Table 8-1: SDI-12 commands
SDI-12
command
Variable name
Description
aR5!
Read lifetime max temperature
Max. temperature – floating point (°C)
aR6!
Read and reset user resettable min
temperature
Min. temperature – floating point (°C).
This value constitutes the minimum of all
1-second measurements taken since the
previous
aR6!
command.
aR7!
Read and reset user resettable max
temperature
Max. temperature – floating point (°C).
This value constitutes the maximum of all
1-second measurements taken since the
previous
aR7!
command.
aV!
Verification command
S1 = BootRom Signature
S2 = Firmware Signature
aAb!
Change Address command
Valid addresses in sequence are:
1–9 / A–Z / a–z (no Address 0)
Sending a broadcast message with the
address change “{” can correct units that
have conflicting addresses.
aI!
SDI-12 Identification command
X13CAMPBELLCS225 1.0 SN:XXXXX
8.1.1 SDI-12 addressing
Each temperature sensor has a different default SDI-12 address. The starting addresses is 1 and
coincides with the top temperature point. The last address coincides with the bottom sensor.
If multiple SDI-12 sensors are connected to the data logger, Campbell Scientific recommends
using separate terminals when possible. However, multiple SDI-12 sensors or multiple CS225
sensors can connect to the same data logger control or U terminal if they have different SDI-12
addresses. If changing the SDI-12 addresses, Campbell Scientific recommends starting the
readdressing process with the largest temperature sensor address to avoid duplicate addresses.
(p. 13) provides the SDI-12 addresses and positions.
CS225 Temperature String
12