44
15.9 - Refrigerant
30RQS/RQSY units operate with refrigerant R-410A.
15.10 - High-pressure safety switch
30RQS/RQSY units are equipped with automatically reset
safety pressure switches on the high-pressure side. For the
alarm acknowledgements refer to the 30RB/RQ Touch Pilot
Junior control manual).
15.11 - Storage tank
30RQS/RQSY units are equipped with mechanically welded
storage tanks that permit storing the excess charge when the
unit operates in heating mode.
15.12 - Four-way valve
This permits reversal of the cycle for operation in cooling
and heating mode and during defrost cycles.
15.13 - Control box
The control box of the 30RQS/RQSY units is equipped with
electric heaters to prevent condensation during operation at
low outside temperatures. They are installed on the top of
the control box on the outside, and are covered by a thermal
insulation layer. These heaters are switched on, based on the
outside temperature.
15.8 - Water evaporator/condenser
The evaporator/condenser is a plate heat exchanger with one
or two refrigerant circuits. The water connection of the heat
exchanger is a Victaulic connection. It has a thermal insulation
of 19 mm thick polyurethane foam and includes frost protection,
as standard.
The products that may be added for thermal insulation of
the containers during the water piping connection procedure
must be chemically neutral in relation to the materials and
coatings to which they are applied. This is also the case for
the products originally supplied by Carrier SCS.
NOTES - Monitoring during operation:
• Follow the regulations on monitoring pressurised
equipment.
•
It is normally required that the user or operator sets
up and maintains a monitoring and maintenance file.
•
If there are no regulations or to complement them follow
the control programmes of EN 378.
•
If they exist follow local professional recommendations.
•
Regularly check for possible presence of impurities (e.g.
silicon grains) in the heat exchange fluids. These
impurities maybe the cause of the wear or corrosion by
puncture.
•
The reports of periodical checks by the user or operator
must be included in the supervision and maintenance file.
According to the Regulation No. 640/2009 and amendment 4/2014 implementing Directive 2005/32/EC with regard to
ecodesign requirements for electric motors.
Product/option
30RQS standard* or
with option 15LS
30RQS standard**
30RQSY standard or 30RQS
standard with option 42
Motor type
Dual-speed
asynchronous
Dual-speed
asynchronous
Asynchronous
Number of poles
8
6
6
Nominal input frequency
Hz
50
50
60
Nominal voltage
V
400
400
400
Number of phases
3
3
3
Motor included in the application domain of the regulation
640/2009 and amendment 4/2014
No
No
No
Sales leaflet for exemption
Article 2.1
Article 2.1
Article 1.2.c).(ii)
Ambient air temperature for which the motor is specifically
designed
°C
68.5
68.5
68.5
* Only for sizes 039-050 and 080-120
** Only for sizes 060-078 and 140-160