CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
Group d1: Motor Parameters
d1.01
①
motor stator
resistance
Range:
0.001 ~ 65.535
(
drive power<=55kW
)
0.0001 ~ 6.5535
(
drive power >55kW
)
Default: Model dependent
Unit: Ω
asynchronous motor stator resistance.
d1.02
①
motor rotor
resistance
Range:
0.001 ~ 65.535
(
drive power <=55kW
)
0.0001 ~ 6.5535
(
drive power >55kW
)
Default: Model dependent
Unit: Ω
asynchronous motor rotor resistance..
d1.03
①
motor leakage
inductance
Range:
0.01 ~ 655.35
(
drive power <=55kW
)
0.001 ~ 65.535
(
drive power >55kW
)
Default: Model dependent
Unit: mH
asynchronous motor leakage inductance.
d1.04
①
motor mutual
inductance
Range:
0.1 ~ 6553.5
(
drive power <=55kW
)
0.01 ~ 655.35
(
drive power >55kW
)
Default: Model dependent
Unit: mH
asynchronous motor mutual inductance
d1.05
①
motor no-load
current
Range: 0.01 ~ motor rated current
(
b0.08
)(
drive power <=55kW
)
0.1 ~ b0.08
(
drive power >55kW
)
Default: Model dependent
Unit: A
asynchronous motor no-load current.
d1.06
①
Range: 0.000 ~ 1.000
Default: 0.400
Motor weaken
flux coefficient 1
The flux coefficient corresponds to 20% of flux current.
d1.07
①
Range: 0.000 ~ 1.000
Default: 0.700
Motor weaken
flux coefficient 2
The flux coefficient corresponds to 50% of flux current.
d1.08
①
Range: 0.000 ~ 1.000
Default: 1.000
Motor weaken
flux coefficient 3
The flux coefficient corresponds to 80% of flux current.
Содержание CDE500 Series
Страница 8: ......
Страница 28: ...CDE500 Vector Control AC Drive Chapter 2 Product Information 15 C01 C02 A B D H1 W H C03 ...