  A control with a minimum10-Second Post-

Purge MUST be used with this Damper Motor 

to ensure the High-Fire Damper is closed at 

the end of the call for heat/at the start of your 

next call for heat.

  Installer/servicer – Except where specifically stated 

otherwise, this Supplement must be used only by a 

qualified service technician. Follow all guidelines 

in the Burner Manual and Boiler Manual. Failure 

to comply with this or other requirements in this 

manual could result in severe personal injury, death 

or substantial property damage.

©

 

Copyright 2020 – Carlin Combustion Technology                                    

Tech  support  800-989-2275      

carlincombustion.com

 

MODEL

 

SQN71

 

 

Damper 

Actuator 

Supplement

Quick Reference Guide

Reference 

Number

Description

1

Disengaging Pin (In the engaged 

position)* 

2

Adjustment Wrench 

3

Cam Stack 

4

Damper Position Scale ( Damper po-

sition indicated by slit in the white ring 

5

Red Cam (High-Fire) 

6

Blue Cam (Low-Fire) 

7

Transition Cam (Shares adjustment 

scale with Blue Cam)** 

*

* To rotate damper and cam stack by hand, disengaging pin must be pushed in. The pin 

must be out when the burner is operating

**Transition cam sets the transition point between Low Fire and High Fire