Carrier 40WAW007 Скачать руководство пользователя страница 5

5

5.

Make sure the mounting plate is leveled and flush with
the wall.

6.

Secure the unit in position by lifting the unit over the
mounting plate. Make sure the hook on the mounting
plate aligns with the slot on the back of the unit. To ensure
proper fit, slide the unit sideways. If the unit is locked in
the correct position, it should not move.

Step 4 — Connect Piping

GENERAL

1.

For condensate and refrigerant piping, lift the unit from
bottom, making sure the unit is still attached to the
mounting plate at the top. See Fig. 5. 

2.

Introduce temporary cushioning material to maintain the
space needed to connect the piping and to avoid damage
to unit and wall. See Fig. 5.

3.

When the piping connections are completed, remove the
cushioning material and make sure the unit is flush with
the wall.

CONDENSATE PIPING  — The  unit  is  supplied  with  a

3

/

4

-in. OD drain connection to connect copper or PVC drain

piping. When installing condensate piping, follow these recom-
mendations:

• Condensate drain should slope downward in the direc-

tion of condensate flow.

• DO NOT install any U bends or dump the condensate

line in a sump filled with water. See Fig. 6.

• When multiple units are connected to a common conden-

sate drain, ensure that the drain is large enough to accom-
modate the volume of condensate from all units. It is also
recommended to have an air vent in the condensate pip-
ing to prevent any air locks.

• Condensate piping must not be installed where it may be

exposed to freezing temperatures.

• Condensate piping can be routed in one of the four direc-

tions shown in Fig. 7.

REFRIGERANT PIPING

When connecting from an indoor unit to an outdoor unit,

follow these procedures:

• Check maximum height drop and length of refrigerant

piping between the indoor and outdoor unit. If the differ-
ence between them is more than 33 ft, consider mounting
the outdoor unit above indoor unit.

• Refrigerant piping connection between indoor and out-

door units should be performed once the units are
secured at their respective installation locations.

• The refrigeration piping starts at the indoor unit and ends

at the outdoor unit. 

• The number of bends in the refrigeration piping must be

fewer than 15.

• The refrigerant piping should be dry and free of dust and

other impurities.

• The bending angle of the refrigerant pipe should not

exceed 90 degrees and the bending radius should be as
large as possible to prevent any breakage in piping.

• Use proper cutting and flaring tools to avoid leakage.

• Before insulating the suction and liquid refrigeration

pipes, perform pressure and leak tests. For details, see
the outdoor unit installation manual. Insulating both suc-
tion and liquid refrigerant pipes is recommended. 

• Vacuuming and charging of the system should be carried

out as described in the outdoor unit installation manual.

Step 5 — Complete Electrical Connections —

Installation of wiring must conform with local building codes
and with National Electric Code ANSI/NFPA 70, latest edi-
tions. Units must be electrically grounded in conformance with
the code. In Canada, wiring must comply with CSA C22.1,
Electrical Code.

CUSHIONING
MATERIAL

HOOK

A40-1707

Fig. 5 — Piping Connection

a40-1708

Fig. 6 — Condensate Piping, Poor Installation

CAUTION

When connecting from an indoor unit to an outdoor unit,
the isolation valve at the outdoor unit should be in closed
position throughout the refrigerant piping process. Failure
to follow this procedure may result in equipment damage.

WARNING

Electrical shock can cause personal injury and death. Dis-
connect power supply before making wiring connections.
There may be more than one disconnect switch. Tag all dis-
connect locations to alert others not to restore power until
work is completed.

 

 

RIGHT PIPING

RIGHT BACK PIPING

LEFT BACK PIPING

LEFT PIPING

A40-1709

Fig. 7 — Condensate Pipe Routes

Содержание 40WAW007

Страница 1: ... 1 Understand the signal words DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in personal inju ry or death CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage Recognize safety information This is the safety alert...

