38MBR: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
32
High Temperature Protection of Compressor Top Diagnosis and Solution (P2)
Troubleshooting
Error Code
P2
Malfunction decision conditions
If the sampling voltage is not 5V, the LED displays the failure.
Supposed Causes
• Power supply problems
• System leakage or block
• PCB faulty
Power
OFF
.
Wait 10 minutes and re-start the unit.
No
Yes
Check the compressor temperature.
Is it within acceptable parameters
?
Yes
Check the refrigerant system.
/ƐŝƚĨƵŶĐƟŽŶŝŶŐƉƌŽƉĞƌůLJ͍
Replace the outdoor control PCB.
Yes
Clear up the air inlet and outlet or the heat
exchanger of the indoor and outdoor units.
Yes
ŶƐƵƌĞĂƉƌŽƉĞƌĐŽŶŶĞĐƟŽŶ͘
No
Check the indoor and outdoor unit’s
ĂŝƌŇŽǁƐLJƐƚĞŵƐ͘
Does a problem exist
?
Check the overload protector.
Is it properly wired
?
No
Yes
Measure the resistance between the
two OLP ports.
Is it zero
?
No
Replace the OLP.
Yes