NOTE:
When using the RFM18, the user-supplied mounting hardware must be capable of
withstanding the Maximum Wind Load given in
(p. 8). See Note 2 in that
section for a description of factors that affect wind load. In addition, the tower must make
use of guy wires to further increase the stability of the tower.
FIGURE 7-12. RFM18 flat roof mounting base
7.1.3 Guy anchor installation
There are two types of anchors for the tower guy wires: the UTEYE eye bolts are poured in
concrete; the UTDUK duckbill anchors are driven into the soil.
7.1.3.1 UTEYE eyebolt guy anchor
1. Dig a hole 24 inches square by 24 inches deep at each anchor location (
2. Optional — Construct a concrete form out of 2-inch x 4-inch lumber, 24 inches square
(inside dimensions) for each hole. Center the forms over the holes and level them by using
a carpenter’s level and stakes.
3. Fill the holes with concrete and install the eyebolts as shown in
UT20 and UT30 Universal Towers
21