30 9 1 20 12 155 20 115 60 1 127 104 15 0 29 8 8 20 12 Permissible l...

Страница 16: ...f 030 in 76 mm thickness minimum pre painted galvanized steel Two Speed Inducer Motor Two Speed Inducer motor shall be soft mounted to reduce vibration transmission Draft Safeguard Switch Draft Safeguard Switch blocked vent safeguard shall be factory installed to reduce the possibility of vent gas infiltration due to a blocked or restricted vent pipe Heat Exchangers Heat exchangers shall be a 4 Pa...

Отзывы: