Note 2:
6 Amp Relay Rating
Maximum current that can be switched reliably when connected to a ‘non-inductive load’ up to
30VDC. Electric strikes and magnetic locks are considered ‘inductive loads’. It is important to
have diode or MOV attached at the locking device to remove the EMF pulse that is generated
when switching an ‘inductive load’. It is advisable to use a 50% switch factor or 3 amps as the
maximum switching current for longer relay life. An external relay should be used on larger
voltage and current requirements
.
WEBSTER 64 SYSTEM INDICATORS
POWER LED
: ON indicates 12 volts DC is connected.
MEBR LED, MEBT LED
: For future use.
Webster Mode
:
Mode indicator: Webster 64 emits 2 beeps after powered up.
PM1 LED
: ON,
PM2 LED
: OFF
IOM LED
: Flashing RED – IOM (Input Output Module) is in normal operation.
PLM LED
:
Flashing GREEN – PLM (Panel Logic Module) is waiting for Webster to
initialize.
Steady GREEN – PLM (Panel Logic Module) Webster is up and ready.
IMPORTANT:
In some jurisdictions, the use of a UL approved power supply and
connection to the fire alarm system for emergency release may be required. Installers
should contact the local authority having jurisdiction to verify the specific
requirements. Also, a building permit may be required in some jurisdictions for the
installation of magnetic locks.
Note
:
PM1 and PM2 LED will occasionally and rapidly toggle ON and OFF when host
communication is in progress
.
Содержание Webster 64
Страница 1: ...Webster 64 Controller INSTALLATION MANUAL September 2023...
Страница 13: ...Webster 64 Page 13 of 32 Installation Manual February 2024 Rev 1 1 Figure 6 Non Supervised...
Страница 14: ...Webster 64 Page 14 of 32 Installation Manual February 2024 Rev 1 1 Figure 7 Supervised...
Страница 32: ...Webster 64 Page 32 of 32 Installation Manual February 2024 Rev 1 1...