OPERATION MODES AND FUNCTIONS
Abbreviation
Table 14 — Unit Element Abbreviations
Safety Features
Compressor Three-Minute Delay at Restart
Compressor functions are delayed for up to ten seconds upon the first
start-up of the unit, and are delayed for up to three minutes upon
subsequent unit restarts.
Automatic shutoff based on discharge temperature
If the compressor discharge temperature exceeds 226
F (108
C) for
nine seconds, the compressor ceases operation.
Automatic shutoff based on fan speed
If the indoor fan speed registers below 300RPM or over 1500RPM
for an extended period of time, the unit ceases operation and the
corresponding error code appears on the indoor unit.
Inverter module protection
The inverter module has an automatic shutoff mechanism based on the
unit’s current, voltage, and temperature. If the automatic shutoff is
initiated, the corresponding error code appears on the indoor unit and
the unit ceases operation.
Indoor fan delayed operation
• When the unit starts, the louver is automatically activated and the
indoor fan will operate after a period of setting time or when the
louver is in place.
• If the unit is in the
HEATING
mode, the indoor fan is regulated by
the anti-cold wind function.
Compressor Preheating
Preheating is automatically activated when the T4 sensor is lower than
the setting temperature.
Sensor redundancy and automatic shutoff
• If one temperature sensor malfunctions, the air conditioner
continues operation and displays the corresponding error code,
allowing for emergency use.
• When more than one temperature sensor malfunctions, the air
conditioner stops.
Display Function
Unit Display Functions
Fig. 13 — Unit Display Functions
Table 15 — Unit Function Displays
ABBREVIATION
ELEMENT
T1
Indoor room temperature
T2
Evaporator Coil temperature
T3
Condenser Coil temperature
T4
Outdoor ambient temperature
Tsc
Adjusted setting temperature
TP
Compressor discharge temperature
FUNCTION
DISPLAY
Temperature
Set temperature value
Temperature (FAN and DRYING mode)
Room temperature
Activation of Timer ON, Fresh, Swing,
Turbo, or Silent
ON
(3S)
Cancellation of Timer OFF, Fresh, Swing,
Turbo, or Silent
OF
(3S)
Defrost
dF
Warming in heating mode
cF
Self-clean
SC
Heating in room temp under
46°F (8°C) or 54°F (12°C)
FP
Fresh
(Not available on
these systems)
ECO function
Wi-Fi Control
The current operation power
(Not available on these systems)
kW