CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
Group C5
:
Virtual Digital Input/Output
Virtual terminals can be useful in some applications such as input terminal signal is
determined by output terminal.
User can connect the virtual outputs with virtual inputs without actual wires. The usage
method is similar with actual terminal.
C5.00
①
Range: 0~58
Default: 0
VX1 function
Same As C0.01. Refer to Tab6-C1.
C5.01
①
Range: 0~58
Default: 0
VX2 function
Same As C0.01. Refer to Tab6-C1.
C5.02
①
Range: 0~58
Default: 0
VX3 function
Same As C0.01. Refer to Tab6-C1.
C5.03
①
Range: 0~58
Default: 0
VX4 function
Same As C0.01. Refer to Tab6-C1.
C5.04
Range: 0000~4444
Default: 1111
VX active state
mode selection
This defines signal source for virtual digital input.
0: VYn
VYn=1,VXn function is active.
VYn=0, VXn function is inactive.
n = 1~4
1:
C5.05
2: AI1
3: AI2
4: AI3
Unit's digit:
VX1
Hundred's digit:
VX3
Ten's digit:
VX2
Thousand's digit:
VX4
C5.05
Range: 0000~1111
Default: 0000
Digital setting of
VX active state
When
C5.04
= 1,VX1~VX4 input status are determined by C5.05.
0: active
1: inactive
Unit's digit:
VX1
Hundred's digit:
VX3
Ten's digit:
VX2
Thousand's digit:
VX4
C5.06
①
Range: 000~111
Default: 000
Active mode for
AI as VX input
When
C5.04
select AI as the input for VX, AI level defines as high level if
AI voltage is greater than the setting of
C5.07
, AI level defines as low level
if AI voltage is less than the setting of
C5.08
.
This parameter defines the active status is high level or low level.
0: high level
1: low level
Unit's digit: AI1
Ten's digit: AI2
Hundred's digit: AI3