Страница 2: ...eted Failure to follow these proce dures may result in damage to equipment For information about replacement oil type and viscosity see the Single Phase VRF Outdoor Unit installation instructions UNIT 40WAW 007 009 012 015 018 POWER SUPPLY V Ph Hz 208 230 1 60 COOLING CAPACITY Btuh 7 500 9 500 12 000 15 000 19 000 HEATING CAPACITY Btuh 8 500 10 900 13 600 17 000 21 000 INDOOR FAN MOTOR Type AC Mot...

Страница 3: ...ostats controller etc are accounted for whether packaged separately or shipped at a later date Any hidden damage should be re corded a claim should be filed with the transportation compa ny and the factory should be notified In the event a claim for Fig 1 Model Number Nomenclature LEGEND VRF Variable Refrigerant Flow 40 WA W 007 3 40 Indoor Unit Product Type WA Single Phase VRF Voltage V Ph Hz 3 2...

Страница 4: ...lable power source Refer to unit nameplate and wiring diagram In addition Check all tags on unit to determine if shipping screws are to be removed Remove screws as directed Rotate the fan wheel by hand to ensure that the fan is unrestricted and can rotate freely Check for shipping damage and fan obstructions Adjust blower motor as required Step 2 Position the Unit Select the unit position with the...

Страница 5: ...e than 33 ft consider mounting the outdoor unit above indoor unit Refrigerant piping connection between indoor and out door units should be performed once the units are secured at their respective installation locations The refrigeration piping starts at the indoor unit and ends at the outdoor unit The number of bends in the refrigeration piping must be fewer than 15 The refrigerant piping should ...

Страница 6: ...ntrol wiring do not cross as this might cause disturbance on the controls side See Fig 8 for wiring diagram WARNING All units must be wired strictly in accordance with the wir ing diagram furnished with the unit Any wiring different from the wiring diagram could result in personal injury and property damage CAUTION Any original factory wiring that requires replacement must be replaced with wiring ...

Страница 7: ...r C Fan Capacitor CS Water Level Switch DM Pump Motor EEV Electronic Expansion Valve FM Indoor Fan GM Swing Motor HEAT Auxiliary Heater T1 Inlet Air Temperature T2 Coil Temperature T2B Evap Outlet Temperature in Cooling Mode TR Transformer XP1 7 Plug XS1 7 Jack XT1 2 Terminal Block Optional Component or Field Wiring ...

Страница 8: ...le and 4 pin connector from electrical box of indoor unit see Fig 10 For setup in structions refer to the controller installation manual WIRED REMOTE CONTROLLER NON PROGRAM MABLE To connect wired remote controller thermostat to the indoor unit use 5 core shielded cable and 5 pin connec tor from unit display panel see Fig 11 For setup instructions refer to the controller installation manual CENTRAL...

Страница 9: ...ser fan is in operation c Indicator light is showing normal operation and no er ror is indicated NOTE If unit is turned off or restarted there is a 3 minute time delay for the compressor to start from the time power is restored MAINTENANCE EVERY 3 MONTHS Check air filter condition Clean or replace if necessary EVERY 6 MONTHS Follow 3 month maintenance sched ule In addition Clean condensate tray wi...

Страница 10: ... short circuited or disconnected Check or reconnect signal wire Signal wire order is incorrect Correct signal wire order Signal wires crossing over high voltage power wires Separate and distance the signal wire from high voltage power wires Signal wire close to electromagnetic source Distance signal wires from electromagnetic source Signal wire length exceeds 360 ft Reduce the signal wire length P...

Страница 11: ...ig B SW2 Settings ON OFF 1 2 3 4 a40 1923 POSITION 1 2 COIL TEMPERATURE HEATING MODE OFF OFF Coil Temperature 59 F No Heat Default OFF ON Coil Temperature 68 F No Heat ON OFF Coil Temperature 75 2 F No Heat ON ON Coil Temperature 78 8 F No Heat ON OFF 1 2 3 4 a40 1924 POSITION 3 4 MODE FAN STATUS SP REACHED SP Set Point OFF OFF Cooling Mode Fan On SP Reached Heating Mode Fan On SP Reached Default ...

Страница 12: ...ight to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53400030 01 Printed in U S A Form 40WAW 2SI Pg 12 4 16 Replaces 40WAW 1SI Carrier Corporation 2016 ...

Отзывы: