39
Boiler Setup Programming Instructions
Adjust stack limit
Description
Programming Instructions
•
Adjust stack limit based on
vent material used
•
PVC: 149
o
F
•
CPVC: 194
0
F
•
PP, AL29-4C, Stainless steel:
230
o
F
1)
Place both toggle switches in
LOCAL
2)
Press
and select
Login
3)
Select
Quick Start
4)
Select
Adjustable Stack limit
, and enter desired stack limit rate using 5-way control and press
Adjust outlet high limit
Description
Programming Instructions
•
Adjust outlet high limit
1)
Place both toggle switches in
LOCAL
2)
Press
and select
Login
3)
Select
Quick Start
4)
Select
Adjustable high limit
, and enter desired stack limit rate using 5-way control and press