Installation and adjustment instructions 

 

vent-captor 

3205.13/.12 S310/45 

 

Please read carefully: No liability can be accepted for damage caused by improper use of the captor. 

 

  
 

 1.0 Installation:

 

 With fitting G ½“ A (to be ordered separately), unit see drawing no. K722559 

  

 1.1 Installation depth

 

 Dependent on duct or pipe diameter, min. 15 mm. 

  

 

1.2 Flow direction

 

 See under „Positioning“ in „Technical Information“ 

  
 

2.0 Electrical connection:

 

 See „Connection diagram“ in „Technical Information“ 

  

 3.0 Switching characteristics 

  
 3.1 Starting override time 

 

 

The thermal time

 

delay applies to a cold unit.  

 

3.2 Switching delay 

The time delay of the vent-captor is defined by the rate of change of flow speed relative to the set-point. 

This time delay is not constant, the faster the change, the shorter the time delay. Depending upon  
adjustment it varies from approx. 1 sec. to more than 5 sec. (3205.13/.12 S310/45). 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 t 

(s) 

 60 

 50 

 40 

 30 

 20 

 10 

 0 

0.1     0.2      0.3      0.4      0.5     0.6     0.7     0.8     0.9      1.0 

Adjustable set-point   (m/s) 