Capetti Elettronica WSD12PS-4AI Скачать руководство пользователя страница 7

WSD12PS-4AI 

User Manual

 

 

 

 

 

PAGE   7

 

 

WA0285E_WSD12PS-4AI_User Manual_R06 V6.0 

 

www.

capetti

.it 

8.

 

Wireless device user interface. 

The user interface consists of a “virtual” button that can be activated using the

 

WineCapKey 

and of a two-colours led. 

To give a command, user must approach the 

WineCapKey

 

to the device’s sensible area and keep it in that position.; the following picture

 (

Picture 6 

- WineCapKey positioning

shows device’s sensible points

 

 

 

 

 

 

 

 

 

The following COMMAND table describes the available commands:  

WIRELESS MODE COMMAND table   

Flash count 

Command 

Description 

1 flash 
  

STATUS 

Shows the device STATUS. As answer the led perform a flash sequence as reported in 
the  STATUS  table.  If  the  device  is  performing  the  TEST  (

refer  to  TEST  command

)  this 

command stops it.

 

2 flashes 
 

TEST 

Enter in TEST mode and transmits status and measurements every 5 seconds. If the 
device  is  in  STANDBY  mode  or  it  is  out  of  radio  range,  this  command  forces  the 
connection procedure to the WSN and the return to the operative mode. The TEST 
stops  after  120  seconds.  During  TEST,  the  led  continuously  shows  the  STATUS  to 
monitor the received radio signal quality. 
CAUTION: Measures acquired during TEST phase are NOT saved. 

3 flashes 
 

ENROLL 

Association to the network: must be used when the device has not yet been included 
in  a  network,  starts  the  entry  and  association  procedure  to  the  gateway  (

refer  to 

WineCap System - User Manual R30

). 

4 flashes 

 

+ 4 flashes 

 

STANDBY 

Temporary device deactivation: the device is stopped. The sampling process and the 
radio are/is. turned off losing the connection to the network. To reactivate, a TEST 
command is necessary. The STANDBY command must be given twice to confirm it: at 
the first sequence the led flashes alternating RED and GREEN lights, waiting for the 
second  confirm  sequence  within  15  seconds.  At  the  command  execution  the  led 
flashes as the STANDBY status (

refer to 

Picture 8 - Status table - Radio signal quality

). 

5 flashes 

 

+ 5 flashes 

 

FACTORY RESET 

The device performs the memory deleting procedure and goes in STOP status. All 
samples, configuration and wireless network data associated are LOST. To reactivate 
the  device  a  new  association  and  configuration  procedure  is  necessary  (

ENROLL 

command

). Also in this case, the FACTORY RESET command must be given twice to 

confirm it. At the command execution the led flashes as the “PROBE/DATALOGGER 
NOT ASSOCIATED” status

 (

refer to “

Picture 8 - Status table - Radio signal quality

). 

5 flashes 

 

+ 3 flashes 

 

LOGGER 

NO WSN 

As  the  previous  command  but  performs  only  the  WSN  deleting  procedure  and 
disassociate from the gateway. The device enters in LOGGER STAND ALONE mode: 
data are kept, and the sampling activity CONTINUES with previous setup. Command 
must  be  given  with  2  sequences:  5  flashes  and  then  3  flashes.  At  the  command 

execution wait for the device reboot.  At the STATUS command, “

LOGGER

” will be the 

answer (

refer to 

Picture 9 - Stand-alone device - Status table

). A new association (

ENROLL 

command

) is possible to a new gateway. 

Picture 7 - Command table

 

Picture 6 - WineCapKey positioning 

LED 

WineCapKey 

Содержание WSD12PS-4AI

Страница 1: ...WSD12PS 4AI User Manual ...

Страница 2: ...p to 100mA distributed on 4 analog channels Measurements acquired are expressed in percentage of full scale 2 Channel description Picture 1 Product image SHIELD shield cable connection PS INPUT datalogger generated voltage negative pole Input signal negative reference INPUT Signal input 0 25mA 0 5Vdc 0 10Vdc 0 25Vdc Full scale selectable using scale jumpers PS datalogger generated voltage positive...

Страница 3: ...c 100mA default Picture 3 Jumper positions Removing jumper J10 Errore L origine riferimento non è stata trovata voltage generation on pin PS of the terminal block is disabled This situation may be useful in case the DC voltage is not necessary Consequently the battery life is increased 4 Full scale setting The measurement s full scale selection is done positioning a jumper on the proper strip 0 25...

Страница 4: ...PS 4AI can be programmed using WineCapManager to supply a warm up time variable from 1 default to 32 seconds Be sure that the device is linked to its gateway refer to 10 Installation procedure Run WineCapManager and open the plant related database If the database doesn t exist and the gateway is not properly licensed on connected PC refer to WineCap System User Manual R30 From the WineCapManager m...

Страница 5: ...ww capetti it Click on InfoReq button Select the card Calibration Modify the Zero field with the desired warm up value default 1 maximum 32 The inserted value is expressed in seconds and represents the duration of output power supplied to transducer net off 0 4s of tolerance ...

Страница 6: ...ociate it make reference to the WineCap System User Manual R30 software manual It is necessary to use the WineCapManager software on the PC connected to the gateway that will be linked with the device b USB Logger Mode For this operation mode stand alone with data downloads through USB the connection with the PC and the WineCapManager running on it is necessary to modify the device s operation mod...

Страница 7: ...flashes STANDBY Temporary device deactivation the device is stopped The sampling process and the radio are is turned off losing the connection to the network To reactivate a TEST command is necessary The STANDBY command must be given twice to confirm it at the first sequence the led flashes alternating RED and GREEN lights waiting for the second confirm sequence within 15 seconds At the command ex...

Страница 8: ...TUS RADIO SIGNAL QUALITY 5 green flashes ACTIVE Radio signal Excellent 4 green flashes ACTIVE Radio signal Good 3 green flashes ACTIVE Radio signal Fair 2 amber flashes ACTIVE Radio signal Sufficient 1 red flash ACTIVE Radio signal Insufficient 1 red flash 2 long OUT OF RANGE Network searching 2 red flashes 2 long STANDBY Radio off No Logging Short long short red flashes series FACTORY RESET Devic...

Страница 9: ...time you can issue the STANDBY command refer to Picture 7 Command table It corresponds to the command number 4 and must be issued twice to confirm the operation Position the WineCapKey in the spot indicated in Picture 6 WineCapKey positioning and wait for four AMBER flashes then remove the WineCapKey from device Verify that the device asks for confirmation of STANDBY command with alternate GREEN R...

Страница 10: ... up to 100mA Selectable onboard using jumpers Warm up time From 1 default to 32 seconds Selectable using WineCapManager Sampling interval Selectable from one minute to 24 hours 60 minutes default Datalogger capacity 64 000 samples for each channel Working temperature Operative 30 C 60 C Warehousing 40 C 70 C Radio frequency ISM 868MHz Radio coverage Up to 6Km in line of sight can be extended using...

Страница 11: ...ion voltage measures on distances exceed 15 20 meters are subjected to electromagnetic disturbances 0 25mA inputs have a superior electromagnetic compatibility EMC Avoid passage in cavities with power or high voltage cables The protection and safety measures and the warranty provided by the Manufacturer with the equipment may be compromised if it s used in a manner that does not comply with this u...

Страница 12: ...nic devices The WEEE logo on the label indicates that this product is compliant with the WEEE EC Directive This symbol valid only in the European Union countries indicates that the product it is applied to MUST NOT be discarded with ordinary household or industrial waste but must be sent to an authorized reception point The end user should contact the device provider either the manufacturer or the...

Отзывы: