29
NOTE: Use the same baud rate for all controllers on the network segment. Wire the controls on a BACnet MS/TP ARC156 network segment in a daisy-
chain configuration. If the AppController is at either end of a network segment, connect a BT485 (purchased separately) to the AppController. The
communication selection DIP Switches are defined on the AppController (see Fig. 32).
Table 7 —
CCN Communication Bus Wiring
Step 6 —
Install Accessories/Optional Equip-
ment
LOW AMBIENT OPERATION
If outdoor ambient operating temperatures below 20°F (–6.67°C)
and the wind velocity is anticipated to be greater than 5 mph
(8 km/h), wind baffles are required. If required, the wind baffles
are field fabricated and installed. Two are required, one for each
end. Wind baffle should be constructed with minimum 18-gage
galvanized sheet metal or other suitable corrosion-resistant materi
-
al with cross breaks for strength. See Fig
31. Use field-supplied
screws to attach baffle to the corner posts of the machine. Be sure
to hem or turn a flange on all edges to eliminate sharp edges.
Mount a baffle on each end of the unit. Use the upper notches to
locate the baffle. This reduces the risk of damaging a coil while
drilling. Loosen the upper corner post bolts and slide the baffle un
-
derneath the flange bolt. Tighten the bolt. Drill holes in the bottom
of the flange of the baffle and mount with two screws to secure the
bottom to the corner post.
FIELD-INSTALLED ACCESSORY INSTALLATION
For applications requiring special accessories, the following pack
-
ages are available: hail guard and security grilles. For installation
details, refer to separate installation instructions supplied with
these accessory packages.
Table 6 —
Wiring Specifications
CABLE
22 AWG or 24 AWG, low capacitance, twisted stranded, shielded copper wire
MAXIMUM LENGTH
2000 feet (610 meters)
Set the communication type and baud rate.
For...
Set Communications
Selection jumper to...
Set DIP switches 1 and 2 to...
Set DIP switches 3 and 4 to...
MS/TP
BACnet MS/TP
The appropriate baud rate. See the
MS/TP Baud diagram on the con-
troller.
Off/Off
ARC156
BACnet ARC156
N/A. Baud rate will be 156 kbps
regardless of the DIP switch set-
tings.
Off/Off
MANUFACTURER
PART NUMBER
Regular Wiring
Plenum Wiring
Alpha
1895
—
American
A21451
A48301
Belden
8205
884421
Columbia
D6451
—
Manhatten
M13402
M64430
Quabik
6130
—
WARNING
Disconnect all power to the unit before performing
maintenance or service. Electrical shock and personal injury
could result.
CAUTION
To avoid damage to the refrigerant coils and electrical
components, use extreme care when drilling screw holes and
screwing in fasteners.
Содержание 09FC020
Страница 8: ...8 Fig 5 09FC 020 Unit Dimensions...
Страница 9: ...9 Fig 6 09FC 030 Unit Dimensions...
Страница 10: ...10 Fig 7 09FC 040 Unit Dimensions...
Страница 11: ...11 Fig 8 09FC 050 Unit Dimensions...
Страница 12: ...12 Fig 9 09FC 060 Unit Dimensions...
Страница 13: ...13 Fig 10 09FC 070 Unit Dimensions...
Страница 14: ...14 Fig 11 09FC 080 Unit Dimensions...
Страница 69: ......