ALX SERIES  

SPUN ALUMINUM EXHAUSTER

OPERATION INSTRUCTIONS AND PARTS MANUAL 

READ AND SAVE THESE INSTRUCTIONS

GENERAL SAFETY

1.

All electrical work must be done in accordance with all applicable electrical codes by  a  
qualified electrician. 

2.

Prior to wiring ensure the power supply is locked in the OFF position and that the motor  
nameplate voltage matches the supply voltage. 

3.

Do not install or operate this fan in an environment where combustible materials, gases or  
fumes are present. 

4. Caution:

 the fan contains rotating parts and electrical service. Appropriate safety  

precautions should be taken during installation, operation and maintenance.  
When servicing the fan motor may be hot, allow time for cooling down. 

5.

Before starting the unit, ensure the wheel rotates freely. 

6.

Check and tighten where necessary all nuts, bolts & set screws prior to fan start up (as 
some may have loosened during shipment). 

7. Please follow all applicable national, state/provincial and local codes, all of them will  

supersede this manual. 

8. Failure to follow the safety instructions in this manual may cause serious injury or  

death due to electrical shock or high speed rotating parts.

 

The purpose of this manual is to aid in the proper installation and operation of the blowers. These instructions are intended to supplement good 
general practices and are not intended to cover detailed instruction procedures. 

 

IT IS THE RESPONSIBILITY OF THE PURCHASER TO ASSURE THAT THE INSTALLATION AND MAINTENANCE OF THIS EQUIPMENT IS 

HANDLED BY QUALIFIED PERSONNEL.

 

 
Inspect all shipments carefully for damage. 

THE RECEIVER MUST NOTE ANY DAMAGE ON THE CARRIER’S BILL OF LADING AND FILE A 

CLAIM IMMEDIATELY WITH THE FREIGHT COMPANY. 

 

DO NOT LIFT THE UNIT BY THE HOOD OR MOTOR. PLEASE LIFT THE UNIT BY HORIZONTAL SUPPORTS.

 

DIMENSION & COMPONENT

ALX-M-06_27_22

Page 1 of 7

A

B

D

E

C

G

F

A

B

D

E

C

G

F

UPBLAST  

MODELS

DOWNBLAST  

MODELS

NOTE:  DUE TO MOTOR MANUFACTURERS VARIANCES IN DESIGN, 
PLEASE SEE PAGE 5 FOR MOTOR DIMENSIONAL GUIDELINES.

DOWNBLAST 

UPBLAST

Downblast Direct 

Drive Shown

Note: Belt drive units are weighted without motor & drives.

Upblast Belt  

Drive Shown 

 

Motor plate detail varies 

on different sizes

Model

A

B

C

D

E

F

G Ø

Wheel

Diameter

Roof

Opening

Net

Weight

(lbs)

ALX105-DD

18.00

25.00 19.00 2.50

1.50 3.50 0.38

10.50

15.00

33

ALX120-DD

19.00

25.00 19.00 3.50

1.50 3.50 0.38

12.25

15.00

35

ALX135-DD/DB

22.25 / 25.25 31.25 21.00 3.13

2.00 3.75 0.44

13.50

17.00

51 / 59

ALX150-DD/DB

23.13 / 26.13 31.25 21.00 3.75

2.00 3.75 0.44

15.00

17.00

56 / 65

ALX165-DD/DB

27.13 / 31.13 36.25 24.75 5.00

2.00 4.00 0.44

16.50

20.75

100 / 106

ALX180-DD/DB

27.75 / 31.75 36.25 28.00 5.50

2.00 4.00 0.44

18.25

20.75

104 / 110

ALX210-DB

36.25

43.75 33.13 5.25

2.50 4.00 0.44

21.25

29.00

176

ALX245-DB

37.00

43.75 33.13 5.88

2.50 4.00 0.44

24.50

29.00

181

Dimensions (inches)

Model

A

B

C

D

E

F

G Ø

Wheel

Diameter

Roof

Opening

Net

Weight

(lbs)

ALX105-UD

17.63

25.00 19.00 13.00 1.50 3.50 0.38

10.50

15.00

35

ALX120-UD

18.63

25.00 19.00 13.00 1.50 3.50 0.38

12.25

15.00

37

ALX135-UD/UB

22.25 / 25.25 32.13 21.00 17.13 1.50 3.75 0.44

13.50

17.00

53 / 62 

ALX150-UD/UB

23.13 / 26.13 32.13 21.00 17.13 1.50 3.75 0.44

15.00

17.00

58 / 67

ALX165-UD/UB

27.13 / 31.13 37.50 24.75 21.13 2.00 4.00 0.44

16.50

20.75

100 /108 

ALX180-UD/UB

27.75 / 31.75 37.50 28.00 21.13 2.00 4.00 0.44

18.25

20.75

108 / 116

ALX210-UB

36.25

43.75 33.13 25.50 2.50 4.00 0.44

21.25

29.00

178

ALX245-UB

37.00

43.75 33.13 25.50 2.50 4.00 0.44

24.50

29.00

183

Dimensions (inches)

!

Содержание ALX105-UD

Страница 1: ... LADING AND FILE A CLAIM IMMEDIATELY WITH THE FREIGHT COMPANY DO NOT LIFT THE UNIT BY THE HOOD OR MOTOR PLEASE LIFT THE UNIT BY HORIZONTAL SUPPORTS DIMENSION COMPONENT ALX M 06_27_22 Page 1 of 7 A B D E C G F A B D E C G F UPBLAST MODELS DOWNBLAST MODELS NOTE DUE TO MOTOR MANUFACTURERS VARIANCES IN DESIGN PLEASE SEE PAGE 5 FOR MOTOR DIMENSIONAL GUIDELINES DOWNBLAST UPBLAST Downblast Direct Drive S...

Страница 2: ... from full RPM to the RPM just set The lowest minimum voltage that may be applied to the motors is 65VAC Running at lower voltage can cause premature failure to the motor For 3 phase motors a variable frequency drive VFD is required to adjust motor speed VARIABLE SPEED CONTROL SINGLE PHASE VARIABLE FREQUENCY DRIVE THREE PHASE INSTALLATION RECOMMENDED ROOF OPENING WIRED TO POWER BY OTHERS ROOF DECK...

Страница 3: ...odel The control module features a 4 digit LED display that indicates demand of full speed and motor speed in rpm The display also indicates an error code message for minor diagnostics if required Motor speed can be changed by adjusting the speed control pot located on the control module A small screwdriver can be used to make the speed adjustment ALX SERIES SPUN ALUMINUM EXHAUSTERS ALX M 06_27_22...

Страница 4: ...s can be used in the system RESTAURANT EXHAUST APPLICATION 1 Lock out all power sources 2 Inspect all fasteners and set screws and tighten as required 3 Inspect belt alignment and tension where applicable 4 Confirm power source voltage and motor voltage are the same and that the motor is wired correctly 5 Rotate the wheel to ensure that neither the fan blade nor the belts come into contact with th...

Страница 5: ...lippage which will burn out belts Proper belt deflection should be 1 64 half way between sheave centers for each inch of belt span when a force of approximately 5 lbs is applied 6 The belt alignment should be checked to be sure that the belt is running perpendicular to the rotating shafts Motor and drive shafts must be parallel 7 A periodic inspection of all fasteners should be carried out to ensu...

Страница 6: ...7 NO 5 5 ALX180UB DB 48 56 143 145 8 5 8 13 7 NO 5 5 ALX210UB DB 56 143 145 182 184 11 5 11 12 8 YES 8 ALX245UB DB 56 143 145 182 184 11 5 11 12 8 YES 8 FAN MAX A MAX B MAX C C FACE ONLY ALX105 120UD 14 14 8 5 56 FRAME ALX105 120DD 10 10 7 5 56 FRAME ALX135 150UD 15 15 15 56 FRAME ALX135 150DD 15 15 15 56 FRAME ALX165UD 16 16 15 5 56 FRAME ALX165DD 16 16 15 5 56 FRAME 1 HP ADAPTER PLATE 48 OR 56 F...

Страница 7: ...ary according to size ALX M 06_27_22 Page 7 of 7 Canarm Ltd Corporate Head Office 2157 Parkedale Avenue PO Box 367 Brockville Ontario Canada K6V 5V6 Tel 613 342 5424 Fax 613 342 8437 www canarm com hvacsales canarm ca WARRANTY CANARM Ltd warrants every new fan to be free of defects in material and workmanship to the extent that within a period of one year from the date of purchase CANARM Ltd shall...

Страница 8: ...T FAIRE UNE RÉCLAMATION AU TRANSPORTEUR IMMÉDIATEMENT NE SOULEVEZ PAS L ÉQUIPEMENT PAR LE CAPOT OU LE MOTEUR SOULEVEZ L UNITÉ PAR LES SUPPORTS HORIZONTAUX DIMENSIONS ET PIÈCES ALX M FR 06_27_22 Page 1 de 7 MODÈLE À DÉBIT VERS LE HAUT MODÈLE À DÉBIT VERS LE BAS MODÈLE À DÉBIT VERS LE HAUT MODÈLE À DÉBIT VERS LE BAS Modèle A B C D E F G Ø Diamètre de la roue Ouverture Toit Poids Net LBS ALX105 UD 17...

Страница 9: ...er un défaillance prématurée du moteur Pour un moteur 3 phases un entraînement à fréquence varaible VFD est requis pour ajuster la vitesse du moteur CONTRÔLE DE VITESSE VARIABLE UNE PHASE ENTRAÎNEMENT À FRÉQUENCE VARIABLE TROIS PHASES 1 Posez le rebord le scellant et la membrane pour assurer l étanchéité 2 Tournez la roue du souffleur à la main La roue ne doit pas frotter contre le boîtier Si il y...

Страница 10: ...ire La vitesse du moteur peut être changée en ajustant le pot de contrôle de la vitesse situé sur le module de contrôle Un petit tournevis peut être utilisé pour faire cet ajustement Contrôle de la Vitesse de Moteur EC Contrôlé électroniquement N B Les moteurs EC ont un démarrage progressif À la mise sous tension le module de commande recueille les informations sur le moteur puis commence le proce...

Страница 11: ... attaches sont serrées et que la tension des courries sont adéquate et bien alignées DÉMARRAGE INSTALLATION DE L ÉVACUATEUR DE RESTAURANT UL762 À DÉBIT VERS LE HAUT INSTALLATION DE L ÉVACUATEUR MURAL DE RESTAURANT À DÉBIT VERS LE HAUT OUVERTURE DU TOIT RECOMMANDÉE OUVERTURE DU TOIT RECOMMANDÉE CONDUIT SOUDÉ PAR AUTRUI CONDUIT SOUDÉ PAR AUTRUI REBORD VENTILÉ MINIMUM DE 20 DE LA CIME DU TOIT CÂBLÉ P...

Страница 12: ... qui pourraient endommager la courroie 5 La tension adéquate de la courroie est importante Trop serrée cause une pression excessive sur les roulement à billes qui pourrait résulter en une surcharge du moteur Une courroie trop lâche résulte en un glissement de la courroie qui la brûlera La déflection adéquate de la courroie est à 1 64 à demi distance des centres de poulie par pouce de longueur de c...

Страница 13: ... 5 8 13 7 NO 5 5 ALX210UB DB 56 143 145 182 184 11 5 11 12 8 YES 8 ALX245UB DB 56 143 145 182 184 11 5 11 12 8 YES 8 VENTILATEUR MAX A MAX B MAX C C FACE SEULEMENT ALX105 120UD 14 14 8 5 56 FRAME ALX105 120DD 10 10 7 5 56 FRAME ALX135 150UD 15 15 15 56 FRAME ALX135 150DD 15 15 15 56 FRAME ALX165UD 16 16 15 5 56 FRAME ALX165DD 16 16 15 5 56 FRAME 1 HP ADAPTER PLATE 48 OR 56 FRAME BOTH SIDES 48 56 1...

Страница 14: ...on inadéquate et non conforme aux instructions AVIS Aucune réclamation ne sera honorée par Canarm sans autorisation obtenue au préalable 1 1 1 2 3 4 4 6 5 7 8 9 4 1 2 12 4 0 1 1 3 1 ÉVACUATEUR DE LA SÉRIE ALX EN ALUMINIUM REPOUSSÉ À DÉBIT VERS LE HAUT VUE DÉTAILLÉE ITEM DESCRIPTION QTÉ 1 CAPUCHON DU HAUT 1 2 ENVELOPPE DU MOTEUR 1 3 PLAQUE SOUTIEN DE MOTEUR 1 4 ÉLIMINATEUR DE VIBRATION 4 5 PLAQUE D...

Отзывы: