background image

 

 

52 

 

DynaMax HS is setup to allow outdoor combustion air to be 
connected  directly  to  the  appliance.  It  is  highly 
recommended that combustion air be connected directly to 
the appliance. For installations in a common boiler room with 
atmospheric  appliances  or  if  there  is  the  possibility  of 
negative  pressure  in  the  boiler  room,  the  air  inlet  must  be 
piped directly to the DynaMax HS. 

9.10 

GAS VALVE VOLTAGE 

This  appliance  uses  a  transformer  to  supply  a  24  volt 
signal  to  the  Honeywell  SOLA.  The  voltage  on  the 
secondary side should be 24 to 28VAC when measured 
with a voltmeter. A secondary voltage of 21VAC or less 
supplied to 24VAC components may cause operational 
problems. 

 

9.11 

COMBUSTIBLE MATERIALS 

CAUTION 

Keep appliance clear from combustible materials; do not 
store 

GASOLINE

 and other flammable vapors and liquids 

in the proximity of the appliance. 

9.12 

FREEZE PROTECTION FOR INDOOR & 
OUTDOOR INSTALLATIONS 

Installations  are  not  recommended  in  areas  where  the 
danger of freezing exists. Proper freeze protection must be 
provided  for  appliances  installed  outdoors,  in  unheated 
mechanical  rooms  or  where  temperatures  may  drop  to  the 
freezing point or lower. If freeze protection is not provided for 
the  system,  a  low  ambient  temperature  alarm  is 
recommended  for  the  mechanical  room.  Damage  to  the 
appliance by freezing is non-warrantable.  

 

Location 

- Heating boilers, hot water supply boilers or 

water  heaters  must  be  located  in  a  room  having  a 
temperature of at least 40ºF (5ºC). 

 

Caution 

-  A  mechanical  room  operating  under  a 

negative  pressure  may  experience  a  downdraft  in  the 
flue of an appliance that is not firing. The cold outside 
air  may  be  pulled  down  the  flue  and  causing  a  frozen 
heat  exchanger.  This  condition  must  be  corrected  to 
provide adequate freeze protection.  

 

Freeze protection for the appliance using an indirect coil 
can  be  provided  by  using  hydronic  system  antifreeze. 
Follow  the  manufacturer’s  instructions. 

DO  NOT 

use 

undiluted or automotive type antifreeze.  

 

Shut-down and draining

 - If for any reason, the unit is 

to be shut off in a space where danger of freezing exists, 
the following precautionary measures must be taken:  

o

  Shut off gas supply. 

o

  Shut off water supply. 

o

  Shut off electrical supply. 

o

  Drain  the  main  exchanger  and  the  brazed  plate 

heat exchanger, if supplied, completely. 

o

  Ensure  that  the  pump  and  connecting  piping  are 

fully drained. 
 

9.13 

FREEZE PROTECTION FOR A HEATING 
BOILER SYSTEM (Optional) 

 

Use  only  properly  diluted  inhibited  glycol  antifreeze 
designed  for  hydronic  systems.  Camus®  recommends 

using a 30/70 mixture of glycol antifreeze to water. 

DO 

NOT

 exceed a mixture of 50/50. 

 

Follow 

the 

instructions 

from 

the 

antifreeze 

manufacturer.  Quantity  of antifreeze  required is  based 
on  total  system  volume  including  expansion  tank 
volume.  

 

Antifreeze  is  denser  than  water  and  changes  the 
viscosity  of  the  system.  The  addition  of  antifreeze 
will  decrease  heat  transfer  and  increase  frictional 
loss  in  the  boiler  and  related  piping. 

Where 

antifreeze  has  been  used,  to  maintain  the 
temperature rise across the appliance confirm that 
the  recommended  GPM  for  pure  water  has  been 
increased by 15% and the head loss by 20%. 

 

Local  codes  require  a  back  flow  preventer  or  actual 
disconnect  from  city  water  supply  when  antifreeze  is 
added to the system. 

 

Always  follow  the  chemical 

manufacturer’s  directions 

when filling or topping-up the system with water mixed 
with  antifreeze.  This  will  prevent  any  possible  reaction 
of the water with antifreeze which can create sludge. 

 
 

PART 10  INSTALLATIONS 

WARNING 

Before starting the boiler, smell near the floor and around 
the  boiler  for  any  gas  odours  or  any  unusual  odour. 
Remove the stainless steel jacket and smell the interior of 
the boiler. If there is any sign of a gas leak, do not proceed 
with startup. Repair all the leaks before attempting to start 
the boiler. 

 

WARNING 

Propane boilers ONLY 

– Your local propane supplier adds 

an  odorant to the  propane  gas  to  allow  for  propane gas 
leak  detection.  In  some  cases,  the  added  odorant  can 
fade and the gas may not give off any noticeable odour. 
Before startup have the local propane supplier check for 
the correct odorant level in the gas. 

10.1 

CHECKING THE INSTALLATION 

 

Inspect the connections for water, gas and electricity. 

 

Inlet  gas  pressure  must  be  a  minimum  of  3”  W.C.  for 
natural gas and 11” W.C. for propane. 

 

With the boiler off, open the main gas supply valve and 
vent the trapped air from the piping leading to the boiler. 
Confirm that all gas connections to the heater are tight 
and that there are no missing test plugs. 

Refer to Section 8.1 Setting the Correct Combustion of the 
manual  for  recommendations  on  setting  combustion 
characteristics 

10.2 

CHECKING THE CONSTRUCTION 

 

Check  the  boiler  wiring  to  see  that  it  agrees  with  the 
wiring diagram supplied. 

 

Confirm that all terminal strips and field connections are 
identified. 

 

Confirm that the DynaMax HS Controller control is set in 
the proper mode. In remote mode an external controller 
determines the set point and the stage contacts on the 

Содержание DynaMax DMH201

Страница 1: ...to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If yo...

Страница 2: ......

Страница 3: ...CHECKING GAS SUPPLY PRESSURE 16 3 5 HIGH and LOW GAS PRESSURE SWITCHES Optional 17 3 6 AIR GAS RATIO VALVE 17 3 7 BURNER 17 PART 4 WATER CONNECTION 18 4 1 FREEZE PROTECTION OUTDOOR INSTALLATION 18 4...

Страница 4: ...OLTAGE 52 9 11 COMBUSTIBLE MATERIALS 52 9 12 FREEZE PROTECTION FOR INDOOR OUTDOOR INSTALLATIONS 52 9 13 FREEZE PROTECTION FOR A HEATING BOILER SYSTEM Optional 52 PART 10 INSTALLATIONS 52 10 1 CHECKING...

Страница 5: ...e appliance 1 5 SEQUENCE OF OPERATION 1 Power switch is placed in the ON position 2 Minimum 120 VAC 60Hz single phase 15A circuit is supplied to the DynaMax HS field connection board 3 24Vac power is...

Страница 6: ...ade These shall be carefully followed in all cases Authorities having jurisdiction shall be consulted before installations are made In the absence of such requirements the installation shall conform t...

Страница 7: ...Never use a pressure washer or compressed air to clean the burner 4 Reinstall parts removed in steps 2 and 3 Be sure that vent pipe has proper pitch and is properly sealed Replace any damaged gasket o...

Страница 8: ...tection afforded by the shelter will help to minimize nuisance problems with electrical connections and will allow easier servicing of the appliance under severe weather conditions 1 11 CLEARANCE FROM...

Страница 9: ...23 1 2 19 3 3 2 1 1 4 1 2 Maintain minimum specified clearances for adequate operation All installations must allow sufficient space for servicing the vent connections water pipe connections circulat...

Страница 10: ...14 1 4 23 24 1 4 34 1 4 32 3 3 2 4 1 1 4 1 2 299 47 1 8 34 7 8 14 23 29 7 8 33 7 8 32 4 3 3 5 1 1 4 3 4 399 47 1 8 34 7 8 14 23 29 7 8 33 7 8 32 4 3 3 5 1 1 2 1 500 47 1 8 34 7 8 14 23 29 7 8 33 7 8...

Страница 11: ...7 Figure 5 DynaMax HS Wall Hung Service Clearances Figure 6 DynaMax HS Floor Mount Service Clearances...

Страница 12: ...ces vented by natural draft shall not be connected into any portion of a mechanical draft system operating under positive pressure A UL listed concentric vent air intake kit may be used with the DynaM...

Страница 13: ...minimize external sweating The following air intake options shall be utilized Outside air sealed direct vertical or horizontal Outside air ducted to jacket flange Indoor Air NOTE For wall hung units t...

Страница 14: ...ilding to minimize external sweating The following air intake options shall be utilized Outside air sealed direct vertical or horizontal Outside air ducted to jacket flange Indoor Air NOTE Sealed comb...

Страница 15: ...be located a minimum of 12 inches 0 30m away from the flue gas termination but never above 3 Air piping must terminate in a down turned elbow to avoid recirculation of flue products into the inlet ai...

Страница 16: ...other equipment In all cases local codes take precedence 6 Position the air inlet and vent terminations so they are not likely to be damaged by foreign objects or exposed to build up of debris 7 Perfo...

Страница 17: ...ing system Under these circumstances an engineered air supply is necessary If the appliance is to be installed near a corrosive or potentially corrosive air supply the appliance must be isolated from...

Страница 18: ...ssembly 3 ft 91 cm within a height of 15 ft 4 6 m above the meter regulator assembly I Clearance to service regulator vent outlet 3 ft 91 cm J Clearance to non mechanical air supply inlet to building...

Страница 19: ...1 cm within a height of 15 ft 4 6 m above the meter regulator assembly I Clearance to service regulator vent outlet 3 ft 91 cm J Clearance to non mechanical air supply inlet to building or the combust...

Страница 20: ...op and must never be smaller than the size of the connection on the appliance Sizing based on Table 8 is recommended depending on model Before operating the appliance the complete gas train and all co...

Страница 21: ...for the gas combustion process The valve is a 1 1 negative pressure gas valve The valve performs the functions of a pressure regulator safety shutoff and air gas ratio control Full closing of the val...

Страница 22: ...ty codes before proceeding If the appliance is installed above radiation level it must be provided with a low water cut off device at the time of appliance installation available from Camus Some local...

Страница 23: ...r damage Table 10 Minimal System Pipe Size Input BTU hr Water Size NPT in 199 000 1 1 4 250 000 1 1 4 299 000 1 1 2 399 000 2 500 000 2 600 000 2 700 000 2 800 000 2 4 5 HEAT EXCHANGER This appliance...

Страница 24: ...7 299 000 18 9 9 3 16 2 7 0 399 000 25 2 8 4 21 6 6 3 500 000 31 5 9 2 27 0 6 9 600 000 38 8 17 5 32 0 11 8 700 000 45 3 18 2 40 0 14 4 800 000 51 8 23 5 43 0 16 0 Table 12 Flow and Pressure Drop at...

Страница 25: ...t When testing the operation of the flow proving device always ensure that 115Vac is being supplied to the pump 4 9 WATER FLOW SWITCH Floor mount hydronic and DHW models only A paddle style water flow...

Страница 26: ...he end user the DHW tuning valve is designed to act as a maximum flow controller The tuning valve is designed to provide the correct amount of hot water for each particular DynaMax HS model and applic...

Страница 27: ...Valve Interlock J6 Safety Annunciation Alarm LCI J8 24VAC Power Inlet Outlet Sensor J9 DHW Stack Sensor 5 3 1 SERVICE PARTS The DynaMax HS Controller is not repairable Any modification or repairs will...

Страница 28: ...e upper stainless steel jacket and the lower black sheetmetal jacket which are each held on by two 2 screws On a DynaMax HS Floor Mount boiler the DynaMax HS Controller can be accessed by carefully li...

Страница 29: ...configurable parameters Delta T Outlet and Inlet water temperature differential o F LL Operating Temp Indicates temperature at modulation sensor if equipped Default S5 system sensor LL system setpoint...

Страница 30: ...tion Figure 26 Temperature screen Intermittent Pump Electrical Connection Terminals 7 and 8 115Vac relay coil Terminals 4 and 6 Normally open contacts Pump Delay Relay Constant Pump Operation Electric...

Страница 31: ...int Modulates on boiler inlet sensor default Heat demand is generated when Remote Operator is closed 1 Place both toggle switches to LOCAL 2 Press and select Login 3 Select Quick Start 4 Select CH Set...

Страница 32: ...switches to LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select CH Config 5 Select Outdoor Reset Config 6 Select Outdoor Reset and Press and select Enable 7 Set Max outdoor temp Warm weath...

Страница 33: ...nsor to J3 ECOM connector 4 Place both toggle switches in LOCAL 5 Press and select Login 6 Select Advanced Setup 7 Select CH Config 8 Select Outdoor Reset Config 9 Select Outdoor Reset and Press and s...

Страница 34: ...present 1 Place both toggle switches in LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select CH Config 5 Select Modulation rate source 4 20mA and burner on off 6 Place right hand toggle swi...

Страница 35: ...ration 5 Select Demand switch DHW switch and Press 6 Select Mod sensor Inlet and Press go to step 7 DHW Sensor operation 5 Select Demand switch Sensor only and Press 6 Select Mod sensor DHW and Press...

Страница 36: ...t Heat demand is generated when Remote Operator is closed DHW Sensor if required 1 Place both toggle switches in LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select DHW Config 5 Select Dem...

Страница 37: ...s address 1 8 Select CH Config twice 9 Select Modulation Sensor S5 10 Select Lead Lag Config 11 Select Lead Lag Master Config 12 Select Master enable Enable Fixed Setpoint operation 13 Select Setpoint...

Страница 38: ...ches in LOCAL 2 Press and select Login 3 Select Advanced Setup 4 Select System 5 Select System ID Access 6 Select MB1 Modbus address 2 To be in sequential order 7 Select MB2 Modbus address 2 To be in...

Страница 39: ...ess 6 Select S5 and Press Master Boiler 7 Place both toggle switches in LOCAL 8 Press and select Login 9 Select Advanced Setup 10 Select Lead Lag Config 11 Select Lead Lag Outdoor Reset 12 Select Outd...

Страница 40: ...stage delay 2 minutes a lag boiler will be brought online and will also fire at the base load rate specified Modulation of boilers will only occur after all boilers in the Lead Lag system are firing a...

Страница 41: ...3oC Add stage inter stage delay 722 0 64800 seconds Default 120 seconds Drop stage threshold 727 0 130oC Default 5oF 3oC Drop stage inter stage delay 731 0 64800 seconds Default 120 seconds Lead rotat...

Страница 42: ...800 Auxiliary Pump Options 2 754 16385 Ignition Parameters Preferred Lightoff Rate 666 3000 Fahrenheit o F Celcius o C Enter Into Display 20 28 9 289 10 23 3 233 0 17 8 178 10 12 2 122 20 6 7 67 30 1...

Страница 43: ...tches in LOCAL 2 Press and select Login 3 Select Quick Start 4 Select Adjustable Stack limit and enter desired stack limit rate using 5 way control and press Adjust outlet high limit Description Progr...

Страница 44: ...AL 2 Press and select Display Setup 3 Select Line that needs to be changed and press View burner run time pump cycles Description Programming Instructions To view burner run time pump cycles for maint...

Страница 45: ...out For proper operation minimum 0 8Vdc must be fed back to the module Oxide deposit on the sensor rod must be removed with steel wool DO NOT use sand paper or grit cloth since this will contaminate t...

Страница 46: ...from the system Verify that wiring is correct Flame Failure Pressing the manual OK button on the DynaMax HS Control Panel to restart the ignition sequence The boiler has failed to ignite the burner af...

Страница 47: ...rocedure Clean or replace the burner if required Air in the piping system Purge all air from the piping system Incorrect igniter gap Check that spark gap is 9 64 Auto Reset High Limit Trips The outlet...

Страница 48: ...e wired correctly Measure the resistance of the sensors 10k sensors Replace the sensor if necessary Fan Not Turning Fan refuses to rotate Alert 122 123 128 129 130 131 132 Check fan power wires Fan si...

Страница 49: ...urner switch turned OFF 30 Burner switch turned ON 47 Flame rod to ground leakage 49 Abnormal 24Vac voltage 50 Modulation Fault 61 Anti short Cycle 62 Fan speed not proved 67 Interlock Off safety circ...

Страница 50: ...turn at a time NO Verify gas valve is being powered by ignition control Check ignition speed is between 2500 to 3000 RPM using System Monitor NO Adjust ignition speed to 3000 RPM YES YES Burner light...

Страница 51: ...ressure switch tripped optional To identify the safety that is open set the multimeter to Vac and measure the voltage from one contact to ground The contacts produce a 24Vac when the circuit is closed...

Страница 52: ...he circuit is closed Is pump powered NO Check pump wiring and pump delay relay YES Is there a current transformer NO Check operation of paddle style flow switch installed on outlet of DynaMax HS YES U...

Страница 53: ...an 150o F is selected and PVC venting is used the setpoint must be reduced to below 150o F to avoid nuisance flame failures If a setpoint greater than 150o F is required venting with CPVC AL29 4C 316L...

Страница 54: ...rod Is Flame sensor plug secure NO Fasten flame sensor plug securely to flame sensor wire and check for corrosion deposits at wire terminals YES Check continuity of flame sensor wire from flame sensor...

Страница 55: ...HS must be firing before proceeding DM 0200 250 260 Figure 56 Venturi Gas Valve Assembly To adjust the high fire setting 1 Press the button 2 Select Test and press 3 Select Forced Rate and press 4 Se...

Страница 56: ...r 5 minutes DM 500 800 Figure 58 DM 500 800 Gas Valve To adjust the high fire setting 1 Press the button 2 Select Test and press 3 Select Forced Rate and press 4 Select Set High Fire Locate the input...

Страница 57: ...Profile short dense and blue Normal Flame A normal flame at 100 of burner input is blue with a well defined flame and no flame lifting Yellow Tip Yellow tipping can be caused by blockage or partial ob...

Страница 58: ...ine across the floor Check neutralized pH level regularly or as required by local jurisdiction Replace neutralizer medium as required Neutralizer medium is expected to last approximately three to six...

Страница 59: ...t it was removed NOTE When the combustion air fan is removed for any reason the inlet to the burner must be covered to prevent foreign objects from falling into the burner Always look inside the burne...

Страница 60: ...BOILER SYSTEM Optional Use only properly diluted inhibited glycol antifreeze designed for hydronic systems Camus recommends using a 30 70 mixture of glycol antifreeze to water DO NOT exceed a mixture...

Страница 61: ...s to accumulate a line scale build up Lime scale buildup This will be a NON WARRANTABLE FAILURE 2 If boiler pumps are not operated when treated water is introduced a corrosion cell may be created in t...

Страница 62: ...piping between the tank and heater and the control of water velocity as explained below are important for correct operation of your hot water heater 10 9 DOMESTIC HOT WATER WITH PLATE HEAT EXCHANGER T...

Страница 63: ...following components are needed for a Lead Lag setup 1 10k System Sensor Turn off all the boilers before beginning the setup process To setup the DynaMax HS lead lag system follow the instructions Sys...

Страница 64: ...ve NOTE Recycle power on all boilers after programming is complete if lag boilers are not discovered automatically NOTE CH Setpoint or DHW Setpoint must match Setpoint located in Lead Lag Master Confi...

Страница 65: ...eader to minimize induced flow through zones 2 Separate boiler loop as shown is recommended for system piping greater than 50 equivalent feet Pressure Reducing Valve Pressure Gauge Ball Valve Air Sepa...

Страница 66: ...Valve Air Separator Expansion Tank Zone Circulator Flow Check Valve DynaMax HS Boiler Temperature Pressure Gauge Drain Union Anti scald Mixing Valve Note 1 Size main header to minimize induced flow th...

Страница 67: ...Separator Expansion Tank Zone Circulator Flow Check Valve DynaMax HS Boiler Temperature Pressure Gauge Drain Union Anti scald Mixing Valve Note 1 Size main header to minimize induced flow through zone...

Страница 68: ...60 Figure 34 Single Boiler Hydronic Heating Direct Storage Tank Zoned Piping Arrangement Cold Water In DHW Sensor Union Direct DHW Tank Anti Scald Mixing Valve Cold Water In Hot Water Out...

Страница 69: ...Flow Check Valve DynaMax HS Boiler Master M1 Temperature Pressure Gauge Drain Union DynaMax HS Boiler Slave S2 System Sensor Note 1 Size main header to minimize induced flow through zones 2 Location...

Страница 70: ...62 PART 14 EXPLODED VIEW PARTS LIST DYNAMAX HS WALL HUNG 10 May be located outside cabinet...

Страница 71: ...63 DYNAMAX HS FLOOR MOUNT 10 May be located outside cabinet...

Страница 72: ...GM20 40 154 00 X X X 4 Heat Exchanger Flange Nuts GM10 05 012 X 5 Igniter GM10 35 108 03 X X X X X X X GM10 35 161 01 X X X 6 Flame Sensor GM10 35 109 03 X X X X X X X GM10 35 162 00 X X X 7 Igniter F...

Страница 73: ...MR6100 E X X X X VCZND6100 U X VBN3EM3POX X X VBN3FP3POX X X X 18 High Limit TCL085A X TCL110A X 19 Turn Lock Wall Hung X Floor Mount X 20 Wall Mount Back Panel 14 5402 14 5402 250 X X 21 Wall Mount F...

Страница 74: ...5506 60 75 X X X 44 Side Panel Left 14 5507 20 25 X X 14 5507 X X X 14 5507 60 75 X X X 45 Front Panel Bottom 14 5508 X X X X X X X X 46 Side Panel Left Front 14 5509 20 25 X X 14 5509 X X X X X X 48...

Страница 75: ...74 Igniter Gasket GM10 25 018 X 75 Flame Sensor Gasket GM10 25 004 X 76 Burner Refractory GM10 25 098 01 X X GM10 25 107 02 X X X X X GM10 25 128 03 X X X 77 Automatic Air Vent FV 4M1 X 78 Terminal Bo...

Страница 76: ...0566 X X X X 300611 X X X Stainless to Plastic Vent Adapter FS0604PVCR X 300537 X X 10 3 Rubber Air Sleeve 1056 22 X X X X X X 1056 33 X 1056 44 X X 1056 55 X 10 4 Burner Gasket GM10 25 074 09 X X X X...

Страница 77: ...69 11 6 Front Strut 14 8037 X X Not shown in Exploded View Part Recommended spare parts...

Страница 78: ...70 PART 15 ELECTRICAL DIAGRAMS 15 1 DM 200 299 INTERNAL WIRING DIAGRAM...

Страница 79: ...71 15 2 DM 399 800 INTERNAL WIRING DIAGRAM...

Страница 80: ...72...

Страница 81: ...ough sequential Modbus addresses Connect the system sensor to the master boiler The master boiler will use the water temperature in the primary loop to control the operation of the lead lag setup If o...

Страница 82: ...lay J4 2 3 DHW Pump 1 6hp 4 24Vac or 115Vac for pump contact 5 6 3 way diverter valve 7 Boiler pump contact 10 24Vac return 12 Ground J5 1 Interlock 2 Gas Valve contact J6 1 Blocked Flue 2 Flow switch...

Страница 83: ...excluded however if caused by appliance operation at large changes exceeding 150 F between the water temperature at inlet and appliance temperature or operating at temperatures exceeding 210o F BURNE...

Страница 84: ...ing boilers as well as a supplier of specialty HVAC products Our service line is open 24 hours 7 days a week The CAMUS CERTIFIED seal assures you that Reliability Efficiency Serviceability are built i...

Отзывы: