5 Unpackaging and Inspection
5 / 32
5 Unpackaging and Inspection
Before unpacking the inverter, check the package appearance thoroughly, such as for holes and cracks, and check the
inverter model accordingly. If you discover any damage to the packaging which indicates the inverter may have been
damaged, or the inverter model is not the one you requested, do not unpack the product and contact the local dealer
immediately.
After opening the package, check all of the accessories carefully in the carton. If any damage is found or any
component is missing, contact your local installer.
Note: For details information about the components, see the packing list document in the packing case.
6 Installation
6.1 Basic Installation Requirements
1) Do not install the inverter on the structures constructed of flammable, thermolabile or explosive materials.
2) The installation surface must be strong enough to bear the inverter's weight for a long period time. (Please check
the inverter’s weight in the product specification of Appendix B).
3) The inverter is protected to IP65, can be installed indoors and outdoors.
4) The humidity of the installation location should be below 100% without condensation.
5) The ambient temperature should be between -25°C to 60°C.
6) Install at eye-level for easy operation.
7) Do not install the inverter near television antenna or any other antennas and antenna cables.
8) Ensure the inverter is out of children's reach.
9) Install inverter at the locations with some cover or protection, to ensure the optimum operation.
FIG.6-1 Inverter Installation Positions FIG.6-2 Forbid to Install in Small Closed Cabinet
10) Do not install in small closed cabinet where air cannot circulate freely. Do not put any other objects on the
inverter, as per FIG.6-2.
11) Comply with the Min. clearance to walls, other inverters, or objects to ensure the installation and maintenance,
meanwhile for the good heat dissipation.
FIG.6-3 Installation Clearance Requirement
Direction
Min. clearance (cm)
Above
50
Below
50
Sides
30
Front
30