Installation Instructions

and Accessory Applications

 

TA04617   C      Page 1 of 4

Mounting Feet:

This enclosure is shipped with its mounting brackets and 
installation screws packaged inside. Bracket design permits this 
enclosure mounted with major dimension vertical. The purchase 
of mounting feet (Part No. CJB 159) permits this enclosure to 
be mounted with the major dimension horizontal to the ground. 
(Cut out style only.) Use flathead screw (1/4-20x1/2”) to secure 
brackets to enclosure.  Securely tightening the mounting brackets 
will insure positive positioning of the enclosure. Torque limits for 
these flathead screws are 50 in-lbs (maximum).

Covers:

The fastenings for the cover are captive slotted stainless steel 
filister head screws (10-32), which are factory installed. The 
torqued down limits for these screws are 25 in-lbs (maximum).

Installation of Conduit:

1)  CONDUIT HOLES:

Cut holes in enclosure (when required) at the desired location. 
The use of a standard hole saw is the preferred method.
For proper location of hubs, prepare a paper template with 
the recommended B x C (End Installation) or A x C (Side 
Installation) dimensions.  Reference the table below for the 
specific enclosure size. Position a standard hole saw anywhere 
within the rectangle and drill (care should be taken to prevent 
damaging the bosses). The maximum hub and hole size varies 
with the size of the enclosure.
Reference point F should always be centered midway
between the bosses.
For side installation on hinge models, hinge side, conduit holes 
should be positioned a minimum of 1” from bottom of hinge 
assembly. All other dimensions are the same as on hingeless 
models.
C Series Enclosures do not have the same conduit placement 
requirements. It is recommended that hole locations be 
centered on the sides a minimum of 1-1/2” from the bottom 
and 2-1/2” from the top.

TEMPLATE DIMENSIONS FOR LOCATION                                         

OF ELECTRICAL FITTING IN CUTOUT BOXES

PS, PJ, CS, CJ, CV & CC MODELS

Catalog 

Number

Inside Box 

Size

Side 

Installa-

tion

A

End      

Installa-

tion

B

C

Long 

Side 

Max. 

Conduit 

Size

Short 

Side 

Max. 

Conduit 

Size

CS665

6x6x5-3/4

5-1/4

2-3/4

2-1/4

1-1/2

1-1/2

CS863

8x6x3-1/2

7-1/8

2-3/4

1-5/8

1-1/2

1-1/2

CS1085

10x8x5-3/4

4

4-3/4

2-1/4

1-1/2

1-1/2

CS12106

12x10x6-3/4

4-3/4

6-3/4

3-3/4

2-1/2

2-1/2

CS14126

14x12x6-3/4

6

8-3/4

4-1/2

3-1/2

3-1/2

CS16147

16x14x7-1/2

6-3/4

10-3/4

4-1/2

3-1/2

3-1/2

Figure 1

2)  CONDUIT CONNECTIONS:

a.  Metallic Conduit:

1. Secure the conduit connector (hub) onto the conduit, as 

the hub shall be connected to the conduit BEFORE the 
hub is connected to the enclosure.

2.  Secure conduit connector (hub) into the prepared 

enclosure hole using the connector locknut.

3.  Attach grounding bushing having the proper size ground 

wire lug over the connector locknut.

CAUTION

In accordance with the National Electrical Code, the 
enclosure must be bonded between the grounding 
bushings or between the grounding bushings and 
the equipment grounding terminal (when provided).

Figure 2

Carlon Watertight Hubs

(See Hub Section)

b.  Nonmetallic Conduit (see illustration above): Secure 

conduit to the conduit connector (hub), and the 
hub shall be connected to the conduit BEFORE the 
hub is connected to the enclosure, then secured 
into the prepared hole using the connector locknut.          

NOTE:

 Ground bushing not required when 

attaching to nonmetallic conduit.

English

Содержание CS863

Страница 1: ... conduit holes should be positioned a minimum of 1 from bottom of hinge assembly All other dimensions are the same as on hingeless models C Series Enclosures do not have the same conduit placement requirements It is recommended that hole locations be centered on the sides a minimum of 1 1 2 from the bottom and 2 1 2 from the top TEMPLATE DIMENSIONS FOR LOCATION OF ELECTRICAL FITTING IN CUTOUT BOXE...

Страница 2: ... will permit the snap tang to clear the molded interference Then pull the hinge cap from the slot Figure 3 Figure 4 WARRANTY Thomas Betts sells this product with the understanding that the user will perform all necessary tests to determine the suitability of this product for the user s intended application Thomas Betts warrants that this product will be free from defects in materials and workmansh...

Страница 3: ...charnières Toutes les autres dimensions sont les mêmes que sur les modèles sans charnières Les boîtiers de série C n ont pas les mêmes exigences de placement de conduit Il est recommandé que l emplacement des trous soit centré sur les côtés à plus de 1 1 2 po du bas et 2 1 2 po du haut DIMENSIONS DU GABARIT POUR L EMPLACEMENT DE RACCORD ÉLECTRIQUE DANS DES BOÎTES DE DISJONCTEUR MODÈLES PS PJ CS CJ...

Страница 4: ...le et pousser la pointe avec le côté du boîtier Cela permettra de dégager le tenon à pression Puis retirer le capuchon de charnière de la fente Figure 3 Figure 4 GARANTIE Thomas Betts vend ce produit à condition que l utilisateur se charge des tests nécessaires pour déterminer si le produit convient à l application qu il veut en faire Thomas Betts garantit que ses produits sont libres de vices de ...

Отзывы: