Section 7. Installation
216
software documentation available at
www.campbellsci.com
. Be aware of the
following precautions:
•
The CR800 does not check for out-of-bounds values in mode variables.
•
Valid mode variable entries are
1
or
4
.
Before, during, and after calibration, one of the following codes will be stored in
the
CalMode
variable:
FieldCal() Codes
Value Returned
State
-1
Error in the calibration setup
-2
Multiplier set to
0
or
NAN
; measurement =
NAN
-3
Reps
is set to a value other than
1
or the size of
MeasureVar
0
No calibration
1
Ready to calculate (
KnownVar
holds the first of a
two point calibration)
2
Working
3
First point done (only applicable for two point
calibrations)
4
Ready to calculate (
KnownVar
holds the second of a
two-point calibration)
5
Working (only applicable for two point calibrations)
6
Calibration complete
7.7.11.4.1 One-Point Calibrations (Zero or Offset)
Zero operation applies an offset of equal magnitude but opposite sign. For
example, when performing a zeroing operation on a measurement of 15.3, the
value –15.3 will be added to subsequent measurements.
Offset operation applies an offset of equal magnitude and same sign. For
example, when performing an offset operation on a measurement of 15.3, the
value 15.3 will be added to subsequent measurements.
See
FieldCal() Zero or Tare (Opt 0) Example
(p. 218)
and
FieldCal() Offset (Opt 1)
Example
(p. 220)
for demonstration programs:
1. Use a separate
FieldCal()
instruction and variables for each sensor to be
calibrated. In the CRBasic program , put the
FieldCal()
instruction
immediately below the associated measurement instruction.
2.
Set mode variable = 0 or 6 before start
ing.
3. Place the sensor into zeroing or offset condition.
Содержание CR800 Series
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 32: ......
Страница 34: ......
Страница 54: ......
Страница 92: ......
Страница 190: ...Section 7 Installation 190 FIGURE 40 Running Average Frequency Response FIGURE 41 Running Average Signal Attenuation ...
Страница 310: ......
Страница 446: ...Section 8 Operation 446 8 11 2 Data Display FIGURE 100 CR1000KD Displaying Data ...
Страница 448: ...Section 8 Operation 448 FIGURE 102 CR1000KD Real Time Custom ...
Страница 449: ...Section 8 Operation 449 8 11 2 3 Final Storage Data FIGURE 103 CR1000KD Final Storage Data ...
Страница 450: ...Section 8 Operation 450 8 11 3 Run Stop Program FIGURE 104 CR1000KD Run Stop Program ...
Страница 452: ...Section 8 Operation 452 FIGURE 106 CR1000KD File Edit ...
Страница 456: ......
Страница 462: ......
Страница 523: ...Section 11 Glossary 523 FIGURE 116 Relationships of Accuracy Precision and Resolution ...
Страница 524: ......
Страница 526: ......
Страница 556: ......
Страница 558: ......
Страница 560: ......
Страница 597: ......