CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
Group d3
:
Torque Control
d3.00
①
Range: 0 ~ 1
Default: 0
Speed/Torque
control selection
It is used to select motor control mode in vector control.
0: Speed Control
1: Torque Control
If one of the input digital terminals is set to function 35 (torque control
forbidden), speed control will be active when the terminal is active
regardless the setting of d3.00.
If one of the input digital terminals is set to function 34 (speed/torque
control switch), the actual control mode will be different with the setting of
d3.00 when the terminal is active.
d3.01
①
Range: 0 ~ 7
Default: 0
Torque reference
source
0: d3.02+UP/DOWN
1: AI1
2: AI2
3: AI3
4: X6/FI
5: Communication
6: MIN
(
AI1,AI2
)
7: MAX
(
AI1,AI2
)
When this parameter is set to 0, the torque reference can be setting
through terminal up/down adjustment function or up/down key when
C0.18 is set to 1. When this parameter is set to none 0, 100% of the
setting corresponds to the value of d3.02.
d3.02
Range: -300.0 ~ 300.0
Default: 50.0
Digital setting of
torque reference
Unit: %
Digital setting of torque reference. 100% of the setting corresponds to the
rated motor torque.
d3.03
①
Range: 0 ~ 7
Default: 0
Torque
compensation
source
0: d3.04
1: AI1
2: AI2
3: AI3
4: X6/FI
5: Communication
6: MIN
(
AI1,AI2
)
7: MAX
(
AI1,AI2
)
User can choose a suitable source as torque reference compensation
according to actual application.