background image

 

 

www.canadiansolar.com       

Rev IM/GN-CM-EN/1.0          Copyright© October, 2020 Canadian Solar Inc.        8

 

5.2      GROUNDING 

 

For  grounding requirements  in North  America,  a module with exposed  conductive parts  is  considered  to 
comply  with  UL  61730  only  when  it  is  electrically  grounded  in  accordance  with  both  the  instructions 
presented  below  and  the  requirements  of  the  National Electrical  Code.  Any  grounding  means  used  with 
Canadian Solar Inc. modules should be NRTL certified to UL 467 and UL 2703 standards. Please consult our 
technical service team for the formal approval process. 

 

For  grounding  requirements  in  other  areas,  although  the  modules  are  certified  to  Safety  Class  II,  we 
recommend  them  to  be  grounded  and  that  module  installation  should  comply  with  all  applicable  local 
electrical  codes  and  regulations.  Grounding  connections  should  be  installed  by  a  qualified  electrician. 
Connect module frames together using adequate grounding cables: we recommend using 4-14 mm² (AWG 
6-12) copper wire. Holes provided for this purpose are identified with a grounding symbol 

(IEC61730-1). 

All conductive connection junctions must be firmly fixed. 

 

Do not drill any extra ground holes for convenience this will void the modules warranty. 

 

All bolts, nuts, flat washers, lock washers and other relevant hardware should be made of stainless steel, 
unless otherwise specified.   

 

Canadian Solar Inc. does not provide grounding hardware. 

 

One grounding method is recommended for Canadian Solar Inc. classic modules, as described below. For 
alternative  grounding  methods,  please  refer  to  Annex  B  (Alternative  Grounding  Methods)  of  this 
installation manual. It may not be possible to use standard grounding methods for certain module ranges. 
Please refer to Annex B for more details. 
 

Grounding Method: Bolt + Toothed Nut + Cup washer. 

 

 

A grounding kit containing an M5 (

3/16"

) SS cap bolt, an M5 (

3/16"

) SS flat washer, an M5 (

3/16"

) SS cup 

washer,  and  an  M5  (

3/16"

)  SS  nut  (with  teeth)  is  used  to  attach  copper  grounding  wire  to  a  pre-drilled 

grounding hole on the frame (see image above).   

 

Place  the  wire  between  the  flat  washer  and  the  cup  washer.  Ensure

 

that  the  cup  washer  is  positioned 

between the frame and

 

the wire with the concave side up to prevent galvanic corrosion. Tighten the bolt 

securely  using  the  SS  toothed  nut.  A  wrench  may  be  used  to  do  this.  The  tightening  torque  is  3-7  Nm 
(2.2-5.2 ft-lbs). 
 

6.0    MOUNTING INSTRUCTIONS 

The applicable regulations pertaining to work safety, accident prevention and 
securing the construction site must be observed. Workers and third party 
personnel shall wear or install fall arrest equipment. Any third party need to 
be protected against injuries and damages. 

 

1.

 

To  fix  the  wire  between 

the  flat  washer  and  cup 

washer,  place  the  cup 

washer  (concave  side  up) 

between  the  frame  and 

the wire. 

2.  Then  tighten  the  bolt 

using the toothed nut. 

Содержание CS5AH-180M

Страница 1: ...ABILITY 1 2 0 SAFETY PRECAUTIONS 1 3 0 MECHANICAL ELECTRICAL SPECIFICATIONS 2 4 0 UNPACKING AND STORAGE 4 5 0 MODULE INSTALLATION 4 5 1 MODULE WIRING 7 5 2 GROUNDING 8 6 0 MOUNTING INSTRUCTIONS 8 6 1...

Страница 2: ...nguage versions of this document the English version shall prevail Please refer to our product lists and documents published on our website at http www canadiansolar com as these lists are updated on...

Страница 3: ...e junction box cover closed at all times Do not disassemble a module or remove any module part Do not artificially concentrate sunlight on a module Do not connect or disconnect modules when current fr...

Страница 4: ...circuit voltage can be calculated using the following formula CVoc 1 Voc 25 T T is the lowest expected ambient temperature at the system installation site Voc C is the voltage temperature coefficient...

Страница 5: ...n to avoid module backsheets being damaged by sharp objects as scratches may directly affect product safety Do not leave modules unsupported or unsecured Do not change the wiring of bypass diodes Keep...

Страница 6: ...Temperature and humidity Please consult the Canadian Solar Inc technical support department for more information on the use of modules in special climates such as an altitude greater than 2000m Do no...

Страница 7: ...en designing the system The recommended maximum series fuse rating is stated in a table in the Annex C Modules should be safely fixed to bear all expected loads including wind and snow loads A minimum...

Страница 8: ...erproof when unmated When installing modules connector should be connected to each other as soon as possible or appropriate measures like using connector endcaps should be taken to avoid moisture and...

Страница 9: ...less steel unless otherwise specified Canadian Solar Inc does not provide grounding hardware One grounding method is recommended for Canadian Solar Inc classic modules as described below For alternati...

Страница 10: ...modules can be installed in either landscape or portrait orientations Refer to the detailed instructions for further guidance Please note that in areas with heavy snowfall 2400 Pa further countermeas...

Страница 11: ...de using four standard mounting holes Mounting rails run perpendicularly to the long frame side An additional support bar should be placed below the module as shown below Maximum Load Uplift load 2400...

Страница 12: ...oad 2400 Pa Downforce load 5400 Pa Compatible module types CS6XH P and CS6XH M 7 0 MAINTENANCE Do not make modifications to any component of the PV module diode junction box plug connectors or others...

Страница 13: ...nadiansolar com Rev IM GN CM EN 1 0 Copyright October 2020 Canadian Solar Inc 12 performed by qualified personnel only Please refer to Annex D Module Cleaning Guide for additional information on this...

Страница 14: ...as described below All the requirements of the standard module installation manual and specific tracker detailed installation instructions should apply Tracker 1P Clamping method Overlap support lengt...

Страница 15: ...10 41 6 5 07 49 4 5 38 15 CS5PH 235P 235 50 8 4 63 62 6 4 93 15 1602 1061 40 1602 1061 35 20 30 CS5PH 240P 240 51 0 4 71 62 8 5 00 15 CS5PH 245P 245 51 4 4 79 63 0 5 07 15 CS5PH 250P 250 51 4 4 87 63...

Страница 16: ...290 30 6 9 48 36 9 10 08 20 CS6PH 295M 295 30 9 9 55 37 1 10 14 20 CS6PH 300M 300 31 2 9 62 37 3 10 19 20 CS6PH 305M 305 31 5 9 69 37 5 10 25 20 CS6PH 310M 310 31 8 9 75 37 7 10 31 20 CS6XH 345M 345...

Страница 17: ...t in injury Ensure that the array has been disconnected to other active components such as inverter or combiner boxes before starting with the cleaning Wear suitable protection clothes insulated glove...

Страница 18: ...be applied as long as the method is efficient enough considering the existing conditions Method B Wet cleaning If excessive soiling is present on the module surface a non conductive brush sponge or o...

Отзывы: