READ AND SAVE THESE INSTRUCTIONS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

FAN DISTRIBUTION UNITS

Model HXBG

I.  MOUNTING
 NOTE: 

 

For Fan Distribution Units shipped attached to humidifiers also refer to Carnes Humidifier

  Catalog 

900-0119.

The fan distribution unit must be mounted securely on a level and plumb surface at least four feet below the 
ceiling to prevent steam from condensing on the ceiling surface. Allow 30 feet in front of the HXBG for the steam 
to be absorbed into the air. Do not mount the units above any item that would be damaged if a water leak were 
to develop. The humidifier or fan distribution unit must never be mounted outside or where it may be exposed to 
freezing temperatures.
For remote mounted fan distribution units see Tables 1 and 2 below:

Table 1 - Maximum Operating Weight

Table 2 - Fastener Recommendations.

II.  CONNECTING THE STEAM HOSE - Remote Units
 

 

  Copper or Brass Tube is the only acceptable substitute

 

 

 

for Carnes Steam Hose or Condensate Hose

1.  For guidelines on typical steam hose installation refer to Humidifier Installation, Operation and Maintenance

 Instructions.
2.  The steam hose should be installed so there is a continuous rise from the humidifier to the bottom connection 
  of the remote unit. Support the steam hose at intermediate points to prevent dips or pockets. If there are any low 
  point add a “T” fitting to drain condensate.
3.  Any turns should have a minimum of 8” to prevent the hose from kinking.
4.  Fasten the steam hose to the connection point on the manifold of the remote unit with one of the hose clamps 
 provided.
5.  Push the steam hose through the opening on the top of the humidifier cabinet and slip over the outlet stub on
  top of the cylinder. Fasten with the hose clamp provided.

III.  CONNECTING THE CONDENSATE RETURN HOSE

     - Remote Mounted Units

1.  Fasten the condensate return line to the connection point on the manifold of the remote unit with the hose clamp 
 provided.
2.  Follow the steam hose to the humidifier cabinet and secure the return line to the steam hose.
3.  Connect the condensate return line from the fan distributor unit to the condensate return line at the top of the
 humidifier 

cabinet.

4.  If it is impossible to maintain a drop to the top of the cabinet, it is permissible to run the condensate return
  line directly to the air gap drain fitting or some other common drain. If condensate is run to a common drain, a 
  trap must be incorporated close to the drain to prevent steam and/or hot  water from entering.

 

Model Weight 

(lbs.)

 HXBG 

21

 

Type of Wall 

4 Fasteners Required

  Wood Studs or Solid Wall 

1/4” Lag Screws, 1” minimum length

(Continued on reverse side of sheet)

COPYRIGHT © 2013 CARNES COMPANY  

ALL RIGHTS RESERVED

SUPERSEDES 16812-A

 16812-B, Page 1

CARNES COMPANY    448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040    Phone: (608)845-6411    Fax: (608)845-6504    www.carnes.com