CDE360 Vector Control AC Drive Chapter 6 Parameters Description
L2.14
①
Range: 0~1
Default: 0
Motor 2 UVW
phase sequence
of UVW Encoder
0: Positive
1: Negative
L2.15
①
Range: 0.0~359.9
Default: 0.0
Motor 2 UVW
Encoder angle
offset
Unit: deg
The parameter is used to set the angle offset of UVW encoder for motor 2.
L2.16
①
Range: 1~65535
Default: 1
Motor 2 poles of
resolver
The parameter is used to set the poles of resolver for motor 2.
L2.17
①
Range: 0.0~10.0
Default: 0.0
Motor 2 Encoder
wire-break fault
detection time
Unit: Sec
0.0: The encoder wire-break detection function is disabled.
>0.0: The encoder wire-break detection function is enabled.
Group P0: User-defined Parameters
In user-defined parameters Group, users can add some parameters to
P0
group for
convenient view and set these parameters.
H0.05
= 1 Only display parameters that mapped by P0 group.
For example:
Set the value for P0 group parameters as below:
H0.05 = 0(Display all parameters)
P0.00 = b0.01
P0.01 = b2.01
P0.02 = L1.04
H0.05 = 1(Only display user-defined parameters)
Press Prg key return to Level 0
Press Prg key again, you can use knob on the keypad view the three
parameters as below:
b0.01
b2.01
L1.04
P0.00
Range:
A0.00
~
P1.15
Default:
A0.00
User-defined
Parameter 0
It is used to provide convenient for view and modify parameters.