background image

 

 

   

HSEUiREG04801(R2) MANUAL

                 

Camtec Power Supplies GmbH  -  Gewerbestrasse 30  -  DE-76327  Pfinztal / Germany   

P.1/15 (03/2017.02.2) 

Tel. +49 (721) 46596 - 0  Fax +49 (721) 46596 - 77    

www.camtec-gmbh.com

   -   

[email protected]

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death) 

HSEUiREG04801 

480W Lab Power Supply DIN-Rail

 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

Features: 

 

Real time voltage programming 

 

Real time & value C/V-monitoring 

 

Reference voltage f. autonomous programming 

 

Remote Shutdown 

 

Sense control 2V per load line 

 

Power Good Relay DC-ok  

 

Quick down programming option PS  
 

 

Precise dynamics on load change 

 

Series & parallel operation N+1 

 

Natural convection 

 

Electronic Inrush Limiter 13,8Arms 

 

Up to 90% efficiency 

 

EMI/EMS EN61000-6-2,3, EN55032 class B 

 

EN61010-1, EN61010-2-201, EN62368-1 

 

Model 

Voltage Programmable 

Current Programmable 

HSEUiREG04801.018 

0 – 18Vdc 

0 – 40,0A 

HSEUiREG04801.030 

0 – 30Vdc 

0 – 24,0A 

HSEUiREG04801.050 

0 – 50Vdc 

0 – 15,0A 

HSEUiREG04801.090 

0 – 90Vdc 

0 – 8,0A 

HSEUiREG04801.130 

0 – 130Vdc 

0 – 5,5A 

HSEUiREG04801.180

 

0 – 180Vdc 

0 – 4,0A 

HSEUiREG04801.240

 

0 – 240Vdc 

0 – 3,0A 

 
 
 
 
 
 

Содержание HSEUiREG04801

Страница 1: ...e value C V monitoring Reference voltage f autonomous programming Remote Shutdown Sense control 2V per load line Power Good Relay DC ok Quick down programming option PS Precise dynamics on load change Series parallel operation N 1 Natural convection Electronic Inrush Limiter 13 8Arms Up to 90 efficiency EMI EMS EN61000 6 2 3 EN55032 class B EN61010 1 EN61010 2 201 EN62368 1 Model Voltage Programma...

Страница 2: ...embled device pass stress aging to achieve an even level and to prevent from delayed failures Our internal product engineering guidelines provide a clear target Camtec product reputation must say mount and forget Quality is never a mere promise for our team The HSEUiREG laboratory power supplies provide low noise and ripple a very quick programming and a precise setting at high load changes With a...

Страница 3: ... It is the exact and real value at the output terminals The latency signal preset to the measured value is negligible since the control circuit is constructed completely analogously Constant Voltage or Constant Current Mode CV CC The device can optionally be operated as a DC voltage source or a constant current source The operating mode is signaled via LED Reference Voltage Uref The devices featur...

Страница 4: ...d yes Base Load OCP Non required open circuit protected Load Regulation Time 1ms on load switch 10 100 Accuracy Ureg 0 5 Ireg 1 5 Umon 0 5 Imon 1 5 Uref 1 0 Temperature Control yes thermal shutdown autorecovery 70 C outside measuring point distance 50mm Hold Up Time 50ms 230Vac mains buffering at full load Inrush Current 9 8Arms 13 8Apeak 230Vac active electronic inrush protection no simple NTC MC...

Страница 5: ...ut 3 Ireg Input Current Programming Select 0 5V 0 10V 0 20mA 4 20mA 1 MΩ working resistance with Vprog 500 Ω working resistance with Iprog 4 Ireg Input 5 Umon Output Voltage Monitor Select 0 5Vdc 5mA 0 10Vdc 5mA 6 Umon Output 7 Imon Output Current Monitor Select 0 5Vdc 5mA 0 10Vdc 5mA 8 Imon Output 9 SD Input Control Signal Shutdown Switch Open Collector 10 SD Input 11 Uref Output Reference Voltag...

Страница 6: ...mbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death Monitor Outputs Monitor Connections Potentiometer Programming Programming Inputs Shutdown Power OK Relay LED Indication CV GRN Constant voltage CC YEL Constant current SD YEL Shutdown OT RED Over temperature ...

Страница 7: ...e desired set point may be very long The power supply has large built in capacitors and an enormous energy reserve A similar effect occurs by skidding input energy which is not easily removed from the power supply A PowerSink PS modul can be ordered as an option for each HSEUiREG power supply unit The PS option is used for fast down programming and the degradation of skidding energy fed The option...

Страница 8: ...ines can cause damages to the power supply unit External Shutdown SD The power supply is set to the Shutdown mode when the control input is either shorted via a relay contact a switch contact or an NPN transistor with open collector voltage drop 1V current typ 2mA If the shutdown repeals the power supply starts again Using the soft start the current and the voltage rises within continuously to the...

Страница 9: ... 2 0A 160Vdc 3 0A 480 480W Inrush Current Protection electronic The power supply unit has an electronic current limiter 230Vac 9 8Arms 13 8Apeak It is a precisely working circuit instead of a usual simple NTC solution The accuracy is 10 regardless of the operating temperature and the duty cycles interval 10s We recommend the smallest circuit breaker a characteristic B with 16A for 115Vac and with ...

Страница 10: ...lect the line length from the neutral point or from the busbar to the load as short as possible and use the maximum possible conductor cross section Up to 5 pcs HSEUiREG can be paralleled The HSEUiREG models have no internal O ring diode to operate the devices redundant N 1 We recommend using our RED00202 DIN rail redundant device Electrical Safety Factory Test Field Test Owner 90Vdc 2500Vdc Type ...

Страница 11: ...increase The following formula shows dv dt i C When an electronic current sink is used the output voltage remains constant at the set value The current sink provides a quick dynamic response Fig 1 Fig 2 Fig 3 A Power Sink see Fig 1 enables fast down programming at low load conditions or without a load For comparison see Figure 2 without and Figure 3 with PS option The PS option must be installed i...

Страница 12: ...in a failure or malfunction could result in injury or death MECHANICS ST HD Baseplate Cooling Temperature Management The temperature management of the HSEUiREG series provides a direct dissipation of the main energy losses The internal coolers of the output diodes and the power FETs connect to the back plate cooler It is possible to dissipate about 40 50 of the energy losses out of a system while ...

Страница 13: ...uired and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the HSEUiREG One can use the DIN Rail installation equiped standard with our patented 35mm DIN Rail bracket according to EN60715 It is easy to mount dismount while snaping it onto the 35mm DIN Rail no tools necessary A wallmount back plate option is availble too It is not allowed to inst...

Страница 14: ...H0 5 6 6mm H0 5 12 OR 8mm 1 0mm H1 0 6 6mm H1 0 12 GE 8mm 2 5mm H2 5 12 12mm H2 5 19D BL 14mm 4 0mm H4 0 12 12mm H4 0 20 GDR 14mm 6 0mm H6 0 20 12mm H6 0 20 SW 14mm 10 0mm H10 0 12 12mm H10 0 22 EB 15mm The length of ferrules is to be chosen depending on the rated voltage The outside diameter of the plastic collar should not be larger than the pitch P Ordering Information Ordering Codes Product Co...

Страница 15: ...eration outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things 4 Note The device must not be operated without an upstream circuit breaker CB We recommend the use of B Type 16A for 230Vac and for 115Vac It is prohibited to use the unit without PE It may be ne...

Отзывы: