68
Fig. 80 —
Single Enthalpy Curve Boundaries
CHECKOUT
Inspect all wiring connections at the economizer module’s termi
-
nals, and verify compliance with the installation wiring diagrams.
For checkout, review the Status of each configured parameter and
perform the Checkout tests.
NOTE: For information about menu navigation and use of the
keypad, see Interface Overview on page 58.
Power Up
After the W7220 module is mounted and wired, apply power.
Initial Menu Display
On initial start up, Honeywell displays on the first line and econo
-
mizer W7220 on the second line. After a brief pause, the revision
of the software appears on the first line and the second line will be
blank.
Power Loss (Outage or Brownout)
All set points and advanced settings are restored after any power
loss or interruption.
NOTE: All settings are stored in non-volatile flash memory.
Status
Use the Status menu (see Table 26) to check the parameter values
for the various devices and sensors configured.
NOTE: For information about menu navigation and use of the
keypad, see Interface Overview on page 58.
Checkout Tests
Use the Checkout menu (see page 62) to test the damper operation
and any configured outputs. Only items that are configured are
shown in the Checkout menu.
NOTE: For information about menu navigation and use of the
keypad, see Interface Overview on page 58.
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using the
▲ and ▼ buttons.
2. Press the
(Enter) button to select the item. RUN?
appears.
3. Press the
(Enter) button to start the test. The unit
pauses and then displays IN PROGRESS. When the test is
complete, DONE appears.
4. When all desired parameters have been tested, press the
(Menu Up) button to end the test.
The Checkout tests can all be performed at the time of installation
or at any time during the operation of the system as a test that the
system is operable.
TROUBLESHOOTING
Alarms
The economizer module provides alarm messages that display on
the 2-line LCD.
NOTE: Upon power up, the module waits 60 minutes before
checking for alarms. This allows time for all the configured devic
-
es (e.g. sensors, actuator) to become operational. The exception is
the SAT sensor which will alarm immediately.
ECONOMIZING
AVAILABLE
NOT AVAILABLE
ENTHALPY
RA
HUM (%RH)
RA
TEMP
TEMPERATURE
ABSOLUTE HUMIDITY
ES5
ES4
ES3
ES2
ES1
HL
P1
(T,RH)
P2 (T,RH)
SINGLE ENTHALPY
DUAL ENTHALPY
HIGH LIMIT
Table 37 —
Single Enthalpy and Dual Enthalpy High Limit Curves
ENTHALPY
CURVE
TEMP. DRY
BULB (F)
TEMP.
DEWPOINT (F)
ENTHALPY
(btu/lb/da)
POINT P1
POINT P2
TEMP. (F)
HUMIDITY
(%RH)
TEMP. (F)
HUMIDITY
(%RH)
ES1
80
60
28.0
80
36.8
66.3
80.1
ES2
75
57
26.0
75
39.6
63.3
80.0
ES3
70
54
24.0
70
42.3
59.7
81.4
ES4
65
51
22.0
65
44.8
55.7
84.2
ES5
60
48
20.0
60
46.9
51.3
88.5
HL
86
66
32.4
86
38.9
72.4
80.3
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Be sure to allow enough time for compressor start-up and
shutdown between checkout tests so that you do not short-
cycle the compressors.
Содержание 48TC series
Страница 40: ...40 Fig 56 Typical IGC Wiring Diagram...
Страница 41: ...41 Fig 57 Integrated Gas Control IGC Board RED LED STATUS...
Страница 47: ...47 Fig 62 RTU Open Overlay for Economizer Wiring...
Страница 48: ...48 Fig 63 VFD Overlay for W2770 Controller Wiring...
Страница 96: ...96 Fig C 48TC D17 D30 Control Diagram 208 230 3 60 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS...
Страница 97: ...97 Fig D 48TC D17 D30 Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS...
Страница 98: ...98 Fig E 48TC D17 D30 Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS...
Страница 99: ...99 Fig F 48TC D17 D30 Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS...
Страница 100: ...100 Fig G 48TC D17 D30 Control Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Страница 101: ...101 Fig H 48TC D17 D30 Power Diagram 208 230 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Страница 102: ...102 Fig I 48TC D17 D30 Power Diagram 460 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Страница 103: ...103 Fig J 48TC D17 D30 Power Diagram 575 3 60 with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Страница 104: ...104 Fig K PremierLink System Control Wiring Diagram APPENDIX D WIRING DIAGRAMS...
Страница 105: ...105 Fig L PremierLink System Control Wiring Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Страница 106: ...106 Fig M RTU OPEN Wiring Diagram APPENDIX D WIRING DIAGRAMS...
Страница 107: ...107 Fig N RTU OPEN Wiring Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Страница 109: ......